Viessmann VITOGAS 100 Technical Data Manual
Text of the manual
Cast iron hot water heating boiler
90 to 240 MBH/26 to 70 kW
5167 462 v1.5 02/2011
Vitogas 100 with boiler stand
beside Vitocell-V 100 domestic hot water storage tank
Vitogas 100
Technical Data Manual
Model Nos. and pricing: see Price List
Vitogas 100
GS1 Series – residential, fully assembled boiler
Natural Gas-/Propane-Fired, Single-Stage Boiler
cast iron sectional construction
atmospheric, fully premix burner
Heating input: 90 to 240 MBH
26 to
70 kW
Top performance in a small package. Thanks
to its compact dimensions, the Vitogas 100
is ideal for installation in closets and
alcoves. Apart from saving space, the
Vitogas 100 is economical in terms of
energy consumption with reduced
emissions.
The benefits at a glance:
High operational reliability and a long
service life due to special high-grade gray
cast iron with lamellar graphite and a low
thermal load on the heat exchanger surface.
Clean combustion due to atmospheric
premix burner with super-stoichiometric
premixing: NOx < 27.9 ppm (air-free),
CO < 9.2 ppm (air-free). The Vitogas 100
therefore meets the toughest emission
requirements in North America, such as
California regulations (SMAQMD).
Economical and environmentally friendly
operation via modulating boiler water
temperatures.
Annual fuel utilization efficiency (A.F.U.E.)
of up to 85.6 %.
Intermittent pilot ignition system provides
soft, quiet and extremely reliable ignition.
Compact dimensions – therefore suitable
for installation in a boiler room, a utility
room or even in an open living area.
Problem-free transport into
difficult-to-access boiler rooms due to light
weight and compact design.
Heat exchanger surfaces of special
high-grade gray cast iron for high
operational reliability and a long
service life
5167 462 v1.5
Product may not be exactly as illustrated.
3
Extremely effective
Heat exchanger surfaces of
Vitotronic – the new
insulation
special high-grade gray cast
generation of boiler controls:
iron with lamellar graphite
Intelligent, easy to install,
operate and service
Stainless steel atmospheric
A redundant gas
super-stoichiometric
valve doubles
premix burners for low-
operational safety
emission combustion
5167 462 v1.5
CSA output /
DOE heating capacity
MBH
kW
76
22
98
29
123
36
140
41
161
47
203
60
Net I=B=R rating*1
MBH
kW
66
19
85
25
107
31
122
36
140
41
177
52
Heat exchanger surface area
ft2
m2
16.25
1.51
21.42
1.99
26.48
2.46
31.54
2.93
36.60
3.40
46.82
4.35
Min. gas supply pressure
Natural gas
Liquid propane
“w.c.
“w.c.
5
11
5
11
5
11
5
11
5
11
5
11
Max. gas supply pressure*2
“w.c.
14
14
14
14
14
14
A.F.U.E.*3
%
85.6
85.5
85.5
85.5
85.5
85.4
Overall dimensions*4
Overall length
Overall width
Width
Overall height (operation)
– Height 1 (control unit in
position for operation)
– Height 2 (control unit in
position for servicing)
Height incl. flue pipe elbow
Height of boiler stand
Height of DHW tank
positioned under the boiler
– 42 to 53 USG/
160 to 200 liter capacity
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
inches
mm
33¼
844
25½
650
21½
546
33¼
845
37½
955
46½
1180
39
992
9¾
250
26
660
33¼
844
25½
650
21½
546
33¼
845
37½
955
46½
1180
39¾
1012
9¾
250
26
660
34
864
33
840
29
736
33¼
845
37½
955
46½
1180
39¾
1012
9¾
250
26
660
34
864
33
840
29
736
33¼
845
37½
955
46½
1180
39¾
1012
9¾
250
26
660
34
864
36½
930
32½
826
33¼
845
37½
955
46½
1180
42½
1082
9¾
250
––
34
864
43¾
1110
39½
1006
33¼
845
37½
955
46½
1180
42½
1082
9¾
250
––
Weight, boiler with insulation,
lbs
burner and boiler control unit
kg
273
124
326
148
375
170
428
194
481
218
582
264
Boiler water content
USG
ltr
2.6
9.7
3.1
11.7
3.6
13.8
4.2
15.9
4.7
17.9
5.8
21.9
Max. operating pressure
psig
60
60
60
60
60
60
Number of intermediate
cast iron sections
2
3
4
5
6
8
Number of burners
3
4
5
6
7
9
5167 462 v1.5
Technical data (continued)
Boiler connections
Boiler supply and return
Safety supply
Drain valve
” (male thread)
” (male thread)
” (male thread)
1½
1½
¾
1½
1½
¾
1½
1½
¾
1½
1½
¾
1½
1½
¾
1½
1½
¾
Gas supply connection
” (NPT)
½
½
½
½
½
½
Flue gas*5
Temperature (gross)
Mass flow rate
– with natural gas
– with liquid propane
°F
°C
lbs/h
kg/h
lbs/h
kg/h
230
110
161
73
148
67
230
110
216
98
209
95
235
113
236
107
209
95
266
130
231
105
223
101
230
110
342
155
322
146
252
122
353
160
337
153
Vent pipe collar
outside Ø”
5
6
6
6
7
7
*1Net I=B=R rating based on piping and pick-up allowance of 1.15.
*2If the gas supply pressure is higher than the maximum permissible value, a separate gas regulator must be installed upstream of the
boiler system.
*3With intermittent pilot electronic ignition system and vent damper.
*4Height dimensions for Vitogas 100 include leveling bolts.
*5Measured flue gas temperature after dilution air with combustion air temperature of 68 °F/20 °C.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
5167 462 v1.5