SMART 7KT0310 Manual Introduction
1
1.1 Purpose of this document
This present manual describes the SMART 7KT multifunction meter.
It is intended for the use of:
•� Planners�
•� Plant�operators�
•� Commissioning�engineers�
•� Service�and�maintenance�personnel�
1.2 Required basic knowledge
A�general�knowledge�of�the�field�of�electrical�engineering�is�required�to�understand�this�manual.�
Knowl
SMART 7KT0310 Manual Safety
precautions
2
Please�read�and�understand�these�instructions�before�installing,�operating,�or�maintaining�the�equipment.
DANGER
Hazardous�voltage.�Will�cause�death�or�serious�injury.�Turn�off�and�lock�out�all�power�
supply�to�this�device�before�working�on�this�device.
Replace�all�covers�before�power�supplying�this�device�is�turned�on.
All�
SMART 7KT0310 Manual Technical
specification
3
Display
Type�and�specifics
•� Large�backlit�Liquid�Crystal�display�
•� 4�Lines�with�4�digits�each�to�show�measured�values
•� 5th�Line�with�8�digits�to�show�energy�values
•� Graph�for�current�loading�indication
Size�of�display�(mm�x�mm)
60.3�mm�x�60.3�mm
LCD�Indications
I �
Integration�of�energy�
PRG�
Unit�
SMART 7KT0310 Manual Measured variables
Measured variable
On display
On communication
Voltage�V�L-N,�V�L-L
●
●
Current
●
●
Neutral�current
●
●
Frequency
●
●
Power�factor
●
●
Active�power
●
●
Reactive�power
●
●
Apparent�power
●
●
Active�energy�(Import,�Export,�Total)
●
●
Reactive�energy�(Import,�Export,�Total)
●
●
Apparent�energy
●
●
Max�demand�(current)�over�set�dem
SMART 7KT0310 Manual Assembly
4
Installation
For installing the meter
Prepare�the�panel�cutout�with�proper�dimensions�as�shown�below.
FRONT PANEL DESCRIPTION
OUTLINE
Dimensions (in mm)
PANEL CUTOUT
Dimensions (in mm)
90.5
50
96
5
96
91.5
91.5
1. Insert unit into the panel
2.� Position�the�clamps�(as�shown�in�the�
figure)�and�push�the�same�into�the�slots�
in�their�respective�locations.
3.� Push/Sl
SMART 7KT0310 Manual Installation Guidelines
1.�This�equipment,�being�built-in-type,�normally�becomes�a�part�of�main�control�panel�and�in�such�case�the�terminals�
do�not�remain�accessible�to�the�end�user�after�installation�and�internal�wiring.
2.�Conductors�must�not�come�in�contact�with�the�internal�circuitry�of�the�equipment�or�else�it�may�lead�to�a�s
SMART 7KT0310 Manual Connection
5
N
S2
S1
S2
S1
S2
S1
V1
N
L
O
A
D
I1
V2
V3
L1
L2
L3
I2
I3
DI
L
N
+
RS485
+
CONNECTIONS DIAGRAM
3 Phase 4-Wire (commonly used)
3�Ø�-�4�Wire,�3�CT’S�
3�Ø�-�4�Wire,�3�CT’S�and�3�PT’S
S2
S1
S2
S1
S2
S1
N
V2
V3
LOAD
LINE
L1
L2
L3
N
I1
I2
I3
V1
#
DI
RS485
L
N
L
N
#
+
+
+
SMART 7KT
Voltage upto 500V without PT
LINE
DI
RS485
L
N
L
N
#
LOAD
L1
L2
L3
N
#
S2
S1
S2
S1
S2
S1
N
V1
V2
V3
I1
I2
I3
SMART 7KT0310 Manual 3 Phase 3-Wire
3��-�3�Wire,�2CTs�and�2PTs
1 Phase 2-Wire
1��-�2�Wire,�1�CT
S2
S1
S2
S1
S2
S1
V1
N
V2
V3
LOAD
LINE
L1
L2
L3
I1
I2
I3
#
DI
RS485
L
N
L
N
#
+
+
SMART 7KT
S2
S1
S2
S1
S2
S1
V1
N
V2
V3
LOAD
LINE
L1
N
I1
I2
I3
#
DI
RS485
L
N
L
N
#
+
+
SMART 7KT
Circuit Diagram (Continued)
#�All�Fuse�Type:�0.5A,�Class�gG
SMART 7KT0310 Manual Configuration
6
There�are�4�dedicated�keys�labelled�as�F1,�F2,�F3,�F4.�Use�these�4�keys�to�read�meter�
parameters.�Simply�press�these�keys�to�read�the�parameters.
