ABB REQ650 Applications Manual
Read Online
Read the ABB REQ650 Applications Manual online using the built-in PDF viewer.
Text of the manual
Document ID: 1MRK 505 383-UEN
Issued: October 2017
Revision: A
Product version: 2.2.1
© Copyright 2017 ABB. All rights reserved
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographic
software written/developed by: Eric Young ([email protected]) and Tim Hudson
([email protected]).
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure
and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole
responsibility of the person or entity applying the equipment, and those so
responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standard EN 60255-26 for the EMC directive, and
with the product standards EN 60255-1 and EN 60255-27 for the low voltage
directive. The product is designed in accordance with the international standards of
the IEC 60255 series.
Table of contents
Section 1
Introduction.....................................................................13
This manual......................................................................................13
Intended audience............................................................................13
Product documentation.....................................................................14
Product documentation set..........................................................14
Document revision history........................................................... 15
Related documents......................................................................16
Document symbols and conventions................................................16
Symbols.......................................................................................16
Document conventions................................................................17
IEC 61850 edition 1 / edition 2 mapping...........................................18
Section 2
Application......................................................................23
General IED application....................................................................23
Back-up protection functions............................................................ 24
Control and monitoring functions......................................................25
Communication.................................................................................27
Basic IED functions.......................................................................... 29
Section 3
Configuration..................................................................31
Description of configuration REQ650............................................... 31
Introduction..................................................................................31
Description of B11..................................................................31
Section 4
Analog inputs..................................................................33
Introduction.......................................................................................33
Setting guidelines............................................................................. 33
Setting of the phase reference channel.......................................34
Example................................................................................. 34
Setting of current channels..........................................................34
Example 1.............................................................................. 34
Example 2.............................................................................. 35
Example 3.............................................................................. 36
Examples on how to connect, configure and set CT
inputs for most commonly used CT connections....................39
Example on how to connect a star connected three-
phase CT set to the IED.........................................................40
Example how to connect delta connected three-phase
CT set to the IED....................................................................44
Example how to connect single-phase CT to the IED............ 47
Table of contents
Breaker protection REQ650 2.2 IEC
1
Application manual
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection IED.. 49
Setting of voltage channels......................................................... 49
Example................................................................................. 49
Examples how to connect, configure and set VT inputs
for most commonly used VT connections.............................. 50
Examples on how to connect a three phase-to-earth
connected VT to the IED........................................................ 51
Example on how to connect a phase-to-phase
connected VT to the IED........................................................ 53
Example on how to connect an open delta VT to the IED
for high impedance earthed or unearthed networks...............55
Example how to connect the open delta VT to the IED
for low impedance earthed or solidly earthed
power systems....................................................................... 58
Section 5
Local HMI....................................................................... 61
Display..............................................................................................62
LEDs.................................................................................................64
Keypad............................................................................................. 65
Local HMI functionality..................................................................... 67
Protection and alarm indication................................................... 67
Parameter management .............................................................68
Front communication...................................................................69
Section 6
Current protection...........................................................71
Instantaneous phase overcurrent protection PHPIOC .................... 71
Identification................................................................................ 71
Application...................................................................................71
Setting guidelines........................................................................ 72
Meshed network without parallel line..................................... 72
Meshed network with parallel line.......................................... 74
Directional phase overcurrent protection, four steps OC4PTOC......76
Identification................................................................................ 76
Application...................................................................................76
Setting guidelines........................................................................ 77
Settings for each step.............................................................79
Setting example......................................................................82
Instantaneous residual overcurrent protection EFPIOC .................. 87
Identification................................................................................ 87
Application...................................................................................87
Setting guidelines........................................................................ 87
Directional residual overcurrent protection, four steps EF4PTOC ...90
Identification................................................................................ 90
Setting guidelines........................................................................ 90
Table of contents
2
Breaker protection REQ650 2.2 IEC
Application manual
Common settings for all steps................................................ 91
2nd harmonic restrain.............................................................92
Parallel transformer inrush current logic.................................93
Switch onto fault logic.............................................................94
Settings for each step (x = 1, 2, 3 and 4)............................... 94
Four step directional negative phase sequence overcurrent
protection NS4PTOC .......................................................................97
Identification................................................................................ 97
Application...................................................................................97
Setting guidelines........................................................................ 99
Settings for each step ............................................................99
Common settings for all steps.............................................. 102
Thermal overload protection, one time constant, Celsius/
Fahrenheit LCPTTR/LFPTTR.........................................................103
Identification.............................................................................. 104
Application.................................................................................104
Setting guideline........................................................................104
Breaker failure protection CCRBRF............................................... 105
Identification.............................................................................. 106
Application.................................................................................106
Setting guidelines...................................................................... 106
Stub protection STBPTOC ............................................................ 110
Identification.............................................................................. 110
Application.................................................................................110
Setting guidelines...................................................................... 111
Broken conductor check BRCPTOC ............................................. 112
Identification.............................................................................. 112
Application.................................................................................112
Setting guidelines...................................................................... 112
Section 7
Voltage protection........................................................ 113
Two step undervoltage protection UV2PTUV ................................113
Identification.............................................................................. 113
Application.................................................................................113
Setting guidelines...................................................................... 114
Equipment protection, such as for motors and generators...114
Disconnected equipment detection...................................... 114
Power supply quality ........................................................... 114
Voltage instability mitigation.................................................114
Backup protection for power system faults...........................114
Settings for two step undervoltage protection...................... 115
Two step overvoltage protection OV2PTOV ..................................116
Identification.............................................................................. 116
Application.................................................................................117
Table of contents
Breaker protection REQ650 2.2 IEC
3
Application manual
Setting guidelines...................................................................... 117
Equipment protection, such as for motors, generators,
reactors and transformers.................................................... 118
Equipment protection, capacitors......................................... 118
Power supply quality............................................................ 118
High impedance earthed systems........................................ 118
The following settings can be done for the two step
overvoltage protection..........................................................118
Two step residual overvoltage protection ROV2PTOV ................. 121
Identification.............................................................................. 121
Application.................................................................................121
Setting guidelines...................................................................... 121
Equipment protection, such as for motors, generators,
reactors and transformersEquipment protection for
transformers......................................................................... 122
Equipment protection, capacitors......................................... 122
Power supply quality............................................................ 122
High impedance earthed systems........................................ 122
Direct earthed system.......................................................... 123
Settings for two step residual overvoltage protection...........124
Loss of voltage check LOVPTUV .................................................. 126
Identification.............................................................................. 126
Application.................................................................................126
Setting guidelines...................................................................... 126
Advanced users settings...................................................... 126
Section 8
Secondary system supervision.....................................127
Current circuit supervision CCSSPVC............................................127
Identification.............................................................................. 127
Application.................................................................................127
Setting guidelines...................................................................... 127
Fuse failure supervision FUFSPVC................................................128
Identification.............................................................................. 128
Application.................................................................................128
Setting guidelines...................................................................... 129
General.................................................................................129
Setting of common parameters............................................ 129
Negative sequence based....................................................130
Zero sequence based...........................................................131
Delta U and delta I ...............................................................131
Dead line detection...............................................................132
Section 9
Control..........................................................................133
Synchrocheck, energizing check, and synchronizing SESRSYN...133
Table of contents
4
Breaker protection REQ650 2.2 IEC
Application manual
External fuse failure..............................................................138
Application examples.................................................................139
Single circuit breaker with single busbar.............................. 140
Single circuit breaker with double busbar, external
voltage selection...................................................................141
Single circuit breaker with double busbar, internal
voltage selection...................................................................141
Setting guidelines...................................................................... 142
Autorecloser for 1 phase, 2 phase and/or 3 phase operation
SMBRREC .....................................................................................147
Identification.............................................................................. 147
Application.................................................................................147
Auto reclosing operation Off and On....................................151
Start auto reclosing and conditions for start of a
reclosing cycle......................................................................151
Start auto reclosing from circuit breaker open information...152
Blocking of the auto recloser................................................152
Control of the auto reclosing dead time for shot 1................152
Long trip signal.....................................................................153
Maximum number of reclosing shots....................................153
ARMode = 3ph, (normal setting for a three-phase shot)...... 153
ARMode = 1/2/3ph............................................................... 153
ARMode = 1/2ph, 1-phase or 2-phase reclosing in the
first shot................................................................................154
ARMode = 1ph+1*2ph, 1-phase or 2-phase reclosing in
the first shot..........................................................................154
ARMode = 1/2ph + 1*3ph, 1-phase, 2-phase or 3-phase
reclosing in the first shot.......................................................155
ARMode = 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase
reclosing in the first shot.......................................................155
External selection of auto reclosing mode............................156
Auto reclosing reclaim timer................................................. 156
Pulsing of the circuit breaker closing command and
counter................................................................................. 156
Transient fault.......................................................................156
Permanent fault and reclosing unsuccessful signal............. 157
Lock-out initiation................................................................. 157
Evolving fault........................................................................158
Table of contents
Breaker protection REQ650 2.2 IEC
5
Application manual
Automatic continuation of the auto reclosing sequence....... 159
Thermal overload protection holding the auto recloser back159
Setting guidelines...................................................................... 159
Configuration........................................................................159
Auto recloser settings...........................................................165
Apparatus control APC...................................................................169
Application.................................................................................170
Bay control QCBAY..............................................................174
Switch controller SCSWI...................................................... 175
Switches SXCBR/SXSWI..................................................... 176
Proxy for signals from switching device via GOOSE
XLNPROXY..........................................................................177
Interaction between modules.....................................................180
Setting guidelines...................................................................... 182
Bay control (QCBAY)........................................................... 183
Switch controller (SCSWI)....................................................183
Switch (SXCBR/SXSWI)...................................................... 184
Proxy for signals from switching device via GOOSE
XLNPROXY..........................................................................185
Logic rotating switch for function selection and LHMI
presentation SLGAPC.................................................................... 185
Application.................................................................................185
Setting guidelines...................................................................... 186
Selector mini switch VSGAPC........................................................186
Identification.............................................................................. 187
Application.................................................................................187
Setting guidelines...................................................................... 187
Single point generic control 8 signals SPC8GAPC........................ 188
Identification.............................................................................. 188
Application.................................................................................188
Setting guidelines...................................................................... 188
AutomationBits, command function for DNP3.0 AUTOBITS.......... 188
Identification.............................................................................. 189
Application.................................................................................189
Setting guidelines...................................................................... 189
Single command, 16 signals SINGLECMD.................................... 189
Identification.............................................................................. 189
Application.................................................................................189
Setting guidelines...................................................................... 191
Section 10 Logic.............................................................................193
Tripping logic SMPPTRC ...............................................................193
Identification.............................................................................. 193
Application.................................................................................193
Table of contents
6
Breaker protection REQ650 2.2 IEC
Application manual
Three-phase tripping............................................................ 194
Single- and/or three-phase tripping......................................194
Single-, two- or three-phase tripping.................................... 196
Lock-out................................................................................196
Example of directional data..................................................197
Blocking of the function block...............................................199
Setting guidelines...................................................................... 199
Logic for group alarm ALMCALH....................................................199
Identification.............................................................................. 199
Application.................................................................................200
Setting guidelines...................................................................... 200
Logic for group alarm WRNCALH.................................................. 200
Identification.............................................................................. 200
Application............................................................................200
Setting guidelines.................................................................200
Logic for group indication INDCALH...............................................200
Identification.............................................................................. 200
Application............................................................................201
Setting guidelines.................................................................201
Configurable logic blocks................................................................201
Application.................................................................................201
Setting guidelines...................................................................... 201
Configuration........................................................................201
Fixed signal function block FXDSIGN............................................ 202
Identification.............................................................................. 202
Application.................................................................................202
Boolean 16 to Integer conversion B16I.......................................... 204
Identification.............................................................................. 204
Application.................................................................................204
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC.....................................................205
Identification.............................................................................. 205
Application.................................................................................205
Integer to Boolean 16 conversion IB16.......................................... 206
Identification.............................................................................. 206
Application.................................................................................206
Integer to Boolean 16 conversion with logic node
representation ITBGAPC................................................................207
Identification.............................................................................. 208
Application.................................................................................208
Elapsed time integrator with limit transgression and overflow
supervision TEIGAPC.....................................................................209
Identification.............................................................................. 209
Application.................................................................................209
Table of contents
Breaker protection REQ650 2.2 IEC
7
Application manual
Setting guidelines...................................................................... 209
Comparator for integer inputs - INTCOMP..................................... 210
Identification.............................................................................. 210
Application.................................................................................210
Setting guidelines...................................................................... 210
Setting example.........................................................................210
Comparator for real inputs - REALCOMP...................................... 211
Identification.............................................................................. 211
Application.................................................................................211
Setting guidelines...................................................................... 211
Setting example.........................................................................212
Section 11 Monitoring.....................................................................215
Measurement..................................................................................215
Identification.............................................................................. 215
Application.................................................................................215
Zero clamping............................................................................217
Setting guidelines...................................................................... 218
Setting examples..................................................................221
Gas medium supervision SSIMG................................................... 225
Identification.............................................................................. 225
Application.................................................................................225
Setting guidelines...................................................................... 226
Liquid medium supervision SSIML................................................. 227
Identification.............................................................................. 227
Application.................................................................................227
Setting guidelines...................................................................... 227
Breaker monitoring SSCBR............................................................228
Identification.............................................................................. 228
Application.................................................................................228
Setting guidelines...................................................................... 231
Setting procedure on the IED...............................................231
Event function EVENT....................................................................232
Identification.............................................................................. 232
Application.................................................................................232
Setting guidelines...................................................................... 233
Disturbance report DRPRDRE....................................................... 233
Identification.............................................................................. 233
Application.................................................................................234
Setting guidelines...................................................................... 234
Recording times................................................................... 236
Binary input signals.............................................................. 237
Analog input signals............................................................. 238
Sub-function parameters......................................................238
Table of contents
8
Breaker protection REQ650 2.2 IEC
Application manual
Logical signal status report BINSTATREP..................................... 240
Identification.............................................................................. 240
Application.................................................................................240
Setting guidelines...................................................................... 240
Limit counter L4UFCNT..................................................................240
Identification.............................................................................. 241
Application.................................................................................241
Setting guidelines...................................................................... 241
Running hour-meter TEILGAPC.....................................................241
Identification.............................................................................. 241
Application.................................................................................241
Setting guidelines...................................................................... 242
Section 12 Metering....................................................................... 243
Pulse-counter logic PCFCNT......................................................... 243
Identification.............................................................................. 243
Application.................................................................................243
Setting guidelines...................................................................... 243
Function for energy calculation and demand handling ETPMMTR 244
Identification.............................................................................. 244
Application.................................................................................244
Setting guidelines...................................................................... 245
Section 13 Ethernet-based communication....................................247
Access point................................................................................... 247
Application.................................................................................247
Setting guidelines...................................................................... 247
Redundant communication.............................................................248
Identification.............................................................................. 248
Application.................................................................................249
Setting guidelines...................................................................... 250
Merging unit....................................................................................251
Application.................................................................................251
Setting guidelines...................................................................... 252
Routes............................................................................................ 252
Application.................................................................................252
Setting guidelines...................................................................... 252
Section 14 Station communication.................................................253
Communication protocols...............................................................253
IEC 61850-8-1 communication protocol......................................... 253
Application IEC 61850-8-1.........................................................253
Setting guidelines...................................................................... 255
Table of contents
Breaker protection REQ650 2.2 IEC
9
Application manual
Horizontal communication via GOOSE..................................... 255
Sending data........................................................................ 255
Receiving data......................................................................255
IEC/UCA 61850-9-2LE communication protocol............................ 256
Introduction................................................................................256
Setting guidelines...................................................................... 258
Specific settings related to the IEC/UCA 61850-9-2LE
communication..................................................................... 259
Loss of communication when used with LDCM....................259
Setting examples for IEC/UCA 61850-9-2LE and time
synchronization.................................................................... 264
IEC 61850 quality expander QUALEXP.................................... 269
LON communication protocol......................................................... 270
Application.................................................................................270
MULTICMDRCV and MULTICMDSND..................................... 271
Identification......................................................................... 272
Application............................................................................272
Setting guidelines.................................................................272
SPA communication protocol......................................................... 272
Application.................................................................................272
Setting guidelines...................................................................... 273
IEC 60870-5-103 communication protocol..................................... 275
Application.................................................................................275
Functionality......................................................................... 275
Design.................................................................................. 276
Settings......................................................................................278
Settings for RS485 and optical serial communication.......... 279
Settings from PCM600......................................................... 280
Function and information types................................................. 282
DNP3 Communication protocol...................................................... 283
Application.................................................................................283
Section 15 Security........................................................................ 285
Authority status ATHSTAT............................................................. 285
Application.................................................................................285
Self supervision with internal event list INTERRSIG...................... 285
Application.................................................................................285
Change lock CHNGLCK.................................................................286
Application.................................................................................286
Denial of service SCHLCCH/RCHLCCH ....................................... 287
Application.................................................................................287
Setting guidelines...................................................................... 287
Section 16 Basic IED functions...................................................... 289
Table of contents
10
Breaker protection REQ650 2.2 IEC
Application manual
IED identifiers TERMINALID.......................................................... 289
Application.................................................................................289
Product information PRODINF....................................................... 289
Application.................................................................................289
Factory defined settings............................................................ 289
Measured value expander block RANGE_XP................................ 290
Identification.............................................................................. 290
Application.................................................................................291
Setting guidelines...................................................................... 291
Parameter setting groups............................................................... 291
Application.................................................................................291
Setting guidelines...................................................................... 292
Rated system frequency PRIMVAL................................................ 292
Identification.............................................................................. 292
Application.................................................................................292
Setting guidelines...................................................................... 292
Summation block 3 phase 3PHSUM.............................................. 292
Application.................................................................................292
Setting guidelines...................................................................... 293
Global base values GBASVAL....................................................... 293
Identification.............................................................................. 293
Application.................................................................................293
Setting guidelines...................................................................... 293
Signal matrix for binary inputs SMBI.............................................. 294
Application.................................................................................294
Setting guidelines...................................................................... 294
Signal matrix for binary outputs SMBO ......................................... 294
Application.................................................................................294
Setting guidelines...................................................................... 294
Signal matrix for analog inputs SMAI............................................. 295
Application.................................................................................295
Frequency values...................................................................... 295
Setting guidelines...................................................................... 296
Test mode functionality TESTMODE..............................................301
Application.................................................................................301
IEC 61850 protocol test mode..............................................302
Setting guidelines...................................................................... 303
Time synchronization TIMESYNCHGEN........................................303
Application.................................................................................303
Setting guidelines...................................................................... 304
System time..........................................................................304
Synchronization....................................................................304
Process bus IEC/UCA 61850-9-2LE synchronization.......... 308
Table of contents
Breaker protection REQ650 2.2 IEC
11
Application manual
Section 17 Requirements...............................................................309
Current transformer requirements.................................................. 309
Current transformer basic classification and requirements....... 309
Conditions..................................................................................311
Fault current.............................................................................. 312
Secondary wire resistance and additional load......................... 312
General current transformer requirements................................ 313
Rated equivalent secondary e.m.f. requirements......................313
Breaker failure protection..................................................... 313
Current transformer requirements for CTs according to
other standards..........................................................................314
Current transformers according to IEC 61869-2,
class P, PR...........................................................................314
Current transformers according to IEC 61869-2, class
PX, PXR (and old IEC 60044-6, class TPS
and old British Standard, class X)........................................ 315
Current transformers according to ANSI/IEEE..................... 315
SNTP server requirements............................................................. 316
PTP requirements...........................................................................316
IEC/UCA 61850-9-2LE Merging unit requirements ....................... 316
Section 18 Glossary....................................................................... 319
Table of contents
12
Breaker protection REQ650 2.2 IEC
Application manual
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also provide assistance
for calculating settings.
1.2
Intended audience
GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v11
This manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.
The protection and control engineer must be experienced in electrical power
engineering and have knowledge of related technology, such as protection schemes
and communication principles.
1MRK 505 383-UEN A
Section 1
Introduction
Breaker protection REQ650 2.2 IEC
13
Application manual
Product documentation set
GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v15
IEC07000220-4-en.vsd
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
Deinstalling & disposal
Application manual
Operation manual
Installation manual
Engineering manual
Communication
protocol manual
Cyber security
deployment guideline
Technical manual
Commissioning manual
IEC07000220 V4 EN-US
Figure 1:
The intended use of manuals throughout the product lifecycle
The engineering manual contains instructions on how to engineer the IEDs using
the various tools available within the PCM600 software. The manual provides
instructions on how to set up a PCM600 project and insert IEDs to the project
structure. The manual also recommends a sequence for the engineering of
protection and control functions, LHMI functions as well as communication
engineering for IEC 60870-5-103, IEC 61850, DNP3, LON and SPA.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in the chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED.
The manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for the
checking of external circuitry and energizing the IED, parameter setting and
configuration as well as verifying settings by secondary injection. The manual
Section 1
1MRK 505 383-UEN A
Introduction
14
Breaker protection REQ650 2.2 IEC
Application manual
describes the process of testing an IED in a station which is not in service. The
chapters are organized in the chronological order in which the IED should be
commissioned. The relevant procedures may be followed also during the service
and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for the monitoring,
controlling and setting of the IED. The manual also describes how to identify
disturbances and how to view calculated and measured power grid data to
determine the cause of a fault.
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also provide assistance
for calculating settings.
The technical manual contains operation principle descriptions, and lists function
blocks, logic diagrams, input and output signals, setting parameters and technical
data, sorted per function. The manual can be used as a technical reference during
the engineering phase, installation and commissioning phase, and during normal
service.
The communication protocol manual describes the communication protocols
supported by the IED. The manual concentrates on the vendor-specific
implementations.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The cyber security deployment guideline describes the process for handling cyber
security when communicating with the IED. Certification, Authorization with role
based access control, and product engineering for cyber security related events are
described and sorted by function. The guideline can be used as a technical
reference during the engineering phase, installation and commissioning phase, and
during normal service.
1.3.2
Document revision history
GUID-C8027F8A-D3CB-41C1-B078-F9E59BB73A6C v4
Document revision/date
History
–/May 2017
First release
1MRK 505 383-UEN A
Section 1
Introduction
Breaker protection REQ650 2.2 IEC
15
Application manual
Documents related to REQ650
Document numbers
Application manual
1MRK 505 383-UEN
Commissioning manual
1MRK 505 385-UEN
Product guide
1MRK 505 386-BEN
Technical manual
1MRK 505 384-UEN
Type test certificate
1MRK 505 386-TEN
650 series manuals
Document numbers
Operation manual
1MRK 500 128-UEN
Engineering manual
1MRK 511 420-UEN
Installation manual
1MRK 514 027-UEN
Communication protocol manual, DNP3
1MRK 511 413-UUS
Communication protocol manual, IEC
60870-5-103
1MRK 511 416-UEN
Communication protocol manual, IEC 61850
Edition 1
1MRK 511 414-UEN
Communication protocol manual, IEC 61850
Edition 2
1MRK 511 415-UEN
Communication protocol manual, LON
1MRK 511 417-UEN
Communication protocol manual, SPA
1MRK 511 418-UEN
Point list manual, DNP3
1MRK 511 419-UUS
Accessories guide
IEC: 1MRK 514 012-UEN
ANSI: 1MRK 514 012-UUS
Cyber security deployment guideline
1MRK 511 421-UEN
Connection and Installation components
1MRK 513 003-BEN
Test system, COMBITEST
1MRK 512 001-BEN
Application guide, Communication set-up
1MRK 505 382-UEN
1.4
Document symbols and conventions
1.4.1
Symbols
GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v12
The electrical warning icon indicates the presence of a hazard
which could result in electrical shock.
The warning icon indicates the presence of a hazard which could
result in personal injury.
Section 1
1MRK 505 383-UEN A
Introduction
16
Breaker protection REQ650 2.2 IEC
Application manual
The caution hot surface icon indicates important information or
warning about the temperature of product surfaces.
Class 1 Laser product. Take adequate measures to protect the eyes
and do not view directly with optical instruments.
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. It is important that the user fully complies with all warning and
cautionary notices.
1.4.2
Document conventions
GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v6
•
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the
push button icons.
For example, to navigate between the options, use
and
.
•
HMI menu paths are presented in bold.
For example, select Main menu/Settings.
•
LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and
press
.
•
Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation
setting.
•
Each function block symbol shows the available input/output signal.
1MRK 505 383-UEN A
Section 1
Introduction
Breaker protection REQ650 2.2 IEC
17
Application manual
the character ^ in front of an input/output signal name indicates that the
signal name may be customized using the PCM600 software.
•
the character * after an input signal name indicates that the signal must
be connected to another function block in the application configuration
to achieve a valid application configuration.
•
Logic diagrams describe the signal logic inside the function block and are
bordered by dashed lines.
•
Signals in frames with a shaded area on their right hand side represent
setting parameter signals that are only settable via the PST, ECT or
LHMI.
•
If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts
and continues.
•
Signal paths that extend beyond the logic diagram and continue in
another diagram have the suffix ”-cont.”
Illustrations are used as an example and might show other products
than the one the manual describes. The example that is illustrated is
still valid.
1.5
IEC 61850 edition 1 / edition 2 mapping
GUID-C5133366-7260-4C47-A975-7DBAB3A33A96 v4
Function block names are used in ACT and PST to identify functions. Respective
function block names of Edition 1 logical nodes and Edition 2 logical nodes are
shown in the table below.
Table 1:
IEC 61850 edition 1 / edition 2 mapping
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
AGSAL
AGSAL
SECLLN0
AGSAL
ALMCALH
ALMCALH
ALMCALH
ALTIM
-
ALTIM
ALTMS
-
ALTMS
ALTRK
-
ALTRK
BRCPTOC
BRCPTOC
BRCPTOC
BTIGAPC
B16IFCVI
BTIGAPC
CCPDSC
CCRPLD
CCPDSC
CCRBRF
CCRBRF
CCRBRF
CCSSPVC
CCSRDIF
CCSSPVC
CMMXU
CMMXU
CMMXU
CMSQI
CMSQI
CMSQI
Table continues on next page
Section 1
1MRK 505 383-UEN A
Introduction
18
Breaker protection REQ650 2.2 IEC
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
CVGAPC
GF2LLN0
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC
CVMMXN
CVMMXN
CVMMXN
DPGAPC
DPGGIO
DPGAPC
DRPRDRE
DRPRDRE
DRPRDRE
EF4PTOC
EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC
EFPIOC
EFPIOC
EFPIOC
ETPMMTR
ETPMMTR
ETPMMTR
FUFSPVC
SDDRFUF
FUFSPVC
HZPDIF
HZPDIF
HZPDIF
INDCALH
INDCALH
INDCALH
ITBGAPC
IB16FCVB
ITBGAPC
L4UFCNT
L4UFCNT
L4UFCNT
LCPTTR
LCPTTR
LCPTTR
LD0LLN0
LLN0
LLN0
LDLPSCH
LDLPDIF
LDLPSCH
LFPTTR
LFPTTR
LFPTTR
LMBRFLO
LMBRFLO
LMBRFLO
LOVPTUV
LOVPTUV
LOVPTUV
LPHD
LPHD
LPHD
LT3CPDIF
LT3CPDIF
LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC
MVGAPC
MVGGIO
MVGAPC
NS4PTOC
EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC
EF4PTRC
EF4RDIR
PH1PTOC
OC4PTOC
OC4LLN0
GEN4PHAR
PH3PTOC
PH3PTRC
GEN4PHAR
PH3PTOC
PH3PTRC
OV2PTOV
GEN2LLN0
OV2PTOV
PH1PTRC
OV2PTOV
PH1PTRC
PCFCNT
PCGGIO
PCFCNT
Table continues on next page
1MRK 505 383-UEN A
Section 1
Introduction
Breaker protection REQ650 2.2 IEC
19
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
PHPIOC
PHPIOC
PHPIOC
QCBAY
QCBAY
BAY/LLN0
QCRSV
QCRSV
QCRSV
RCHLCCH
RCHLCCH
RCHLCCH
REFPDIF
REFPDIF
REFPDIF
ROV2PTOV
GEN2LLN0
PH1PTRC
ROV2PTOV
PH1PTRC
ROV2PTOV
SCHLCCH
SCHLCCH
SCHLCCH
SCILO
SCILO
SCILO
SCSWI
SCSWI
SCSWI
SESRSYN
RSY1LLN0
AUT1RSYN
MAN1RSYN
SYNRSYN
AUT1RSYN
MAN1RSYN
SYNRSYN
SLGAPC
SLGGIO
SLGAPC
SMBRREC
SMBRREC
SMBRREC
SMPPTRC
SMPPTRC
SMPPTRC
SP16GAPC
SP16GGIO
SP16GAPC
SPC8GAPC
SPC8GGIO
SPC8GAPC
SPGAPC
SPGGIO
SPGAPC
SSCBR
SSCBR
SSCBR
SSIMG
SSIMG
SSIMG
SSIML
SSIML
SSIML
SXCBR
SXCBR
SXCBR
SXSWI
SXSWI
SXSWI
T3WPDIF
T3WPDIF
T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC
TEIGAPC
TEIGGIO
TEIGAPC
TEILGAPC
TEILGGIO
TEILGAPC
TMAGAPC
TMAGGIO
TMAGAPC
TRPTTR
TRPTTR
TRPTTR
UV2PTUV
GEN2LLN0
PH1PTRC
UV2PTUV
PH1PTRC
UV2PTUV
VMMXU
VMMXU
VMMXU
VMSQI
VMSQI
VMSQI
VNMMXU
VNMMXU
VNMMXU
VSGAPC
VSGGIO
VSGAPC
WRNCALH
WRNCALH
WRNCALH
ZCLCPSCH
ZCLCPLAL
ZCLCPSCH
Table continues on next page
Section 1
1MRK 505 383-UEN A
Introduction
20
Breaker protection REQ650 2.2 IEC
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
ZCPSCH
ZCPSCH
ZCPSCH
ZCRWPSCH
ZCRWPSCH
ZCRWPSCH
ZCVPSOF
ZCVPSOF
ZCVPSOF
ZMFPDIS
ZMFLLN0
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU
PSFPDIS
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU
1MRK 505 383-UEN A
Section 1
Introduction
Breaker protection REQ650 2.2 IEC
21
Application manual
General IED application
GUID-3F024D79-D031-42DC-B0BC-1F3757B8D3E0 v4
Breaker protection REQ650 provides a standalone solution for applications where
synchrocheck controlled closing of the circuit breaker is required, but the
integration of the automatic reclosing function into the main line protection IED is
not preferred or suitable. The advanced automatic reclosing, synchronizing,
synchrocheck and energizing check functions of REQ650 provides an optimized
standalone product.
