These instructions are given as a

guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane CH530 chiller control system on CGWN/CCUN and CGAN 209-214 chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance cont

Warranty is based on the general

terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not cov

Trane CCUN 205-211

Contents CG-SVU02B-E4 4 General Information 2 Overview 5 DynaView Interface 6 Display Screens 6 TechView Interface 19 Software Download 20 Diagnostics 22

Trane CCUN 205-211 The Trane CH530 control system

that runs the chiller consists of several elements: • The main processor collects data, status, and diagnostic information and communicates commands to the LLID (for Low Level Intelligent Device) bus. The main processor has an integral display (DynaView). • LLID bus. The main processor communicates to each input and output device (e.g. temperature and pressure sensors, low voltage binary inputs, an

The display on DynaView is a

1/4 VGA display with a resistive touch screen and an LED backlight. The display area is approximately 4 inches wide by 3 inches high (102mm x 60mm). CAUTION! Equipment Damage! Putting excessive pressure on the touch screen could cause damage. It takes less than 7 kg of force to break the screen. In this touch screen application, key functions are determined completely by software and change dep

Trane CCUN 205-211 The bottom of the screen (7) is

present in all screens and contains the following functions. The contrast (8,9) may require re-adjustment at ambient temperatures significantly different from those present at last adjustment. The other functions are critical to machine operation. The AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STO

The Main screen shall be the default

screen. After an idle time of 30 minutes the CH530 shall display the Main screen with the first data fields. The remaining items (listed in the following table) will be viewed by selecting the up/down arrow icons. Figure 3 - Main screen Main Main Reports Reports Settings Settings Auto Auto Stop Stop Chiller Mode: Circuit 1 Mode: Circuit 2 Mode: Evap Ent / Lvg Water Temp: Co

Figure 4 - Main screen menu, Chiller Operating Modes - Sub Level

Figure 5 - Main screen menu, Chiller Operating Modes - Sub Level Auto Auto Stop Stop Back Circuit 1 Mode: Running - Limit Low Evaporator Pressure Start Auto Auto Stop Stop Back Chiller Mode: Running Maximum Capacity Capacity Control Softloading Ice Building

Trane Network Card Owners Instructions: