GE MultiSync 100 Instruction Manual

Text of GE MultiSync 100 Instruction Manual

1588 GPS Clock

1601-0300-A1 Instruction Manual Revision: 1.0x Manual P/N: 1601-0300-A1 Manual Order Code: GEK-119628

Copyright © 2014 GE Multilin Inc. All rights reserved.

GE Multilin MultiSync 100 GPS Clock Instruction Manual for version 1.0x. MultiSync 100 GPS Clock, EnerVista, Digital Energy, Multilin, and GE Multilin are trademarks or registered trademarks of GE Multilin Inc. The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin.

Safety words and definitions

The following safety and equipment symbols are used in this document. Indicates a hazardous situation which, if not avoided, will result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Indicates practices not related to personal injury. For further assistanc

MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL

v MultiSync 100 GPS Clock Table of contents General safety precautions..........................................................................................ii Safety words and definitions.......................................................................................iii For further assistance ..................................................................................................iii 1 PROD
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL TABLE OF CONTENTS 3 INSTALLATION Device hardware ..........................................................................................................19 Front panel......................................................................................................................................................19 Bottom panel ...........................................................................
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 1 MultiSync 100 GPS Clock Chapter 1: Product description Product description This chapter outlines the product, order codes, and specifications. Product description The MultiSync 100 GPS Clock provides sub-microsecond accuracy for synchronizing intelligent electronic devices, and is available with 1588 timing. Configuration options include adjustable hold-over times in cases of poor GPS coverage, and compensat
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL ORDER CODES CHAPTER 1: PRODUCT DESCRIPTION Order codes This section lists the order codes for the MultiSync 100. NOTE Order codes are subject to change without notice. See the ordering page at store.gedigitalenergy.com for the latest options. Table 1: Order codes Specifications Specifications are subject to change without notice. Accuracy Timing accuracy:................................................<= 100

CHAPTER 1: PRODUCT DESCRIPTION

SPECIFICATIONS MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 3 Output options TTL Programmable pulses: .....................................From 1000 per second to 1 per day with programmable offset & duration DCF-77:....................................................................DC level shift Local or universal time IRIG-B:.......................................................................DC level shift or Modified
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1: PRODUCT DESCRIPTION Pollution Degree:.................................................2 Conformal Coating (humidity protection) optional:.............................................................Request quote OTHER ENVIRONMENTAL Humidity (non-condensing):..........................to 95% MECHANICAL PROPERTIES Dimensions (H × W × D): ..................................45 × 110 ×
CHAPTER 1: PRODUCT DESCRIPTION SPECIFICATIONS MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 5 Testing and certification APPROVALS AND CERTIFICATION IEC 61850-3 EMI TYPE TESTS Compliance Applicable council directive According to CE compliance Low voltage directive EN60950-1 EMC directive EN61000-6-2 EN61000-6-4 North America cULus UL60950-1 C22.2 No. 60950-1 CB Report including all country deviations ISO Manufactured under a registered quality program ISO
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1: PRODUCT DESCRIPTION IEEE 1613 (37.90.X) EMI IMMUNITY TYPE TESTS ENVIRONMENTAL TYPE TESTS Test Description Test Levels IEEE 37.90.3 ESD Enclosure Contact +/-2 kV, +/-4 kV, +/- 8 kV Enclosure Air +/-4 kV, +/-8 kV, +/- 15 kV IEEE 37.90.2 Radiated RFI Enclosure Ports 35 V/m IEEE 37.90.1 Fast Transient Signal Ports +/-4 kV @2.5kHz D.C. Power Ports +/-4 kV IEEE 37.90.1 Oscillatory Signal
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 7 MultiSync 100 GPS Clock Chapter 2: Theory of operation Theory of operation GPS and precise time synchronization The Global Positioning System (GPS) is a satellite-based navigation system that is used as the master time source for clock timing signals published by the MultiSync 100 GPS Clock. Each satellite contains an atomic clock, and each satellite publishes a navigation message, including the clock time,
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL THE IRIG-B TIME CODE STANDARD CHAPTER 2: THEORY OF OPERATION stability. GPS is capable of global time and frequency dissemination 24 hours a day, with timing accuracies in the 100-nanosecond range. This level of accuracy explains why GPS has become the typical time synchronization method for commercial applications. GPS time is not identical to UTC (or civil) time, but is related to UTC time. One major diffe

CHAPTER 2: THEORY OF OPERATION

THE IRIG-B TIME CODE STANDARD MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 9 year code (BCDYEAR) counts years and cycles to the next year on January 1st. There is also an optional Straight Binary Seconds (SBS) code that counts seconds from midnight, recycling daily. There are three methods of communicating analog pulses in the IRIG Standard: • Modulated (amplitude-modulated, sine wave carrier) - the method supported in ol
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL THE IRIG-B TIME CODE STANDARD CHAPTER 2: THEORY OF OPERATION is normally 5V for on, and 0V for off. Newer IEDs typically use DCLS due to accuracy. However, the distance to IEDs is limited to around 100m. DCLS typically uses TTL outputs over shielded, twisted pair cable and BNC connectors. IEEE-1344 Extensions The original IRIG Standard did not provide year information, or BCDYEAR, in the time code: only tim
CHAPTER 2: THEORY OF OPERATION THE IRIG-B TIME CODE STANDARD MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 11 With the IEEE 1344 extensions OFF (no BCDYEAR) these time codes are B002 and B122; with the IEEE 1344 extensions ON, these codes are BOO6 and B126. These time codes are defined by the clock settings as well as the ability of IEDs connected to the clock to support these implementations. A limitation of IRIG is that there can be only one time code o
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL THE IRIG-B TIME CODE STANDARD CHAPTER 2: THEORY OF OPERATION IRIG-B wiring considerations DC Level Shift IRIG time code in the MultiSync 100 is developed at a level of approximately 5 volts peak. This signal is normally distributed using copper wiring, however, in the case of the MultiSync 100 the TTL outputs are coaxial with BNC connectors. It is usually possible to connect an unmodulated IRIG driver to nu
CHAPTER 2: THEORY OF OPERATION IEEE 1588 / PTP / C37.238 MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 13 NTP/SNTP in the MultiSync 100 The MultiSync 100 can act as an NTP or SNTP server, and is intended to be an NTP Stratum- 1 time server. The MultiSync 100 synchronizes to GPS to provide accurate timing signals, and NTP time signals are published through the clock Ethernet port. IEEE 1588 / PTP / C37.238 The IEEE Std. 1588-2008 IEEE Standard for a Precis
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL IEEE 1588 / PTP / C37.238 CHAPTER 2: THEORY OF OPERATION Figure 2: IEEE 1588 master-Slave offset measurement The slave clock calculates the link delay (transmission time between the master and slave), the slave clock offset (the time interval by which the slave leads the master), and the drift between the two clocks based on the four timestamps recorded by the slave clock on the receipt and transmission of

GE GPS Owners Instructions: