Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet

File Specifications

Brand: Greenheck
Category: Smoke Alarm
Model: Combination Fire Smoke Damper FSD-211 (Specification Sheet), prFT4QWIpmYAo
File Type: PDF
File Size: 0.73 Mb
Pages: 7 pages

Download Document

Get a high-quality, printable PDF version of this manual for offline use.

Download PDF Manual (7 pages)

⚠️ Download Safety: This PDF is completely safe to download (last scan date: 20/04/2026).

Read Online

Read the Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet online using the built-in PDF viewer.

Key Pages of Document

Model FSD-211 is a combination fire smoke damper with 3V style

blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and 4 in. wg (1 kPa) for operation and dynamic closure in emergency fire smoke situations. Model FSD-211 may be installed vertically (with blades running horizontal) or horizontally and is rated for airflow and leakage in either direction. Ratings UL 555 Fi re Resistance Rating Fire Rating: 11⁄2 Hours Dynamic Clos ...

Pressure Drop Data

FSD-211 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft3 (1.201 kg/m3). Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a ...

AMCA 5.2 Pressure Drop

FSD-211 5D D = 4 (W) (H) 3.14 Figure 5.3 Figure 5.2 Figure 5.5 R Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams. The AMCA Certified Ratings Seal applies to air performance ratings only. Velocity (fpm) ...

AMCA 5.3 Pressure Drop

FSD-211 5D 6D 5D D= 4 (W) (H) 3.14 Figure 5.3 Figure 5.2 Figure 5.5 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.02 500 0.01 500 0.01 500 0.01 1000 0.09 1000 0.04 1000 0.03 1000 0.04 1500 0.20 1500 0.09 1500 0.06 1500 0.10 2000 0.36 2000 0.16 2000 0.11 2000 0.17 2500 0.56 2500 0.25 2500 0.17 2500 0.27 3000 0.81 3000 0.35 3 ...

AMCA 5.5 Pressure Drop

FSD-211 R Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams. The AMCA Certified Ratings Seal applies to air performance ratings only. D 4 (W) (H) 3.14 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) ...

Actuators and Accessories

Space Envelopes Externally mounted actuators always require space outside of the damper sleeve. The “S” dimension illustrates the clearance required for various available actuators. On dampers less than 18 in. (457mm) high, actuators may also require clearances above and/or below the sleeve. “B” and “T” dimensions are worst case clearance requirements for some dampers less than 18 in. (457mm) high. All damper sizes und ...

32 in. (813mm)

50 in. 32 in. (813mm) 64 in. (1626mm) 50 in. 96 in. (243 50 in. 100 in. (1270mm) (1270mm) 32 in. (813mm) (2540mm) (1270mm) 32 in. (813mm) 128 in. (2540mm) (1270mm) Combination Fire Smoke Dampers meeting the following specifications shall be furnished and installed where shown on plans and/or as described in schedules. Dampers shall meet the requirements of NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall be tested, rated an ...