CPR32-SE v2.0 Access System Controller Firmware 2.06.5018 Requires: PR Master v4.3.3.504 or higher Operating Manual Rev. A ...
3/27/2010 Page 2 from 12 Introduction This document contents minimum information required for electrical connections, installation and initial tests of CPR32-SE access network controller. CPR32-SE is a module which can be used in RACS systems equipped either with PRxx1 or PRxx2 series controllers. The structure which consist of CPR ...
3/27/2010 Page 3 from 12 Note: If there is no evident need for global type functions in the PRxx2 based system, it is recommended not to install CPR32-SE. Installation The CPR32-SE module can be installed in any metal or plastic enclosure which guarantees adequate protection from dust, water and moisture. Also, enclosure should ass ...
3/27/2010 Page 4 from 12 Power supply Controller can be powered from AC source which delivers 18-22VAC/30VA power; it can be ME-1 metal enclosure (from Roger) with built-in 40VA transformer or another AC source which provides required voltage and power. Optionally, CPR32-SE can be supplied directly from 12V DC, in this case 12V DV ...
3/27/2010 Page 5 from 12 Charging current adjustment When required, battery charging current can be adjusted in 100-500mA range. In order to set required charging current connect battery (which is partly discharged) to CPR32-SE and then using screwdriver rotate POT1 potentiometer and observe current which flow into battery. Chargin ...
3/27/2010 Page 6 from 12 Note: Appling voltages above 30V to REL1/REL2 terminals will damage electronic components used to protect relays’ contacts, this will corrupt functionality of relay output. In normal state NC terminal is shorted to COM while NO remains isolated. When active, NO is shorted to COM while NC is isolated. When ...
3/27/2010 Page 7 from 12 however later APB rules must be strictly followed. [15]: Set Armed mode Input Triggering this input switches all controllers in the network to Armed mode. [16]: Set Disarmed mode Input Triggering this input switches all controllers in the network to Disarmed mode. [64]: CTS communication line Output Used fo ...
3/27/2010 Page 8 from 12 [78]: CPR passive Output Active when CPR is disabled (switched OFF by managing program). [79]: Internal failure Output Line indicates an internal problem of CPR module (clock unset, configuration data error, event memory error); output remains active as long as corresponding state exists. [80]: Buffer probl ...
3/27/2010 Page 9 from 12 [12]. Memory Reset Memory Reset procedure clears all existing data in module’s memory and restores factory defaults. Memory Reset procedure: • Press Memory Reset button and keep it pressed • Press uP Reset button for a moment • Release Memory Reset button • Automatically, after last step CPR32-SE ...
3/27/2010 Page 10 from 12 Connection terminals Terminal Function +ACC- Reserve battery. AC AC supply input, 18-22V/30VA. +AUX- Supply output 12VDC/1A, AUX- internally shorted with GND, output current internally limited. REL1-NO REL1 output, normally open contact, 30V/1.5A. REL1-COM REL1 output, common contact, 30V/1.5A. REL1-NC REL ...
⚠️ Download Safety
The Control Systems Operating manual (12 pages) is completely safe to download (last scan date: 08/06/2026).
Related PDF Instructions for Roger CPR32-SE v2.0:
-
Roger PR311-BK Gateway Installation and programming manual, 30 pages
-
Roger RKD32 Control Systems Operation & user’s manual, 14 pages
-
Roger MCT82M IP Access Controllers Installation manual, 2 pages
-
Roger MCT68ME-IO-I IP Access Controllers Operating manual, 15 pages
-
Roger MCX402-BRD IP Access Controllers Installation manual, 2 pages
-
Roger PS20-BRD Power Supply Operation & user’s manual, 3 pages