Simplex 4098 Applications Manual
Text of the manual
Copyright 2000 Simplex Time Recorder Co. All rights reserved.
Printed in the United States of America.
Copyright 2000 Simplex International Time Equipment Co.,Ltd.,
Mississauga, Ontario L4V 1H3 Canada.
All specifications and other information shown were current as of
publication, and are subject to change without notice. No part of this
document
Special Considerations for Smoke Detectors and Sensors...................1
Smoke Detector/Sensor Applications ....................................................1
WHERE TO PLACE DETECTORS/SENSORS ........................................2
WHERE NOT TO PLA
The purpose of this publication is to provide information concerning the proper
application of both heat and smoke detectors and sensors in conjunction with fire
alarm systems.
The information in this publication is intended to be used only as a technical
guide. The requirements of applicable codes and standards, as well as directives
of Authorities Havin
Important: The guidelines in this section are adapted from standards published
by the National Fire Protection Association, Quincy,
Massachusetts, U. S. A. These standards include NFPA 72,
“National Fire Alarm Code”; NFPA 70, “National Electrical
Code”, Article 760; and NFPA 90A, “Standard for the Installation
of Air Conditioning and Ventilating