REQ650 provides backup to the main protection with redundant protection and
control functions.
One pre-configured package has been defined for the following application:
•
A breaker bay connecting a transmission line to a busbar, with back-up
protection functions enabling single or three phase trip (B11)
The backup protection is based on basic overcurrent and voltage based functions.
In line protection applications, autoreclosing with or without synchrocheck is
available.
The package is configured and ready for direct use. Analog and control circuits
have been pre-defined and other signals need to be applied as required for each
application. The pre-configured IED can be changed and adapted to suit specific
applications with the application configuration tool.
The IED can be used in applications with the IEC/UCA 61850-9-2LE process bus
with up to four Merging Units (MU). Each MU has eight analogue channels, four
current and four voltages. Conventional input transformer module and Merging
Unit channels can be mixed freely in your application.
Forcing of binary inputs and outputs is a convenient way to test wiring in
substations as well as testing configuration logic in the IEDs. Basically it means
that all binary inputs and outputs on the IED I/O modules (BOM, BIM and IOM)
can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a
secure solution for enforcing access control to IEDs and other systems within a
substation. This incorporates management of user accounts, roles and certificates
and the distribution of such, a procedure completely transparent to the user.
The Flexible Product Naming allows the customer to use an IED-vendor
independent IEC 61850 model of the IED. This customer model will be used as the
1MRK 505 383-UEN A
Section 2
Application
Breaker protection REQ650 2.2 IEC
23
Application manual
IEC 61850 data model, but all other aspects of the IED will remain unchanged
(e.g., names on the local HMI and names in the tools). This offers significant
flexibility to adapt the IED to the customers' system and standard solution.
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1
The following tables list all the functions available in the IED.
Those functions that are not exposed to the user or do not need to
be configured are not described in this manual.
2.2
Back-up protection functions
GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
Current protection
PHPIOC
50
Instantaneous phase overcurrent protection
1
OC4PTOC
51_671)
Directional phase overcurrent protection, four steps
1
EFPIOC
50N
Instantaneous residual overcurrent protection
1
EF4PTOC
51N
67N2)
Directional residual overcurrent protection, four steps
1
NS4PTOC
46I2
Four step directional negative phase sequence overcurrent protection
1
LCPTTR
26
Thermal overload protection, one time constant, Celsius
1
LFPTTR
26
Thermal overload protection, one time constant, Fahrenheit
1
CCRBRF
50BF
Breaker failure protection
1
STBPTOC
50STB
Stub protection
1
CCPDSC
52PD
Pole discordance protection
1
BRCPTOC
46
Broken conductor check
1
Voltage protection
UV2PTUV
27
Two step undervoltage protection
1
OV2PTOV
59
Two step overvoltage protection
1
ROV2PTOV
59N
Two step residual overvoltage protection
1
LOVPTUV
27
Loss of voltage check
1
1)
67 requires voltage
2)
67N requires voltage
Section 2
1MRK 505 383-UEN A
Application
24
Breaker protection REQ650 2.2 IEC
Application manual
Control and monitoring functions
GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v15
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
Control
SESRSYN
25
Synchrocheck, energizing check and synchronizing
1
SMBRREC
79
Autorecloser
1
QCBAY
Bay control
1
LOCREM
Handling of LR-switch positions
1
LOCREMCTRL
LHMI control of PSTO
1
SXCBR
Circuit breaker
3
SCILO
Interlocking
1
SCSWI
Switch controller
5
SXSWI
Circuit switch
3
XLNPROXY
Proxy for signals from switching device via GOOSE
4
SLGAPC
Logic rotating switch for function selection and LHMI presentation
15
VSGAPC
Selector mini switch
30
DPGAPC
Generic communication function for Double Point indication
16
SPC8GAPC
Single point generic control function 8 signals
5
AUTOBITS
Automation bits, command function for DNP3.0
3
SINGLECMD
Single command, 16 signals
4
I103CMD
Function commands for IEC 60870-5-103
1
I103GENCMD
Function commands generic for IEC 60870-5-103
50
I103POSCMD
IED commands with position and select for IEC 60870-5-103
50
I103POSCMDV
IED direct commands with position for IEC 60870-5-503
50
I103IEDCMD
IED commands for IEC 60870-5-103
1
I103USRCMD
Function commands user defined for IEC 60870-5-103
4
Secondary system supervision
CCSSPVC
87
Current circuit supervison
1
FUFSPVC
Fuse failure supervision
1
Logic
SMPPTRC
94
Tripping logic
6
SMAGAPC
General start matrix block
6
STARTCOMB
Start combinator
32
TMAGAPC
Trip matrix logic
12
ALMCALH
Logic for group alarm
5
WRNCALH
Logic for group warning
5
INDCALH
Logic for group indication
5
Table continues on next page
1MRK 505 383-UEN A
Section 2
Application
Breaker protection REQ650 2.2 IEC
25
Application manual
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
AND, GATE, INV,
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Basic configurable logic blocks (see Table 2)
40–420
FXDSIGN
Fixed signal function block
1
B16I
Boolean to integer conversion, 16 bit
18
BTIGAPC
Boolean to integer conversion with logical node representation, 16 bit
16
IB16
Integer to Boolean 16 conversion
18
ITBGAPC
Integer to Boolean 16 conversion with Logic Node representation
16
TEIGAPC
Elapsed time integrator with limit transgression and overflow
supervision
12
INTCOMP
Comparator for integer inputs
30
REALCOMP
Comparator for real inputs
30
Table 2:
Total number of instances for basic configurable logic blocks
Basic configurable logic block
Total number of instances
AND
280
GATE
40
INV
420
LLD
40
OR
298
PULSETIMER
40
RSMEMORY
40
SRMEMORY
40
TIMERSET
60
XOR
40
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
Monitoring
CVMMXN
Power system measurement
6
CMMXU
Current measurement
10
VMMXU
Voltage measurement phase-phase
6
CMSQI
Current sequence measurement
6
VMSQI
Voltage sequence measurement
6
VNMMXU
Voltage measurement phase-earth
6
AISVBAS
General service value presentation of analog inputs
1
Table continues on next page
Section 2
1MRK 505 383-UEN A
Application
26
Breaker protection REQ650 2.2 IEC
Application manual
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
SSIMG
63
Insulation supervision for gas medium
21
SSIML
71
Insulation supervision for liquid medium
3
SSCBR
Circuit breaker condition monitoring
3
EVENT
Event function
20
DRPRDRE,
A1RADR-
A4RADR,
B1RBDR-
B22RBDR
Disturbance report
1
SPGAPC
Generic communication function for single point indication
64
SP16GAPC
Generic communication function for single point indication 16 inputs
16
MVGAPC
Generic communication function for measured values
24
BINSTATREP
Logical signal status report
3
RANGE_XP
Measured value expander block
66
I103MEAS
Measurands for IEC 60870-5-103
1
I103MEASUSR
Measurands user defined signals for IEC 60870-5-103
3
I103AR
Function status auto-recloser for IEC 60870-5-103
1
I103EF
Function status earth-fault for IEC 60870-5-103
1
I103FLTPROT
Function status fault protection for IEC 60870-5-103
1
I103IED
IED status for IEC 60870-5-103
1
I103SUPERV
Supervision status for IEC 60870-5-103
1
I103USRDEF
Status for user defined signals for IEC 60870-5-103
20
L4UFCNT
Event counter with limit supervision
30
TEILGAPC
Running hour meter
6
Metering
PCFCNT
Pulse-counter logic
16
ETPMMTR
Function for energy calculation and demand handling
6
2.4
Communication
GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v15
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
Station communication
LONSPA, SPA
SPA communication protocol
1
ADE
LON communciation protocol
1
HORZCOMM
Network variables via LON
1
Table continues on next page
1MRK 505 383-UEN A
Section 2
Application
Breaker protection REQ650 2.2 IEC
27
Application manual
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
PROTOCOL
Operation selection between SPA and IEC 60870-5-103 for SLM
1
RS485PROT
Operation selection for RS485
1
RS485GEN
RS485
1
DNPGEN
DNP3.0 communication general protocol
1
CHSERRS485
DNP3.0 for EIA-485 communication protocol
1
CH1TCP, CH2TCP,
CH3TCP, CH4TCP
DNP3.0 for TCP/IP communication protocol
1
CHSEROPT
DNP3.0 for TCP/IP and EIA-485 communication protocol
1
MSTSER
DNP3.0 serial master
1
MST1TCP,
MST2TCP,
MST3TCP,
MST4TCP
DNP3.0 for TCP/IP communication protocol
1
DNPFREC
DNP3.0 fault records for TCP/IP and EIA-485 communication protocol
1
IEC 61850-8-1
IEC 61850
1
GOOSEINTLKRCV
Horizontal communication via GOOSE for interlocking
59
GOOSEBINRCV
GOOSE binary receive
16
GOOSEDPRCV
GOOSE function block to receive a double point value
64
GOOSEINTRCV
GOOSE function block to receive an integer value
32
GOOSEMVRCV
GOOSE function block to receive a measurand value
60
GOOSESPRCV
GOOSE function block to receive a single point value
64
GOOSEXLNRCV
GOOSE function block to receive a switching device
9
MULTICMDRCV/
MULTICMDSND
Multiple command and transmit
60/10
OPTICAL103
IEC 60870-5-103 Optical serial communication
1
RS485103
IEC 60870-5-103 serial communication for RS485
1
AGSAL
Generic security application component
1
LD0LLN0
IEC 61850 LD0 LLN0
1
SYSLLN0
IEC 61850 SYS LLN0
1
LPHD
Physical device information
1
PCMACCS
IED configuration protocol
1
SECALARM
Component for mapping security events on protocols such as DNP3
and IEC103
1
FSTACCS
Field service tool access
1
IEC 61850-9-2 Process bus communication, 4 merging units
1-P31
ACTIVLOG
Activity logging
1
ALTRK
Service tracking
1
PRP
IEC 62439-3 Parallel redundancy protocol
1-P23
HSR
IEC 62439-3 High-availability seamless redundancy
1-P24
PTP
Precision time protocol
1
Table continues on next page
Section 2
1MRK 505 383-UEN A
Application
28
Breaker protection REQ650 2.2 IEC
Application manual
IEC 61850 or
function name
ANSI
Function description
Breaker
REQ650 (B11)
FRONTSTATUS
Access point diagnostic for front Ethernet port
1
SCHLCCH
Access point diagnostic for non-redundant Ethernet port
4
RCHLCCH
Access point diagnostic for redundant Ethernet ports
2
DHCP
DHCP configuration for front access point
1
QUALEXP
IEC 61850 quality expander
32
2.5
Basic IED functions
GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v12
Table 3:
Basic IED functions
IEC 61850 or function
name
Description
INTERRSIG
Self supervision with internal event list
TIMESYNCHGEN
Time synchronization module
BININPUT,
SYNCHCAN,
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA
Time synchronization
PTP
Precision time protocol
TIMEZONE
Time synchronization
IRIG-B
Time synchronization
SETGRPS
Number of setting groups
ACTVGRP
Parameter setting groups
TESTMODE
Test mode functionality
CHNGLCK
Change lock function
SMBI
Signal matrix for binary inputs
SMBO
Signal matrix for binary outputs
SMAI1 - SMAI12
Signal matrix for analog inputs
3PHSUM
Summation block 3 phase
ATHSTAT
Authority status
ATHCHCK
Authority check
AUTHMAN
Authority management
FTPACCS
FTP access with password
GBASVAL
Global base values for settings
ALTMS
Time master supervision
ALTIM
Time management
COMSTATUS
Protocol diagnostic
1MRK 505 383-UEN A
Section 2
Application
Breaker protection REQ650 2.2 IEC
29
Application manual
Local HMI functions
IEC 61850 or function
name
ANSI
Description
LHMICTRL
Local HMI signals
LANGUAGE
Local human machine language
SCREEN
Local HMI Local human machine screen behavior
FNKEYTY1–FNKEYTY5
FNKEYMD1–
FNKEYMD5
Parameter setting function for HMI in PCM600
LEDGEN
General LED indication part for LHMI
OPENCLOSE_LED
LHMI LEDs for open and close keys
GRP1_LED1–
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15
Basic part for CP HW LED indication module
Section 2
1MRK 505 383-UEN A
Application
30
Breaker protection REQ650 2.2 IEC
Application manual
Description of configuration REQ650
3.1.1
Introduction
GUID-79B8BC84-4AAB-44E7-86CD-FF63098B009D v2
The basic delivery includes one binary input module and one binary output
module, which is sufficient for the default configured IO to trip and close circuit
breaker. All IEDs can be reconfigured with the help of the application
configuration tool in PCM600. The IED can be adapted to special applications and
special logic can be developed, such as logic for automatic opening of
disconnectors and closing of ring bays, automatic load transfer from one busbar to
the other, and so on.
The basic IED configuration is provided with the signal matrix, single line diagram
and the application configuration prepared for the functions included in the product
by default. All parameters should be verified by the customer, since these are
specific to the system, object or application. Optional functions and optional IO
ordered will not be configured at delivery. It should be noted that the standard only
includes one binary input and one binary output module and only the key functions
such as tripping are connected to the outputs in the signal matrix tool. The required
total IO must be calculated and specified at ordering.
The configurations are as far as found necessary provided with application
comments to explain why the signals have been connected in the special way. On
request, ABB is available to support the re-configuration work, either directly or to
do the design checking.
3.1.1.1
Description of B11
GUID-D9C6EAEB-A4EA-49BF-BE90-CC3CAF1CA476 v1
A breaker bay connecting a transmission line to a busbar, with back-up protection
functions enabling single or three phase trip.
1MRK 505 383-UEN A
Section 3
Configuration
Breaker protection REQ650 2.2 IEC
31
Application manual
REQ650 B11 – Single breaker with single phase tripping
12AI (7I+5U)
CC RBRF
50BF 3I>BF
EF4 PTOC
51N_67N 4(IN>)
EF PIOC
50N
IN>>
PH PIOC
50
3I>>
VN MMXU
MET
UN
VN MMXU
MET
UN
S SIMG
63
S SIML
71
WA2_VT
WA1_VT
LINE_CT
LINE_VT
SMP PTRC
94
1->0
SMB RREC
79
5(0→1)
SMP PTRC
94
1→0
SES RSYN
25
SC/VC
UV2 PTUV
27
2(3U<)
V MSQI
MET
Usqi
VN MMXU
MET
UN
V MMXU
MET
U
FUF SPVC
U>/I<
DRP RDRE
DFR/SER DR
C MMXU
MET
I
C MSQI
MET
Isqi
ETP MMTR
MET W/Varh
CV MMXN
MET
P/Q
Other Functions available from the function library
CCS SPVC
87
INd/I
BRC PTOC
46
lub
LC PTTR
26
q>
LOV PTUV
27
NS4 PTOC
46I2
ROV2 PTOV
59N
3U0
OV2 PTOV
59
3U>
OC4 PTOC
51_67 4(3I>)
IEC10000323-6-en.vsd
STB PTOC
50STB 3I>STB
LF PTTR
26
θ>
S CILO
3
Control
S CSWI
3
Control
S XSWI
3
Control
Q CBAY
3
Control
S SCBR
S SCBR
S SCBR
Control
CC PDSC
52PD
PD
S XCBR
3
Control
S XCBR
3
Control
S XCBR
3
Control
IEC10000323 V6 EN-US
Figure 2:
Configuration diagram for configuration B11
Section 3
1MRK 505 383-UEN A
Configuration
32
Breaker protection REQ650 2.2 IEC
Application manual
Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all
directional and differential functions, the directions of the input currents must be
defined in order to reflect the way the current transformers are installed/connected
in the field ( primary and secondary connections ). Measuring and protection
algorithms in the IED use primary system quantities. Setting values are in primary
quantities as well and it is important to set the data about the connected current and
voltage transformers properly.
An AISVBAS reference PhaseAngleRef can be defined to facilitate service values
reading. This analog channel's phase angle will always be fixed to zero degrees and
remaining analog channel's phase angle information will be shown in relation to
this analog input. During testing and commissioning of the IED, the reference
channel can be changed to facilitate testing and service values reading.
The IED has the ability to receive analog values from primary
equipment, that are sampled by Merging units (MU) connected to a
process bus, via the IEC 61850-9-2 LE protocol.
The availability of VT inputs depends on the ordered transformer
input module (TRM) type.
4.2
Setting guidelines
SEMOD55068-1 v1
SEMOD130348-4 v4
The available setting parameters related to analog inputs are
depending on the actual hardware (TRM) and the logic
configuration made in PCM600.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
33
Application manual
Setting of the phase reference channel
SEMOD55055-5 v3
All phase angles are calculated in relation to a defined reference. An appropriate
analog input channel is selected and used as phase reference. The parameter
PhaseAngleRef defines the analog channel that is used as phase angle reference.
4.2.1.1
Example
SEMOD55055-11 v5
4.2.2
Setting of current channels
SEMOD55055-16 v6
The direction of a current to the IED is depending on the connection of the CT.
Unless indicated otherwise, the main CTs are supposed to be star connected and
can be connected with the earthing point to the object or from the object. This
information must be set in the IED. The convention of the directionality is defined
as follows: A positive value of current, power, and so on means that the quantity
has the direction into the object and a negative value means direction out from the
object. For directional functions the direction into the object is defined as Forward
and the direction out from the object is defined as Reverse. See Figure 3
A positive value of current, power, and so on (forward) means that the quantity
flows towards the object. A negative value of current, power, and so on (reverse)
means that the quantity flows away from the object. See Figure 3.
Protected Object
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN-US
Figure 3:
Internal convention of the directionality in the IED
With correct setting of the primary CT direction, CTStarPoint set to FromObject or
ToObject, a positive quantities always flowing towards the protected object and a
direction defined as Forward always is looking towards the protected object. The
following examples show the principle.
4.2.2.1
Example 1
SEMOD55055-23 v6
Two IEDs used for protection of two objects.
Section 4
1MRK 505 383-UEN A
Analog inputs
34
Breaker protection REQ650 2.2 IEC
Application manual
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IEC05000753=IEC05
000753=1=en=Origin
al[1].vsd
Is
Is
Ip
Ip
Ip
IED
IED
IEC05000753 V2 EN-US
Figure 4:
Example how to set CTStarPoint parameters in the IED
Figure 4 shows the normal case where the objects have their own CTs. The settings
for CT direction shall be done according to the figure. To protect the line, direction
of the directional functions of the line protection shall be set to Forward. This
means that the protection is looking towards the line.
4.2.2.2
Example 2
SEMOD55055-29 v7
Two IEDs used for protection of two objects and sharing a CT.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
35
Application manual
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED
IED
IEC05000460 V2 EN-US
Figure 5:
Example how to set CTStarPoint parameters in the IED
This example is similar to example 1, but here the transformer is feeding just one
line and the line protection uses the same CT as the transformer protection does.
The CT direction is set with different reference objects for the two IEDs though it
is the same current from the same CT that is feeding the two IEDs. With these
settings, the directional functions of the line protection shall be set to Forward to
look towards the line.
4.2.2.3
Example 3
SEMOD55055-35 v7
One IED used to protect two objects.
Section 4
1MRK 505 383-UEN A
Analog inputs
36
Breaker protection REQ650 2.2 IEC
Application manual
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Reverse
Forward
Definition of direction
for directional
line functions
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IED
IEC05000461 V2 EN-US
Figure 6:
Example how to set CTStarPoint parameters in the IED
In this example, one IED includes both transformer and line protections and the
line protection uses the same CT as the transformer protection does. For both
current input channels, the CT direction is set with the transformer as reference
object. This means that the direction Forward for the line protection is towards the
transformer. To look towards the line, the direction of the directional functions of
the line protection must be set to Reverse. The direction Forward/Reverse is related
to the reference object that is the transformer in this case.
