Trumeter 7921 Manual 

Brand: Trumeter
Category: Relays
Model: 7921 (Manual )
File Type: PDF
File Size: —
Pages: 40
Text of Trumeter 7921 Manual 

Trumeter 7921 018366-01 Issue 2 12/99

7921 6 digit programmable bi-directional counter relay, with dual preset or batch mode operation, prescaling and EEPROM data storage 6-Stelliger Bi-Direktionaler Zähler mit Supertwist-LCD mit Einzel/Doppel- und Chargen Vorwahl, Skalierung durch Vorteiler und EEPROM-Datenspeicherung Relais de compteur bidirectionnel à 6 chiffres, programmable, avec fonctionnement double en mode automatique ou discontinu, génération d'échelles et

Black on green STN LCD, with yellow/green LED

backlight. Program Storage Erase/write cycles:1,000,000 Life: 40 years min Count Range -99999 to 999999 Count Pre-scaler Multiplier 0.00250 to 9.99999 Divider 1 to 99999 External Reset response time Max 2ms Count Inputs High Speed: 10kHz max (electronic) (Dividing prescaler: 7kHz max) Duty cycle: 60:40 max Low Speed: 30Hz max (contact closure) Relay Contacts 5A resistive load 100,000 opera

Trumeter 7921 multiplying prescaler value, or the unit may not operate correctly.

The P1 preset can be set at any time. In Reset to Zero mode, the change will be accepted immediately. In Reset to P1 mode, the change will not be accepted until after a Reset. The P2 preset can be set as shown below. The change will be accepted immediately. Count Modes (see page 35) The diagrams show how the P1 and P2 Relays are controlled by the Count, by Batch Total and by Reset. The dia

Connections (see pages 37 & 38)

Inputs A and B in Unidirectional mode In the two Unidirectional modes, the count is incremented or decremented by input A, whilst the direction is dependent on input B. In Unidirectional High mode, both inputs are high speed inputs, suitable only for electronic signal sources, eg. transistors, proximity switches, encoders. In Unidirectional Low mode, both inputs are low speed inputs (30Hz max), suitable for contact closure

Relays (see page 38)

The P1 and P2 relays can be programmed independently to be normally-open or normally-closed. The contacts of a normally-closed relay will open when it operates, and those of a normally-open relay will close. The relays can be programmed independently to operate in pulsed or latched mode. In pulsed mode (P1 relay: Auto Reset Off only) the relay will operate for a length of time set by the program. In latched mode the relay will operat

If the Prescaler or the Reset Mode or the Batch Mode are changed, the new

configuration will not be fully effective until after exit from Program mode, AND THEN AFTER a Reset. Decimal Point The decimal point can be in one of three positions, or off. Prescaling A multiplying or dividing factor can be used. If a multiplying prescaler of n is used, the counter will count: 0, n, 2n, 3n etc. If a dividing prescaler of n is used, the counter will increment or

Trumeter 7921 No Decimal point

1 Decimal place 2 Decimal places 3 Decimal places Main menu Prescaling No prescaling Multiply -------- Divide ---------- Main menu P1 Relay Condition Normally open Normally closed Main menu P2 Relay Condition Normally open Normally closed Main menu P1 Relay Type Pulsed ---------- Latched* Main menu P2 Relay Type Pulsed ** ---------- Latched Main menu P1 Relay Safe State Current state Normal state Operated state Main menu P2

Die beiden Tasten auf der Frontblende dienen zum Programmieren des Zählers sowie zum

Anzeigen und Einstellen der Vorwahlwerte P1 und P2. Alle Tasten können über den Tastensperren-Eingang deaktiviert werden (siehe „Programmierung" auf S. 12). Automatische Rücksetzung (siehe 1 und 3 auf S. 35) Bei eingeschalteter automatischer Rücksetzung wird der Zähler wie folgt automatisch zurückgesetzt: Im Modus „Auf Null zurücksetzen" wird der Zähler auf �

Trumeter 7921 jeweils grösser sein als der Wert des Prescaler-Multiplikators, da das Gerät sonst nicht

ordnungsgemäss funktioniert. Die Voreinstellung P1 kann jederzeit eingestellt werden. Im Modus „Auf Null zurücksetzen" wird die Änderung sofort übernommen. Im Modus „Auf P1 zurücksetzen" wird die Änderung erst nach einem Rücksetzen übernommen. Die Voreinstellung P2 kann wie nachstehend beschrieben eingestellt werden. Die Änderung wird sofort übernommen.

Anschlüsse (siehe S. 37 und 38)

Eingänge A und B im unidirektionalen Modus In den beiden unidirektionalen Modi wird der Zählerwert durch Eingang A erhöht oder reduziert; dabei bestimmt Eingang B die Zählrichtung. Im Modus „Unidirektional hoch" fungieren beide Eingänge als Hochgeschwindigkeitseingänge, die sich nur für elektronische Signalquellen wie Transistoren, Näherungsschalter, Codierer usw. eignen. Im Modus „Unidirektional niedrig" fungie

Trumeter Relays Owners Instructions: