Siemens SMART 7KT Manual 

Text of Siemens SMART 7KT Manual 

SMART 7KT0310 Manual

MANUAL SMART 7KT Multifunction meter 7KT0310 SMART 7KT power monitoring devices
SMART 7KT0310 Manual 1. Introduction 3 2. Safety precautions 4 3.� Technical�specification� 5 4. Installation 7 5.� Connection� 9 6.� Configuration� 10 7.� Communication� 14 8.� Maintenance� 19 SMART 7KT Multifunction meter 7KT0310 Manual Index 01/2022 SME7KT03100122
SMART 7KT0310 Manual Introduction 1 1.1 Purpose of this document This present manual describes the SMART 7KT multifunction meter. It is intended for the use of: •� Planners� •� Plant�operators� •� Commissioning�engineers� •� Service�and�maintenance�personnel� 1.2 Required basic knowledge A�general�knowledge�of�the�field�of�electrical�engineering�is�required�to�understand�this�manual.� Knowl
SMART 7KT0310 Manual Safety precautions 2 Please�read�and�understand�these�instructions�before�installing,�operating,�or�maintaining�the�equipment. DANGER Hazardous�voltage.�Will�cause�death�or�serious�injury.�Turn�off�and�lock�out�all�power� supply�to�this�device�before�working�on�this�device. Replace�all�covers�before�power�supplying�this�device�is�turned�on. All�
SMART 7KT0310 Manual Technical specification 3 Display Type�and�specifics •� Large�backlit�Liquid�Crystal�display� •� 4�Lines�with�4�digits�each�to�show�measured�values •� 5th�Line�with�8�digits�to�show�energy�values •� Graph�for�current�loading�indication Size�of�display�(mm�x�mm) 60.3�mm�x�60.3�mm LCD�Indications I � Integration�of�energy� PRG� Unit�
SMART 7KT0310 Manual Measured variables Measured variable On display On communication Voltage�V�L-N,�V�L-L ● ● Current ● ● Neutral�current ● ● Frequency ● ● Power�factor ● ● Active�power ● ● Reactive�power ● ● Apparent�power ● ● Active�energy�(Import,�Export,�Total) ● ● Reactive�energy�(Import,�Export,�Total) ● ● Apparent�energy ● ● Max�demand�(current)�over�set�dem
SMART 7KT0310 Manual Assembly 4 Installation For installing the meter Prepare�the�panel�cutout�with�proper�dimensions�as�shown�below. FRONT PANEL DESCRIPTION OUTLINE Dimensions (in mm) PANEL CUTOUT Dimensions (in mm) 90.5 50 96 5 96 91.5 91.5 1. Insert unit into the panel 2.� Position�the�clamps�(as�shown�in�the� figure)�and�push�the�same�into�the�slots� in�their�respective�locations. 3.� Push/Sl
SMART 7KT0310 Manual Installation Guidelines 1.�This�equipment,�being�built-in-type,�normally�becomes�a�part�of�main�control�panel�and�in�such�case�the�terminals� do�not�remain�accessible�to�the�end�user�after�installation�and�internal�wiring. 2.�Conductors�must�not�come�in�contact�with�the�internal�circuitry�of�the�equipment�or�else�it�may�lead�to�a�s
SMART 7KT0310 Manual Connection 5 N S2 S1 S2 S1 S2 S1 V1 N L O A D I1 V2 V3 L1 L2 L3 I2 I3 DI L N + RS485 + CONNECTIONS DIAGRAM 3 Phase 4-Wire (commonly used) 3�Ø�-�4�Wire,�3�CT’S� 3�Ø�-�4�Wire,�3�CT’S�and�3�PT’S S2 S1 S2 S1 S2 S1 N V2 V3 LOAD LINE L1 L2 L3 N I1 I2 I3 V1 # DI RS485 L N L N # + + + SMART 7KT Voltage upto 500V without PT LINE DI RS485 L N L N # LOAD L1 L2 L3 N # S2 S1 S2 S1 S2 S1 N V1 V2 V3 I1 I2 I3
