Hamilton PUR Installation Instruction
Text of the manual
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . 3
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . 12
EL
035-17477-002 Rev. D (1202)
2
Unitary Products Group
GENERAL INFORMATION
DESCRIPTION
This Category IV, dual certified direct vent and 1-pipe vent
furnace is designed for residential or commercial applica-
tion. It may be installed without modification to the conden-
sate system in a basement, garage, equipment room, alcove,
attic or any other indoor locatio
035-17477-002 Rev. D (1202)
Unitary Products Group
3
VENT SAFETY CHECK PROCEDURE
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are not
in operation:
1.
Seal any unused openings in the venting system.
2.
Inspect the venting system for pr
035-17477-002 Rev. D (1202)
4
Unitary Products Group
A manufactured (mobile) home installation must conform with
the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, or when this standard is not applica-
ble, the Standard for Manufactured Home Installations (Man-
ufactured Home Sites, Communities and Set-Ups), ANSI
A225.1, and/or
035-17477-002 Rev. D (1202)
Unitary Products Group
5
.
FIGURE 1 : DIMENSIONS - UPFLOW MODELS: P*UR/G9T-UP/FG9-UP
20
6-3/8
1-1/4
2-3/4
6-1/8
B
A
28-1/2
6-7/8
9-7/8
20-5/8
1-3/4
14-1/2
22-3/4
B
20
FRONT
TOP IMAGE
SUPPLY END
BOTTOM IMAGE
RETURN END
FRONT
3/4”
FLANGE
A
C
28-1/2
23
WITH K.O.
REMOVED
MODELS P*UR/
G9T-UP/ FG9-UP
A
B
C
40 / 37 / 1000 /”A”
60
035-17477-002 Rev. D (1202)
6
Unitary Products Group
FIGURE 2 : DIMENSIONS - DOWNFLOW/HORIZONTAL MODELS: P*DH/G9T-DH/FG9-DH
B
3/4
45
A
28-1/2
2-3/4
6-1/4
35
1-3/4
5-1/4
18-1/2
3-3/4
1-1/4
20
T'STAT WIRING
7/8 K.O.
CONDENSATE
DRAIN ACCESS
3-1/4 x 3
AIR INTAKE
3-5/8 x 3-5/8
GAS INLET
1-1/4 x 2-1/2
ALT. GAS INLET
1-1/4 x 2-1/2
CONDENSATE
DRAIN ACCESS
3-1/4 x 3
035-17477-002 Rev. D (1202)
Unitary Products Group
7
DUCTWORK
The duct system's design and installation must:
1.
Handle an air volume appropriate for the served space
and within the operating parameters of the furnace spec-
ifications.
2.
Be installed in accordance with standards of NFPA
(National Fire Protection Association) as outlined in
NFPA pamphlets 90
035-17477-002 Rev. D (1202)
8
Unitary Products Group
FILTER INSTALLATION - UPFLOW
All applications require the use of a filter. A high velocity filter
and retainer are provided for field installation on P*UR &
G9T-UP models. FG9-UP models must have a field-supplied
filter and mounting hardware.
Internal Installation
1.
Select desired filter position (left/ri
035-17477-002 Rev. D (1202)
Unitary Products Group
9
The return duct may be attached to the furnace by S-cleat,
bend tabs or other approved methods. Be sure to seal the
duct to the furnace to prevent air leakage.
Where the return duct system is not complete, the return con-
nection must run full size to a location outside the utility room
or basement. For fu