Hunter PRO-C Hydrawise Software/app Owner's Manual
Read Online
Read the Hunter PRO-C Hydrawise Software/app Owner's Manual online using the built-in PDF viewer.
Key Pages of Document
Table of Contents HCC - Quick Start Guide HCC - Connecting AC Power HCC - Power Module Wiring Diagram HCC - Valve Wiring HCC - Installing ICM Station Modules HCC - Wire Distance to Valves HCC - Installing Wi-Fi Antenna Extension Kit Can Two Zones Run Simultaneously with a HCC controller? HCC - Configure Controller Off ...
HCC - Connecting AC Power Connecting the controller to primary AC power should be done by a licensed electrician following all local codes. Install in approved conduit and fittings. The controller can operate with either 120VAC or 230VAC power. Supply wires must be 14AWG/ 2 mm2 or larger. IMPORTANT: If you are using the plug-in method ...
2. Disconnect the facepack ribbon cable 3. Remove the facepack. 4. Remove the cover from the junction box. Copyright 2021 Hunter Industries. All Rights Reserved. 4 ...
2. Route the wires through the conduit opening inside the junction box. 3. Connect the incoming black power wire (HOT) with the black wire lead from the transformer. 4. Connect the incoming white wire (NEUTRAL) with the blue lead from the transformer. 5. Connect the incomi ...
1. Insert the copper wire from earth ground hardware, and tighten the screw in front. 2. Minimum 10 AWG/5mm2 wire to earth ground hardware. 3. Add copper-clad steel ground rods and/or plates sufficient to achieve 10Ω or less resistance at a minimum 8’/2.5 m away from the controller. HCC - Power Module Wiring ...
1. Route valve wires between control valve location and controller. 2. At valves, attach a common wire to either solenoid wire of all valves. The most commonly used color for the common wire is white. Attach a separate control wire to the remaining wire of each valve. All wire splice connections should be done using waterproof connectors. ...
The base model of HCC is supplied with an ICM-800 station output module. The capacity of the controller is increased when new station modules are installed and recognized. Standard ICM station modules are available in 4, 8, and 22 station sizes (ICM-400, ICM-800, ICM- 2200). These may be added at any time after initial in ...
Qty:1 - ICM-2200 STEP 1 STEP 2 STEP 3 Open the controller inner panel, and choose the next available open slot in the controller. Slots are numbered, down the first column and up the second. Flip the blue locking lever into the vertical unlocked position. Tip the two tabs on one end of the module into the mating holes in one end ...
valves. Valve Wire Sizing (Feet) Ground Control Wire 18 16 14 12 10 8 6 18 850 1040 1210 1350 1460 1540 1590 16 1040 1340 1650 1920 2150 2330 2440 14 1210 1650 2150 2630 3080 3450 3700 12 1350 1920 2630 3390 4170 4880 5400 10 1460 2150 3080 4170 5400 6670 7650 ...