When a function is set to Reverse and shall protect an object in reverse direction, it
shall be noted that some directional functions are not symmetrical regarding the
reach in forward and reverse direction. It is in first hand the reach of the directional
criteria that can differ. Normally it is not any limitation but it is advisable to have it
in mind and check if it is acceptable for the application in question.
If the IED has sufficient number of analog current inputs, an alternative solution is
shown in Figure 7. The same currents are fed to two separate groups of inputs and
the line and transformer protection functions are configured to the different inputs.
The CT direction for the current channels to the line protection is set with the line
as reference object and the directional functions of the line protection shall be set to
Forward to protect the line.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
37
Application manual
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional
line functions
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED
IEC05000462 V2 EN-US
Figure 7:
Example how to set CTStarPoint parameters in the IED
Figure 8:
For busbar protection, it is possible to set the CTStarPoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in Figure 8, set CTStarPoint = ToObject, and for all CT
inputs marked with 2 in Figure 8, set CTStarPoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that
case for all CT inputs marked with 1 in Figure 8, set CTStarPoint = FromObject,
and for all CT inputs marked with 2 in Figure 8, set CTStarPoint = ToObject.
Regardless which one of the above two options is selected, busbar differential
protection will behave correctly.
The main CT ratios must also be set. This is done by setting the two parameters
CTsec and CTprim for each current channel. For a 1000/1 A CT, the following
settings shall be used:
•
CTprim = 1000 (value in A)
•
CTsec =1 (value in A).
Section 4
1MRK 505 383-UEN A
Analog inputs
38
Breaker protection REQ650 2.2 IEC
Application manual
Examples on how to connect, configure and set CT inputs for most
commonly used CT connections
SEMOD55055-296 v7
Figure 9 defines the marking of current transformer terminals commonly used
around the world:
In the SMAI function block, you have to set if the SMAI block is
measuring current or voltage. This is done with the parameter:
AnalogInputType: Current/Voltage. The ConnectionType: phase -
phase/phase-earth and GlobalBaseSel.
ISec
IPri
S1 (X1)
P1
(H1)
P2
(H2)
S2 (X2)
P2
(H2)
P1
(H1)
x
x
a)
b)
c)
en06000641.vsd
S2 (X2)
S1 (X1)
IEC06000641 V1 EN-US
Figure 9:
Commonly used markings of CT terminals
Where:
a)
is symbol and terminal marking used in this document. Terminals marked with a square
indicates the primary and secondary winding terminals with the same (that is, positive)
polarity
b) and
c)
are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that
for these two cases the CT polarity marking is correct!
It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
•
1A
•
5A
However, in some cases, the following rated secondary currents are used as well:
•
2A
•
10A
The IED fully supports all of these rated secondary values.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
39
Application manual
It is recommended to:
•
use 1A rated CT input into the IED in order to connect CTs
with 1A and 2A secondary rating
•
use 5A rated CT input into the IED in order to connect CTs
with 5A and 10A secondary rating
4.2.2.5
Example on how to connect a star connected three-phase CT set to
the IED
SEMOD55055-352 v11
Figure 10 gives an example about the wiring of a star connected two-phase CT set
to the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the
IED as well.
For correct terminal designations, see the connection diagrams
valid for the delivered IED.
L1
IL1
IL2
IL3
L2
L3
Protected Object
CT 600/5
Star Connected
IL1
IL2
IL3
IED
IEC13000002-4-en.vsdx
1
2
3
4
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
5
IN
IEC13000002 V4 EN-US
Figure 10:
Star connected three-phase CT set with star point towards the protected object
Section 4
1MRK 505 383-UEN A
Analog inputs
40
Breaker protection REQ650 2.2 IEC
Application manual
The drawing shows how to connect three individual phase currents from a star connected
three-phase CT set to the three CT inputs of the IED.
2)
The current inputs are located in the TRM. It shall be noted that for all these current inputs
the following setting values shall be entered for the example shown in Figure 10.
•
CTprim=600A
•
CTsec=5A
•
CTStarPoint=ToObject
Ratio of the first two parameters is only used inside the IED. The third parameter
(CTStarPoint=ToObject) as set in this example causes no change on the measured
currents. In other words, currents are already measured towards the protected object.
3)
These three connections are the links between the three current inputs and the three input
channels of the preprocessing function block 4). Depending on the type of functions, which
need this current information, more than one preprocessing block might be connected in
parallel to the same three physical CT inputs.
4)
The preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all three input channels
•
harmonic content for all three input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block. For this
application most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in power plants), then the setting parameters DFTReference shall be set
accordingly.
Section SMAI in this manual provides information on adaptive frequency tracking for the
signal matrix for analogue inputs (SMAI).
5)
AI3P in the SMAI function block is a grouped signal which contains all the data about the
phases L1, L2, L3 and neutral quantity; in particular the data about fundamental frequency
phasors, harmonic content and positive sequence, negative and zero sequence quantities
are available.
AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain the
fundamental frequency phasors and the harmonic content of the corresponding input
channels of the preprocessing function block.
AIN is the signal which contains the fundamental frequency phasors and the harmonic
content of the neutral quantity. In this example, GRP2N is not connected so this data is
calculated by the preprocessing function block on the basis of the inputs GRPL1, GRPL2
and GRPL3. If GRP2N is connected, the data reflects the measured value of GRP2N.
Another alternative is to have the star point of the three-phase CT set as shown in
Figure 11:
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
41
Application manual
IEC11000026 V4 EN-US
Figure 11:
Star connected three-phase CT set with its star point away from the protected object
In the example, everything is done in a similar way as in the above described
example (Figure 10). The only difference is the setting of the parameter
CTStarPoint of the used current inputs on the TRM (item 2 in Figure 11 and 10):
•
CTprim=600A
•
CTsec=5A
•
CTStarPoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third
parameter as set in this example will negate the measured currents in order to
ensure that the currents are measured towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the three-phase CT
set connected to the IED as shown in Figure 11.
Section 4
1MRK 505 383-UEN A
Analog inputs
42
Breaker protection REQ650 2.2 IEC
Application manual
IEC06000644 V4 EN-US
Figure 12:
Star connected three-phase CT set with its star point away from the protected object and the
residual/neutral current connected to the IED
Where:
1)
Shows how to connect three individual phase currents from a star connected three-phase
CT set to the three CT inputs of the IED.
2)
Shows how to connect residual/neutral current from the three-phase CT set to the fourth
input in the IED. It shall be noted that if this connection is not made, the IED will still
calculate this current internally by vectorial summation of the three individual phase
currents.
3)
Is the TRM where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
•
CTprim=800A
•
CTsec=1A
•
CTStarPoint=FromObject
•
ConnectionType=Ph-N
The ratio of the first two parameters is only used inside the IED. The third parameter as set
in this example will have no influence on measured currents (that is, currents are already
measured towards the protected object).
4)
Are three connections made in the Signal Matrix tool (SMT) and Application configuration
tool (ACT), which connects these three current inputs to the first three input channels on
the preprocessing function block 6). Depending on the type of functions, which need this
current information, more than one preprocessing block might be connected in parallel to
these three CT inputs.
Table continues on next page
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
43
Application manual
Is a connection made in the Signal Matrix tool (SMT) and Application configuration tool
(ACT), which connects the residual/neutral current input to the fourth input channel of the
preprocessing function block 6). Note that this connection in SMT shall not be done if the
residual/neutral current is not connected to the IED.
6)
Is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all input channels
•
harmonic content for all input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors of the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application, most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations), then the setting parameters DFTReference
shall be set accordingly.
4.2.2.6
Example how to connect delta connected three-phase CT set to the
IED
SEMOD55055-392 v7
Figure 13 gives an example how to connect a delta connected three-phase CT set to
the IED. It gives an overview of the required actions by the user in order to make
this measurement available to the built-in protection and control functions in the
IED as well.
For correct terminal designations, see the connection diagrams
valid for the delivered IED.
Section 4
1MRK 505 383-UEN A
Analog inputs
44
Breaker protection REQ650 2.2 IEC
Application manual
IEC11000027 V3 EN-US
Figure 13:
Delta DAB connected three-phase CT set
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
45
Application manual
shows how to connect three individual phase currents from a delta connected three-phase
CT set to three CT inputs of the IED.
2)
is the TRM where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
CTprim=600A
CTsec=5A
•
CTStarPoint=ToObject
•
ConnectionType=Ph-Ph
3)
are three connections made in Signal Matrix Tool (SMT), Application configuration tool
(ACT), which connect these three current inputs to first three input channels of the
preprocessing function block 4). Depending on the type of functions which need this
current information, more then one preprocessing block might be connected in parallel to
these three CT inputs.
4)
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all three input channels
•
harmonic content for all three input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block. For this
application most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
Another alternative is to have the delta connected CT set as shown in figure 14:
Section 4
1MRK 505 383-UEN A
Analog inputs
46
Breaker protection REQ650 2.2 IEC
Application manual
IEC11000028 V3 EN-US
Figure 14:
Delta DAC connected three-phase CT set
In this case, everything is done in a similar way as in the above described example,
except that for all used current inputs on the TRM the following setting parameters
shall be entered:
CTprim=800A
CTsec=1A
•
CTStarPoint=ToObject
•
ConnectionType=Ph-Ph
It is important to notice the references in SMAI. As inputs at Ph-Ph are expected to
be L1L2, L2L3 respectively L3L1 we need to tilt 180º by setting ToObject.
4.2.2.7
Example how to connect single-phase CT to the IED
SEMOD55055-431 v8
Figure 15 gives an example how to connect the single-phase CT to the IED. It
gives an overview of the required actions by the user in order to make this
measurement available to the built-in protection and control functions within the
IED as well.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
47
Application manual
For correct terminal designations, see the connection diagrams
valid for the delivered IED.
Protected Object
L1
L2
L3
IED
INP
INS
INS
2
IEC11000029-4-en.vsdx
4
3
CT 1000/1
a)
b)
(+)
(+)
(-)
(-)
(+)
(-)
1
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC11000029 V4 EN-US
Figure 15:
Connections for single-phase CT input
Where:
1)
shows how to connect single-phase CT input in the IED.