The�keys�have�multiple�assignments.�Function�assignments�and�key�labeling�change�
according�to�the�context�of�operator�input.�
A�short�press�on�the�key�triggers�the�func
SMART 7KT0310 Manual Parameterization with function keys
Config.
page
Function
Range or Selection
Factory
Setting
Password
0000�to�9998
1000
1
Change�Password
No�/�Yes
No
1.1
New�Password
0000�to�9998
1000
2
Network�
Selection
3P4W,�3P3W,�1P2W-P1,�
1P2W-P2�and�1P2W-P3
3P4W
3
CT�Secondary
1A�or�5A�
5
4
Ct�Primary
1A,�5A�to�10,000A
5
5
Pt�Secondary
100V�to�500V
350
6
Pt�primary
100V�to�500kV
350
7
Sl
SMART 7KT0310 Manual Reading of parameters
Key Press
Screen
number
Description
Press�F1�to�
navigate�to�each�
screen
1
Displays�line�to�neutral�voltage�of�three�phase�and�average�line�to�neutral�voltage.
2
Displays�line�to�line�voltage�of�three�phase�and�average�line�to�line�voltage.
3
Displays�total�percentage�harmonics�of�line�to�neutral�voltage�of�three�phase�and�
SMART 7KT0310 Manual Reading of parameters (Continued)
Key Press
Screen
number
Description
Press�F4�to�
navigate�to�each�
screen. The
energy�values�will�
be�visible�on�the�
5th�line�of�the�
screen
1
Displays�import�active�energy�of�first�phase.
2
Displays�import�active�energy�of�second�phase.
3
Displays�import�active�energy�of�third�phase.
4
Displays�export�active�energy�of�
SMART 7KT0310 Manual Communication
7
Protocol and interface
Protocol:�Modbus�RTU
Interface:�Integrated�RS485�interface
Communication parameters
Communication�address�
1�to�255
Transmission mode
Half�duplex
Data types
Float�and�Integer
Transmission distance
�500m�maximum
Transmission Speed
300,�600,�1200,�2400,�4800,�
9600,�19200�(in�bps)
Parity
�None,�Odd,�Even
Stop bits
1 or 2
Response Time
100ms�Max�
SMART 7KT0310 Manual Address
Hex Address
Parameter
30086
0x56�
kWh2�(Imp)�
30088
0x58�
kWh3�(Imp)�
30090�
0x5A�
kWh1�(Exp)�
30092�
0x5C�
kWh2�(Exp)�
30094�
0x5E�
kWh3�(Exp)�
30096�
0x60�
Total�kWh�(Imp)�
30098�
0x62�
Total�kWh�(Exp)�
30100
0x64�
kVArh1�(Imp)�
30102
0x66�
kVArh2�(Imp)�
30104
0x68�
kVArh3�(Imp)�
30106
0x6A�
kVArh1�(Exp)�
30108
0x6C�
kVArh2�(Exp)�
30110
0
SMART 7KT0310 Manual Address
Hex Address
Parameter
30293�
125�
17th�Harmonic�of�V3N�
30295�
127
18th�Harmonic�of�V3N�
30297�
129�
19th�Harmonic�of�V3N�
30299�
12B
20th�Harmonic�of�V3N�
30301
12D
21st�Harmonic�of�V3N�
30303
12F
22nd�Harmonic�of�V3N�
30305�
131
23rd�Harmonic�of�V3N�
30307
133
24th�Harmonic�of�V3N�
30309�
135�
25th�Harmonic�of�V3N�
30311
137