Hamilton PUR Installation Instruction

Text of the manual

GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2

SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . 3 DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 ELECTRICAL POWER CONNECTION . . . . . . . . . . . . 12 EL

035-17477-002 Rev. D (1202)

2 Unitary Products Group GENERAL INFORMATION DESCRIPTION This Category IV, dual certified direct vent and 1-pipe vent furnace is designed for residential or commercial applica- tion. It may be installed without modification to the conden- sate system in a basement, garage, equipment room, alcove, attic or any other indoor locatio

035-17477-002 Rev. D (1202)

Unitary Products Group 3 VENT SAFETY CHECK PROCEDURE The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for pr

035-17477-002 Rev. D (1202)

4 Unitary Products Group A manufactured (mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when this standard is not applica- ble, the Standard for Manufactured Home Installations (Man- ufactured Home Sites, Communities and Set-Ups), ANSI A225.1, and/or

035-17477-002 Rev. D (1202)

Unitary Products Group 5 . FIGURE 1 : DIMENSIONS - UPFLOW MODELS: P*UR/G9T-UP/FG9-UP 20 6-3/8 1-1/4 2-3/4 6-1/8 B A 28-1/2 6-7/8 9-7/8 20-5/8 1-3/4 14-1/2 22-3/4 B 20 FRONT TOP IMAGE SUPPLY END BOTTOM IMAGE RETURN END FRONT 3/4” FLANGE A C 28-1/2 23 WITH K.O. REMOVED MODELS P*UR/ G9T-UP/ FG9-UP A B C 40 / 37 / 1000 /”A” 60

035-17477-002 Rev. D (1202)

6 Unitary Products Group FIGURE 2 : DIMENSIONS - DOWNFLOW/HORIZONTAL MODELS: P*DH/G9T-DH/FG9-DH B 3/4 45 A 28-1/2 2-3/4 6-1/4 35 1-3/4 5-1/4 18-1/2 3-3/4 1-1/4 20 T'STAT WIRING 7/8 K.O. CONDENSATE DRAIN ACCESS 3-1/4 x 3 AIR INTAKE 3-5/8 x 3-5/8 GAS INLET 1-1/4 x 2-1/2 ALT. GAS INLET 1-1/4 x 2-1/2 CONDENSATE DRAIN ACCESS 3-1/4 x 3

035-17477-002 Rev. D (1202)

Unitary Products Group 7 DUCTWORK The duct system's design and installation must: 1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace spec- ifications. 2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90

035-17477-002 Rev. D (1202)

8 Unitary Products Group FILTER INSTALLATION - UPFLOW All applications require the use of a filter. A high velocity filter and retainer are provided for field installation on P*UR & G9T-UP models. FG9-UP models must have a field-supplied filter and mounting hardware. Internal Installation 1. Select desired filter position (left/ri

035-17477-002 Rev. D (1202)

Unitary Products Group 9 The return duct may be attached to the furnace by S-cleat, bend tabs or other approved methods. Be sure to seal the duct to the furnace to prevent air leakage. Where the return duct system is not complete, the return con- nection must run full size to a location outside the utility room or basement. For fu