13 SEER SINGLE PACKAGED AIR CONDITIONER AND

GAS FURNACE SYSTEM WITH R--410A REFRIGERANT SINGLE AND THREE PHASE 2--5 NOMINAL TONS (SIZES 024--060) A09581 Fig. 1 -- Unit PY3G Single--Packaged Products with Energy--Saving Features and R--410A refrigerant. S Up to 13.5 SEER S Up to 81% AFUE S Factory--Installed TXV S Multi--Speed Blower--Stan ...

High and Low Pressure Switches provide added reliability for the

compressor. Indoor and Outdoor coils are computer--designed for optimum heat transfer and efficiency. The indoor coil is fabricated from copper tube and aluminum fins and is located inside the unit for protection against damage. The outdoor coil is internally mounted on the top tier of the un ...

MODEL NUMBER NOMENCLATURE

PY3G --- --- 024 A Type of Unit PY3G---Single Packaged Gas Heating/Electric Cooling Unit Nominal Cooling Capacity 024 --- 2.0 Tons 030 --- 2.5 Tons 036 --- 3.0 Tons 042 --- 3.5 Tons 048 --- 4.0 Tons 060 --- 5.0 Tons W Heat Input Size (Btuh) 040 --- 40,000 060 --- 60,000 090 --- 90,000 115 --- 115,000 130 --- 130,000 Electrical Sup ...

Cooling Capacities and Efficiencies

UNIT PY3G NOMINAL TONS STANDARD CFM NET COOLING CAPACITIES (Btuh) EER** SEER† 024 2 800 23,000 11.0 13.2 030 2--1/2 1000 28,600 11.2 13.5 036 3 1200 34,400 11.0 13.0 042 3--1/2 1400 40,500 11.2 13.2 048 4 1600 46,500 11.2 13.2 060 5 1750 57,000 11.0 13.4 LEGEND dB---Sound Levels (decibels) db—Dry Bulb ...

NOMINAL CAPACITY (ton)

2 2 2---1/2 2---1/2 3 3 3---1/2 3---1/2 SHIPPING WEIGHT** lb. SHIPPING WEIGHT** (kg) 329 149 329 149 334 152 334 152 344 156 344 156 435 197 435 197 COMPRESSORS Quantity Scroll 1 REFRIGERANT (R---410A) Quantity lb. Quantity (kg) 4.8 2.2 4.8 2.2 6.2 2.8 6. ...

PHYSICAL DATA (CONT)

UNIT SIZE 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) 4 4 4 5 5 5 SHIPPING WEIGHT** lb SHIPPING WEIGHT** kg 443 201 443 201 443 201 465 211 465 211 465 211 COMPRESSORS Quantity Scroll 1 REFRIGERANT (R---410A) Quantity lb Quantity (kg.) 6.4 2.9 6.4 2.9 6.4 2.9 10.0 4.5 10.0 4.5 10.0 4.5 REFRIGERANT METERING DEVICE T ...

OPTIONS AND ACCESSORIES

Field--installed accessories Economizer with Solid--State Controls and Barometric Relief Dampers Manual Air Damper (25% open) Filter Rack Flat Roof Curbs (8--in. [203.2 mm] and 14--in. [355.6 mm]) Square--to--Round Duct Transition Kit Thermostats Crankcase Heater Compressor Start Kit (for use on single--phase units only) Natural--to ...

CAULK BOTTOM CORNER

OF ECONOMIZER ON EACH SIDE BASE COIL FLANGE ON BASE DETAIL ECONOMIZER FI LTER FILTER ACCESS DOOR (HORIZONTAL APPLICATION ONLY.) DO NOT REMOVE FROM DOWNFLOW DISCHARGE. REPLACEMENT PANEL HOLE FOR ECONOMIZER WIRING HARDNESS DOOR LATCH ANGLE HINGED FILTER ACCESS DOOR INSTALL FILTER ACCESS DOOR STICKER ALUMIN ...