2)
is TRM where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
For connection (a) shown in Fgure 15:
CTprim= 1000 A
CTsec= 1A
CTStarPoint=ToObject
For connection (b) shown in Figure 15:
CTprim= 1000 A
CTsec= 1A
CTStarPoint=FromObject
3)
shows the connection made in SMT tool, which connect this CT input to the fourth input
channel of the preprocessing function block 4).
4)
is a Preprocessing block that has the task to digitally filter the connected analog inputs
and calculate values. The calculated values are then available for all built-in protection
and control functions within the IED, which are connected to this preprocessing
function block.
If frequency tracking and compensation is required (this feature is typically required
only for IEDs installed in the power plants) then the setting parameters DFTReference
shall be set accordingly.
Section 4
1MRK 505 383-UEN A
Analog inputs
48
Breaker protection REQ650 2.2 IEC
Application manual
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection
IED
GUID-8EB19363-9178-4F04-A6AC-AF0C2F99C5AB v1
Note that for all line protection applications (e.g. distance protection or line
differential protection) the parameter Base Current (i.e. IBase setting in the IED)
used by the relevant protection function, shall always be set equal to the largest
rated CT primary current among all CTs involved in the protection scheme. The
rated CT primary current value is set as parameter CTPrim under the IED TRM
settings.
For all other protection applications (e.g. generator, shunt reactor, shunt capacitor
and transformer protection) it is typically desirable to set IBase parameter equal to
the rated current of the protected object. However this is only recommended to do
if the rated current of the protected object is within the range of 40% to 120% of
the selected CT rated primary current. If for any reason (e.g. high maximum short
circuit current) the rated current of the protected object is less than 40% of the
rated CT primary current, it is strongly recommended to set the parameter IBase in
the IED to be equal to the largest rated CT primary current among all CTs involved
in the protection scheme and installed on the same voltage level. This will
effectively make the protection scheme less sensitive; however, such measures are
necessary in order to avoid possible problems with loss of the measurement
accuracy in the IED.
Regardless of the applied relationship between the IBase parameter and the rated
CT primary current, the corresponding minimum pickup of the function on the CT
secondary side must always be verified. It is strongly recommended that the
minimum pickup of any instantaneous protection function (e.g. differential,
restricted earth fault, distance, instantaneous overcurrent, etc.) shall under no
circumstances be less than 4% of the used IED CT input rating (i.e. 1A or 5A).
This corresponds to 40mA secondary for IED 1A rated inputs and to 200mA
secondary for IED 5A rated inputs used by the function. This shall be individually
verified for all current inputs involved in the protection scheme.
Note that exceptions from the above 4% rule may be acceptable for very special
applications (e.g. when Multipurpose filter SMAIHPAC is involved in the
protection scheme).
4.2.4
Setting of voltage channels
SEMOD55055-44 v4
As the IED uses primary system quantities, the main VT ratios must be known to
the IED. This is done by setting the two parameters VTsec and VTprim for each
voltage channel. The phase-to-phase value can be used even if each channel is
connected to a phase-to-earth voltage from the VT.
4.2.4.1
Example
SEMOD55055-47 v3
Consider a VT with the following data:
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
49
Application manual
EQUATION2016 V1 EN-US
(Equation 1)
The following setting should be used: VTprim=132 (value in kV) VTsec=110
(value in V)
4.2.4.2
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
SEMOD55055-60 v6
Figure 16 defines the marking of voltage transformer terminals commonly used
around the world.
A
(H1)
B
(H2)
b
(X2)
a
(X1)
A
(H1)
N
(H2)
n
(X2)
a
(X1)
b)
c)
A
(H1)
N
(H2)
dn
(X2)
da
(X1)
d)
UPri
+
+
USec
a)
en06000591.vsd
IEC06000591 V1 EN-US
Figure 16:
Commonly used markings of VT terminals
Where:
a)
is the symbol and terminal marking used in this document. Terminals marked with a
square indicate the primary and secondary winding terminals with the same (positive)
polarity
b)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
earth connected VTs
c)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
phase connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
•
100 V
•
110 V
•
115 V
•
120 V
•
230 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
Section 4
1MRK 505 383-UEN A
Analog inputs
50
Breaker protection REQ650 2.2 IEC
Application manual
Examples on how to connect a three phase-to-earth connected VT to
the IED
SEMOD55055-87 v9
Figure 17 gives an example on how to connect a three phase-to-earth connected VT
to the IED. It gives an overview of required actions by the user in order to make
this measurement available to the built-in protection and control functions within
the IED.
For correct terminal designations, see the connection diagrams
valid for the delivered IED.
L1
IED
L2
L3
66
3
110
3
kV
V
1
3
2
66
3
110
3
kV
V
66
3
110
3
kV
V
.
#Not used
5
IEC06000599-4-en.vsdx
4
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC06000599 V4 EN-US
Figure 17:
A Three phase-to-earth connected VT
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
51
Application manual
IEC16000140 V1 EN-US
Figure 18:
A two phase-to-earth connected VT
Where:
1)
shows how to connect three secondary phase-to-earth voltages to three VT inputs on
the IED
2)
is the TRM where these three voltage inputs are located. For these three voltage
inputs, the following setting values shall be entered:
VTprim =132 kV
VTsec = 110 V
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual VT.
66
66
3
110
110
3
=
EQUATION1903 V1 EN-US
(Equation 2)
Table continues on next page
Section 4
1MRK 505 383-UEN A
Analog inputs
52
Breaker protection REQ650 2.2 IEC
Application manual
are three connections made in Signal Matrix Tool (SMT), which connect these three
voltage inputs to first three input channels of the preprocessing function block 5).
Depending on the type of functions which need this voltage information, more then one
preprocessing block might be connected in parallel to these three VT inputs.
4)
shows that in this example the fourth (that is, residual) input channel of the
preprocessing block is not connected in SMT tool. Thus the preprocessing block will
automatically calculate 3Uo inside by vectorial sum from the three phase to earth
voltages connected to the first three input channels of the same preprocessing block.
Alternatively, the fourth input channel can be connected to open delta VT input, as
shown in Figure 20.
5)
is a Preprocessing block that has the task to digitally filter the connected analog inputs
and calculate:
•
fundamental frequency phasors for all input channels
•
harmonic content for all input channels
•
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control
functions within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to
the default values. However the following settings shall be set as shown here:
UBase=66 kV (that is, rated Ph-Ph voltage)
If frequency tracking and compensation is required (this feature is typically required
only for IEDs installed in the generating stations) then the setting parameters
DFTReference shall be set accordingly.
4.2.4.4
Example on how to connect a phase-to-phase connected VT to the
IED
SEMOD55055-134 v7
Figure 19 gives an example how to connect a phase-to-phase connected VT to the
IED. It gives an overview of the required actions by the user in order to make this
measurement available to the built-in protection and control functions within the
IED. It shall be noted that this VT connection is only used on lower voltage levels
(that is, rated primary voltage below 40 kV).
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
53
Application manual
IEC06000600 V5 EN-US
Figure 19:
A Two phase-to-phase connected VT
Where:
1)
shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on the
IED
2)
is the TRM where these three voltage inputs are located. It shall be noted that for these
three voltage inputs the following setting values shall be entered:
VTprim=13.8 kV
VTsec=120 V
Please note that inside the IED only ratio of these two parameters is used.
Table continues on next page
Section 4
1MRK 505 383-UEN A
Analog inputs
54
Breaker protection REQ650 2.2 IEC
Application manual
are three connections made in the Signal Matrix tool (SMT), Application configuration tool
(ACT), which connects these three voltage inputs to first three input channels of the
preprocessing function block 5). Depending on the type of functions, which need this
voltage information, more than one preprocessing block might be connected in parallel to
these three VT inputs
4)
shows that in this example the fourth (that is, residual) input channel of the preprocessing
block is not connected in SMT. Note. If the parameters UL1, UL2, UL3, UN should be used
the open delta must be connected here.
5)
Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values. However the following settings shall be set as shown here:
ConnectionType=Ph-Ph
UBase=13.8 kV
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
4.2.4.5
Example on how to connect an open delta VT to the IED for high
impedance earthed or unearthed networks
SEMOD55055-163 v9
Figure 20 gives an example about the wiring of an open delta VT to the IED for
high impedance earthed or unearthed power systems. It shall be noted that this type
of VT connection presents a secondary voltage proportional to 3U0 to the IED.
In case of a solid earth fault close to the VT location the primary value of 3Uo will
be equal to:
3 0
3
3
Ph Ph
Ph N
U
U
U
-
-
=
×
= ×
EQUATION1921 V3 EN-US
(Equation 3)
The primary rated voltage of an open Delta VT is always equal to UPh-E. Three
series connected VT secondary windings gives a secondary voltage equal to three
times the individual VT secondary winding rating. Thus the secondary windings of
open delta VTs quite often have a secondary rated voltage equal to one third of the
rated phase-to-phase VT secondary voltage (110/3V in this particular example).
Figure 20 gives overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the
IED as well.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
55
Application manual
# Not Used
5
IEC06000601-4-en.vsdx
# Not Used
# Not Used
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC06000601 V4 EN-US
Figure 20:
Open delta connected VT in high impedance earthed power system
Section 4
1MRK 505 383-UEN A
Analog inputs
56
Breaker protection REQ650 2.2 IEC
Application manual
shows how to connect the secondary side of the open delta VT to one VT input on the
IED.
+3U0 shall be connected to the IED
2)
is the TRM where this voltage input is located. It shall be noted that for this voltage input
the following setting values shall be entered:
3 6.6
11.43
VTprim
kV
=
×
=
EQUATION1923 V1 EN-US
(Equation 4)
110
sec
3
110
3
VT
V
=
×
=
EQUATION1924 V1 EN-US
(Equation 5)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual open delta VT.
6.6
3 6.6
3
110
110
3
×
=
EQUATION1925 V1 EN-US
(Equation 6)
3)
shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool or ACT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), Application configuration tool
(ACT), which connect this voltage input to the fourth input channel of the preprocessing
function block 5).
5)
is a Preprocessing block that has the task to digitally filter the connected analog input
and calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control
functions within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to
the default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations ) then the setting parameters DFTReference
shall be set accordingly.