SMART 7KT0310 Manual 3 Phase 3-Wire 3��-�3�Wire,�2CTs�and�2PTs 1 Phase 2-Wire 1��-�2�Wire,�1�CT S2 S1 S2 S1 S2 S1 V1 N V2 V3 LOAD LINE L1 L2 L3 I1 I2 I3 # DI RS485 L N L N # + + SMART 7KT S2 S1 S2 S1 S2 S1 V1 N V2 V3 LOAD LINE L1 N I1 I2 I3 # DI RS485 L N L N # + + SMART 7KT Circuit Diagram (Continued) #�All�Fuse�Type:�0.5A,�Class�gG
SMART 7KT0310 Manual Configuration 6 There�are�4�dedicated�keys�labelled�as�F1,�F2,�F3,�F4.�Use�these�4�keys�to�read�meter� parameters.�Simply�press�these�keys�to�read�the�parameters. The�keys�have�multiple�assignments.�Function�assignments�and�key�labeling�change� according�to�the�context�of�operator�input.� A�short�press�on�the�key�triggers�the�func
SMART 7KT0310 Manual Parameterization with function keys Config. page Function Range or Selection Factory Setting Password 0000�to�9998 1000 1 Change�Password No�/�Yes No 1.1 New�Password 0000�to�9998 1000 2 Network� Selection 3P4W,�3P3W,�1P2W-P1,� 1P2W-P2�and�1P2W-P3 3P4W 3 CT�Secondary 1A�or�5A� 5 4 Ct�Primary 1A,�5A�to�10,000A 5 5 Pt�Secondary 100V�to�500V 350 6 Pt�primary 100V�to�500kV 350 7 Sl
SMART 7KT0310 Manual Reading of parameters Key Press Screen number Description Press�F1�to� navigate�to�each� screen 1 Displays�line�to�neutral�voltage�of�three�phase�and�average�line�to�neutral�voltage. 2 Displays�line�to�line�voltage�of�three�phase�and�average�line�to�line�voltage. 3 Displays�total�percentage�harmonics�of�line�to�neutral�voltage�of�three�phase�and�
SMART 7KT0310 Manual Reading of parameters (Continued) Key Press Screen number Description Press�F4�to� navigate�to�each� screen. The energy�values�will� be�visible�on�the� 5th�line�of�the� screen 1 Displays�import�active�energy�of�first�phase. 2 Displays�import�active�energy�of�second�phase. 3 Displays�import�active�energy�of�third�phase. 4 Displays�export�active�energy�of�
SMART 7KT0310 Manual Communication 7 Protocol and interface Protocol:�Modbus�RTU Interface:�Integrated�RS485�interface Communication parameters Communication�address� 1�to�255 Transmission mode Half�duplex Data types Float�and�Integer Transmission distance �500m�maximum Transmission Speed 300,�600,�1200,�2400,�4800,� 9600,�19200�(in�bps) Parity �None,�Odd,�Even Stop bits 1 or 2 Response Time 100ms�Max�
SMART 7KT0310 Manual Address Hex Address Parameter 30086 0x56� kWh2�(Imp)� 30088 0x58� kWh3�(Imp)� 30090� 0x5A� kWh1�(Exp)� 30092� 0x5C� kWh2�(Exp)� 30094� 0x5E� kWh3�(Exp)� 30096� 0x60� Total�kWh�(Imp)� 30098� 0x62� Total�kWh�(Exp)� 30100 0x64� kVArh1�(Imp)� 30102 0x66� kVArh2�(Imp)� 30104 0x68� kVArh3�(Imp)� 30106 0x6A� kVArh1�(Exp)� 30108 0x6C� kVArh2�(Exp)� 30110 0
SMART 7KT0310 Manual Address Hex Address Parameter 30293� 125� 17th�Harmonic�of�V3N� 30295� 127 18th�Harmonic�of�V3N� 30297� 129� 19th�Harmonic�of�V3N� 30299� 12B 20th�Harmonic�of�V3N� 30301 12D 21st�Harmonic�of�V3N� 30303 12F 22nd�Harmonic�of�V3N� 30305� 131 23rd�Harmonic�of�V3N� 30307 133 24th�Harmonic�of�V3N� 30309� 135� 25th�Harmonic�of�V3N� 30311 137 26th�Ha