Trane GRAA Installation, Operation And Maintenance Manual
Read Online
Read the Trane GRAA Installation, Operation And Maintenance Manual online using the built-in PDF viewer.
Key Pages of Document
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on th ...
Warnings, Cautions, and Notices Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. The three types of advisories are defined as follows: WARNING Indicates a potentially hazardous situation which, if not avoided, could resu ...
meenntt ((PPPPEE)) RReeqquuiirreedd!! FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheem msseellvveess ffrroom m ppootteennttiiaall eelleeccttrriiccaall,, m meecchhaanniiccaall,, aan ...
Pre-Installation Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Location . . . . . . . ...
Lighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Primary Air Shutter Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Pilot Adjustment. . . . . . . . . . . . . . . ...
crate during shipment. After the unit has been uncrated, check for any visible damage to the unit. Check motor position and turn blower wheel to determine if damage has occurred to these critical parts. If any damage is found, the cosignee should sign the bill of lading indicating such damage and immediately file claim for damag ...
W WAARRNNIINNGG HHaazzaarrddoouuss SSeerrvviiccee PPrroocceedduurreess!! FFaaiilluurree ttoo ffoollllooww aallll pprreeccaauuttiioonnss iinn tthhiiss m maannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheem msseellvveess ffrroom m ppootteennttiia ...
engages with the bottom panel. Turn the screwhead on each latch clockwise. The screw must turn freely one quarter turn before resistance is felt in order for the lock to engage. If the latch does not hold, turn the screw counter-clockwise several turns and repeat the above procedure. Also refer to Figure 8, p. 18, Figure 9, p. 18, and Figure 10 ...
4" (102) 5-1/16" (129) Electrical Connections 5/8" (16) Typ. Anchor Hole Location Vent Cap Is Shipped In Separate Carton A C (Typ.) 10-1/8" (257) B Opening Typ. 13/16" (21) Typ. Anchor Hole Location Gas Connection 8-3/4" (222) * F 1" (25) 26" Typ. (660) 31-1/4" (794) CL D 39" (991) 19" (483) Opening K 1-1/8" (29) Typ. Duct Flange Table 1. Dimensional Data US CAPACITY C ...
4" (102) 1" (25) Typ. 5-1/16" (129) Electrical Connections Anchor Hole Location 5/8" (16) Typ. A 10-1/8" (257) B Opening Typ. Anchor Hole Location 13/16" (21) Typ. Gas Connection 8-3/4" (222) * F 26" (660) 31-1/4" (794) CL 39" (991) 19" (483) Opening K 1-1/8" (29) Flange Typ. Duct Flue Product Outlet Air Inlet Combustion SSppeecciiffiiccaattiioonnss ...
F* NG LP INPUT OUTPUT Temp. Rise Min. Gas Gas Shipping Net CAPACITY RATING MIN. RATING EFF. MAX. °F Static Inlet Inlet Clearance Weight Weight MBH BTU/Hr BTU/Hr % CFM CFM (°C) in. in. of Water in. in. lb. lb. (kW) (kW) (mm) (KPa) (kg) (kg) (cu. m/s) (cu. m/s) Min. - Max. 100 100,000 80,000 823 80 2,469 30 - 90 2 7-1/8 1/2 1/2 256 367 (29.3) (23.4) (0.388) (1.165) (17) - (50) (0.50) (18 ...
Figure 3. High Temperature Rise Duct Furnace — 30–90°F (17–50°C) • Pressure drop through the heat exchanger is based on the CFM throughput. The desired data is obtained in the following manner: – Select heater size based on heat loss of the building to be heated. – Select temperature rise desired. – Based on temperature rise, the horizontal line intersects heater temperature vs. CFM curve. – Follo ...
• Pressure drop through the heat exchanger is based on the CFM throughput. The desired data is obtained in the following manner: – Select heater size based on heat loss of the building to be heated. – Select temperature rise desired. – Based on temperature rise, the horizontal line intersects heater temperature vs. CFM curve. – Follow vertical line dow ...
Built On the Job (Not Furnished by Factory) On occasion when a duct furnace is incorporated in an air handling system, it may be desirable to handle a total of more CFM than the duct furnace will pass at a given static pressure drop and temperature rise. Therefore, it is necessary to arrange to bypass the additional CFM required. The size of the bypass duct can be determined by referring to the chart. This permit ...
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreem moottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduur ...
18" (457) 5/16" (8) Ductwork Natural (or Power) Vent Furnace Air Flow 5/16" (8) 18" (457) 18" (457) 36" (914) 36" (914) Clearance For Drawer Pul-out 18" (457) 5/16" (8) Typ. Power Vent Units required 36" clearance above top of unit. See Figure 1, p. 9 and Figure 2, p. 10 and Tables 1 and 2 in the “Specifications,” p. 9 section. IInnssttaallllaattiioonn ...
Equipment of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54), or applicable provisions of local building codes”. Natural venting models are equipped with a vent cap designed for natural venting. Air for combustion enters at the base of the vent through a protective grille, and the design of the vent cap is such that the ...
1. Remove “Side Access Panel”. 2. Insert Vent Sleeve of “Vent Cap Assembly” (Item 1) thru “Top Panel Assembly” (Item 2), and over Vent Collar of “Flue Collector Assembly” (Item 3). 3. Align “Vent Cap Assembly” so it is square to “Top Panel Assembly”. 4. Fasten with “Drill Screw” or “Sheet Metal Screw” (Item 4) by reaching between “Flue Collector Assembly” (Item 3) & “To ...
either furnace or building through the duct. IIm mppoorrttaanntt:: Do not alter the flange connection for the duct attachment; air may bypass and cause combustion problems. Be sure to properly seal to avoid any air leakage (see Figure 1, p. 9 and Figure 2, p. 10). • Ductwork connected to duct furnaces should have removable acce ...