GE MultiSync 100 Instruction Manual
Text of GE MultiSync 100 Instruction Manual
1588 GPS Clock
1601-0300-A1
Instruction Manual
Revision: 1.0x
Manual P/N: 1601-0300-A1
Manual Order Code: GEK-119628
Copyright © 2014 GE Multilin Inc. All rights reserved.
GE Multilin MultiSync 100 GPS Clock Instruction Manual for version 1.0x.
MultiSync 100 GPS Clock, EnerVista, Digital Energy, Multilin, and GE Multilin are trademarks
or registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin.
Safety words and definitions
The following safety and equipment symbols are used in this document.
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
Indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
Indicates practices not related to personal injury.
For further assistanc
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL
v
MultiSync 100 GPS Clock
Table of contents
General safety precautions..........................................................................................ii
Safety words and definitions.......................................................................................iii
For further assistance ..................................................................................................iii
1
PROD
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL TABLE OF CONTENTS
3
INSTALLATION
Device hardware ..........................................................................................................19
Front panel......................................................................................................................................................19
Bottom panel ...........................................................................
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 1
MultiSync 100 GPS Clock
Chapter 1: Product description
Product description
This chapter outlines the product, order codes, and specifications.
Product description
The MultiSync 100 GPS Clock provides sub-microsecond accuracy for synchronizing
intelligent electronic devices, and is available with 1588 timing. Configuration options
include adjustable hold-over times in cases of poor GPS coverage, and compensat
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL ORDER CODES
CHAPTER 1: PRODUCT DESCRIPTION
Order codes
This section lists the order codes for the MultiSync 100.
NOTE
Order codes are subject to change without notice. See the ordering page at
store.gedigitalenergy.com for the latest options.
Table 1: Order codes
Specifications
Specifications are subject to change without notice.
Accuracy
Timing accuracy:................................................<= 100
CHAPTER 1: PRODUCT DESCRIPTION
SPECIFICATIONS
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL
3
Output options
TTL
Programmable pulses: .....................................From 1000 per second to 1 per day with programmable
offset & duration
DCF-77:....................................................................DC level shift
Local or universal time
IRIG-B:.......................................................................DC level shift or Modified
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL SPECIFICATIONS
CHAPTER 1: PRODUCT DESCRIPTION
Pollution Degree:.................................................2
Conformal Coating (humidity protection)
optional:.............................................................Request quote
OTHER ENVIRONMENTAL
Humidity (non-condensing):..........................to 95%
MECHANICAL PROPERTIES
Dimensions (H × W × D): ..................................45 × 110 ×
CHAPTER 1: PRODUCT DESCRIPTION SPECIFICATIONS
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL
5
Testing and certification
APPROVALS AND CERTIFICATION
IEC 61850-3 EMI TYPE TESTS
Compliance
Applicable council directive
According to
CE compliance
Low voltage directive
EN60950-1
EMC directive
EN61000-6-2
EN61000-6-4
North America
cULus
UL60950-1
C22.2 No. 60950-1
CB Report including all country deviations
ISO
Manufactured under a registered
quality program
ISO
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL SPECIFICATIONS
CHAPTER 1: PRODUCT DESCRIPTION
IEEE 1613 (37.90.X) EMI IMMUNITY TYPE TESTS
ENVIRONMENTAL TYPE TESTS
Test
Description
Test Levels
IEEE 37.90.3
ESD
Enclosure Contact +/-2 kV, +/-4 kV, +/- 8 kV
Enclosure Air
+/-4 kV, +/-8 kV, +/- 15 kV
IEEE 37.90.2
Radiated RFI
Enclosure Ports
35 V/m
IEEE 37.90.1
Fast Transient
Signal Ports
+/-4 kV @2.5kHz
D.C. Power Ports
+/-4 kV
IEEE 37.90.1
Oscillatory
Signal
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL 7
MultiSync 100 GPS Clock
Chapter 2: Theory of operation
Theory of operation
GPS and precise time synchronization
The Global Positioning System (GPS) is a satellite-based navigation system that is used as
the master time source for clock timing signals published by the MultiSync 100 GPS Clock.
Each satellite contains an atomic clock, and each satellite publishes a navigation
message, including the clock time,
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL THE IRIG-B TIME CODE STANDARD
CHAPTER 2: THEORY OF OPERATION
stability. GPS is capable of global time and frequency dissemination 24 hours a day, with
timing accuracies in the 100-nanosecond range. This level of accuracy explains why GPS
has become the typical time synchronization method for commercial applications.
GPS time is not identical to UTC (or civil) time, but is related to UTC time. One major
diffe
CHAPTER 2: THEORY OF OPERATION
THE IRIG-B TIME CODE STANDARD
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL
9
year code (BCDYEAR) counts years and cycles to the next year on January 1st. There is also
an optional Straight Binary Seconds (SBS) code that counts seconds from midnight,
recycling daily.
There are three methods of communicating analog pulses in the IRIG Standard:
•
Modulated (amplitude-modulated, sine wave carrier) - the method supported in ol
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL THE IRIG-B TIME CODE STANDARD
CHAPTER 2: THEORY OF OPERATION
is normally 5V for on, and 0V for off. Newer IEDs typically use DCLS due to accuracy.
However, the distance to IEDs is limited to around 100m. DCLS typically uses TTL outputs
over shielded, twisted pair cable and BNC connectors.
IEEE-1344 Extensions
The original IRIG Standard did not provide year information, or BCDYEAR, in the time code:
only tim
CHAPTER 2: THEORY OF OPERATION THE IRIG-B TIME CODE STANDARD
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL
11
With the IEEE 1344 extensions OFF (no BCDYEAR) these time codes are B002 and B122; with
the IEEE 1344 extensions ON, these codes are BOO6 and B126. These time codes are
defined by the clock settings as well as the ability of IEDs connected to the clock to support
these implementations. A limitation of IRIG is that there can be only one time code o
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL THE IRIG-B TIME CODE STANDARD
CHAPTER 2: THEORY OF OPERATION
IRIG-B wiring considerations
DC Level Shift IRIG time code in the MultiSync 100 is developed at a level of approximately
5 volts peak. This signal is normally distributed using copper wiring, however, in the case of
the MultiSync 100 the TTL outputs are coaxial with BNC connectors. It is usually possible to
connect an unmodulated IRIG driver to nu
CHAPTER 2: THEORY OF OPERATION IEEE 1588 / PTP / C37.238
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL
13
NTP/SNTP in the MultiSync 100
The MultiSync 100 can act as an NTP or SNTP server, and is intended to be an NTP Stratum-
1 time server. The MultiSync 100 synchronizes to GPS to provide accurate timing signals,
and NTP time signals are published through the clock Ethernet port.
IEEE 1588 / PTP / C37.238
The IEEE Std. 1588-2008 IEEE Standard for a Precis
MULTISYNC 100 GPS CLOCK – INSTRUCTION MANUAL IEEE 1588 / PTP / C37.238
CHAPTER 2: THEORY OF OPERATION
Figure 2: IEEE 1588 master-Slave offset measurement
The slave clock calculates the link delay (transmission time between the master and slave),
the slave clock offset (the time interval by which the slave leads the master), and the drift
between the two clocks based on the four timestamps recorded by the slave clock on the
receipt and transmission of