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
57
Application manual
Example how to connect the open delta VT to the IED for low
impedance earthed or solidly earthed power systems
SEMOD55055-199 v6
Figure 21 gives an example about the connection of an open delta VT to the IED
for low impedance earthed or solidly earthed power systems. It shall be noted that
this type of VT connection presents secondary voltage proportional to 3U0 to the
IED.
In case of a solid earth fault close to the VT location the primary value of 3Uo will
be equal to:
3
3
Ph
Ph
Ph
E
U
Uo
U
-
-
=
=
EQUATION1926 V1 EN-US
(Equation 7)
The primary rated voltage of such VT is always equal to UPh-E Therefore, three
series connected VT secondary windings will give the secondary voltage equal
only to one individual VT secondary winding rating. Thus the secondary windings
of such open delta VTs quite often has a secondary rated voltage close to rated
phase-to-phase VT secondary voltage, that is, 115V or 115/√3V as in this particular
example. Figure 21 gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the
IED.
Section 4
1MRK 505 383-UEN A
Analog inputs
58
Breaker protection REQ650 2.2 IEC
Application manual
# Not Used
# Not Used
# Not Used
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
2
3
4
5
IEC06000602 V4 EN-US
Figure 21:
Open delta connected VT in low impedance or solidly earthed power system
1MRK 505 383-UEN A
Section 4
Analog inputs
Breaker protection REQ650 2.2 IEC
59
Application manual
shows how to connect the secondary side of open delta VT to one VT input in the
IED.
+3Uo shall be connected to the IED.
2)
is TRM where this voltage input is located. It shall be noted that for this voltage input
the following setting values shall be entered:
3 138
138
3
VTprim
kV
=
×
=
EQUATION1928 V1 EN-US
(Equation 8)
115
sec
3
115
3
VT
V
=
×
=
EQUATION1929 V1 EN-US
(Equation 9)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that
the ratio of the entered values exactly corresponds to ratio of one individual open
delta VT.
138
138
3
115
115
3
=
EQUATION1930 V1 EN-US
(Equation 10)
3)
shows that in this example the first three input channel of the preprocessing block is
not connected in SMT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), which connect this voltage
input to the fourth input channel of the preprocessing function block 4).
5)
preprocessing block has a task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control
functions within the IED, which are connected to this preprocessing function block in
the configuration tool. For this application most of the preprocessing settings can be
left to the default values.
If frequency tracking and compensation is required (this feature is typically required
only for IEDs installed in the generating stations) then the setting parameters
DFTReference shall be set accordingly.
Section 4
1MRK 505 383-UEN A
Analog inputs
60
Breaker protection REQ650 2.2 IEC
Application manual
IEC13000239 V3 EN-US
Figure 22:
Local human-machine interface
The LHMI of the IED contains the following elements:
•
Keypad
•
Display (LCD)
•
LED indicators
•
Communication port for PCM600
1MRK 505 383-UEN A
Section 5
Local HMI
Breaker protection REQ650 2.2 IEC
61
Application manual
The LHMI is used for setting, monitoring and controlling.
5.1
Display
GUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v11
The LHMI includes a graphical monochrome liquid crystal display (LCD) with a
resolution of 320 x 240 pixels. The character size can vary. The amount of
characters and rows fitting the view depends on the character size and the view that
is shown.
The display view is divided into four basic areas.
IEC15000270-1-en.vsdx
IEC15000270 V1 EN-US
Figure 23:
Display layout
1
Path
2
Content
3
Status
4
Scroll bar (appears when needed)
The function key button panel shows on request what actions are possible with the
function buttons. Each function button has a LED indication that can be used as a
Section 5
1MRK 505 383-UEN A
Local HMI
62
Breaker protection REQ650 2.2 IEC
Application manual
feedback signal for the function button control action. The LED is connected to the
required signal with PCM600.
IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US
Figure 24:
Function button panel
The indication LED panel shows on request the alarm text labels for the indication
LEDs. Three indication LED pages are available.
IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US
Figure 25:
Indication LED panel
The function button and indication LED panels are not visible at the same time.
Each panel is shown by pressing one of the function buttons or the Multipage
button. Pressing the ESC button clears the panel from the display. Both panels have
a dynamic width that depends on the label string length.
1MRK 505 383-UEN A
Section 5
Local HMI
Breaker protection REQ650 2.2 IEC
63
Application manual
The LHMI includes three status LEDs above the display: Ready, Start and Trip.
There are 15 programmable indication LEDs on the front of the LHMI. Each LED
can indicate three states with the colors: green, yellow and red. The texts related to
each three-color LED are divided into three panels.
There are 3 separate panels of LEDs available. The 15 physical three-color LEDs
in one LED group can indicate 45 different signals. Altogether, 135 signals can be
indicated since there are three LED groups. The LEDs are lit according to priority,
with red being the highest and green the lowest priority. For example, if on one
panel there is an indication that requires the green LED to be lit, and on another
panel there is an indication that requires the red LED to be lit, the red LED takes
priority and is lit. The LEDs can be configured with PCM600 and the operation
mode can be selected with the LHMI or PCM600.
Information panels for the indication LEDs are shown by pressing the Multipage
button. Pressing that button cycles through the three pages. A lit or un-
acknowledged LED is indicated with a highlight. Such lines can be selected by
using the Up/Down arrow buttons. Pressing the Enter key shows details about the
selected LED. Pressing the ESC button exits from information pop-ups as well as
from the LED panel as such.
The Multipage button has a LED. This LED is lit whenever any LED on any panel
is lit. If there are un-acknowledged indication LEDs, then the Multipage LED
blinks. To acknowledge LEDs, press the Clear button to enter the Reset menu
(refer to description of this menu for details).
There are two additional LEDs which are next to the control buttons
and
. These LEDs can indicate the status of two arbitrary binary signals by
configuring the OPENCLOSE_LED function block. For instance,
OPENCLOSE_LED can be connected to a circuit breaker to indicate the breaker
open/close status on the LEDs.
Section 5
1MRK 505 383-UEN A
Local HMI
64
Breaker protection REQ650 2.2 IEC
Application manual
IEC16000076 V1 EN-US
Figure 26:
OPENCLOSE_LED connected to SXCBR
5.3
Keypad
AMU0600428 v17
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either
as menu shortcut or control buttons.
1MRK 505 383-UEN A
Section 5
Local HMI
Breaker protection REQ650 2.2 IEC
65
Application manual
IEC15000157 V2 EN-US
Figure 27:
LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
1...5
Function button
6
Close
7
Open
8
Escape
9
Left
10
Down
11
Up
12
Right
13
Key
14
Enter
15
Remote/Local
16
Uplink LED
17
Not in use
18
Multipage
19
Menu
Section 5
1MRK 505 383-UEN A
Local HMI
66
Breaker protection REQ650 2.2 IEC
Application manual
Programmable indication LEDs
24
IED status LEDs
5.4
Local HMI functionality
5.4.1
Protection and alarm indication
GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v15
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
The start and trip LEDs are configured via the disturbance recorder.
The yellow and red status LEDs are configured in the disturbance
recorder function, DRPRDRE, by connecting a start or trip signal
from the actual function to a BxRBDR binary input function block
using the PCM600 and configure the setting to Off, Start or Trip for
that particular signal.
Table 5:
Ready LED (green)
LED state
Description
Off
Auxiliary supply voltage is disconnected.
On
Normal operation.
Flashing
Internal fault has occurred.
Table 6:
Start LED (yellow)
LED state
Description
Off
Normal operation.
On
A protection function has started and an indication message is displayed.
The start indication is latching and must be reset via communication,
LHMI or binary input on the LEDGEN component. To open the reset
menu on the LHMI, press
.
Flashing
The IED is in test mode and protection functions are blocked, or the
IEC61850 protocol is blocking one or more functions.
The indication disappears when the IED is no longer in test mode and
blocking is removed. The blocking of functions through the IEC61850
protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The
yellow LED changes to either On or Off state depending on the state of
operation.
1MRK 505 383-UEN A
Section 5
Local HMI
Breaker protection REQ650 2.2 IEC
67
Application manual
Trip LED (red)
LED state
Description
Off
Normal operation.
On
A protection function has tripped. An indication message is displayed if
the auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI
or binary input on the LEDGEN component. To open the reset menu on
the LHMI, press
.
Flasing
Configuration mode.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An
individual alarm/status signal, connected to any of the LED function blocks, can be
assigned to one of the three LED colors when configuring the IED.
Table 8:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
•
Follow-S sequence: The activation signal is on.
•
LatchedColl-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.
•
LatchedAck-S-F sequence: The activation signal is on, or it is off but the
indication has not been acknowledged.
•
LatchedReset-S sequence: The activation signal is on, or it is off but the
indication has not been acknowledged.
Flashing
•
Follow-F sequence: The activation signal is on.
•
LatchedAck-F-S sequence: The activation signal is on, or it is off but the
indication has not been acknowledged.
•
LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.
5.4.2
Parameter management
GUID-5EE466E3-932B-4311-9FE1-76ECD8D6E245 v9
The LHMI is used to access the relay parameters. Three types of parameters can be
read and written.
•
Numerical values
•
String values
•
Enumerated values
Numerical values are presented either in integer or in decimal format with
minimum and maximum values. Character strings can be edited character by
character. Enumerated values have a predefined set of selectable values.
Section 5
1MRK 505 383-UEN A
Local HMI
68
Breaker protection REQ650 2.2 IEC
Application manual
The RJ-45 port in the LHMI enables front communication.
•
The green uplink LED on the left is lit when the cable is successfully
connected to the port.
•
The yellow LED is not used; it is always off.
IEC13000280-1-en.vsd
1
2
GUID-AACFC753-BFB9-47FE-9512-3C4180731A1B V1 EN-US
Figure 28:
RJ-45 communication port and green indicator LED
1
RJ-45 connector
2
Green indicator LED
The default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.254.0. It can be set through the local HMI path Main
menu/Configuration/Communication/Ethernet configuration/FRONT port/
AP_FRONT.
Do not connect the IED front port to a LAN. Connect only a single
local PC with PCM600 to the front port. It is only intended for
temporary use, such as commissioning and testing.
1MRK 505 383-UEN A
Section 5
Local HMI
Breaker protection REQ650 2.2 IEC
69
Application manual
Instantaneous phase overcurrent protection
PHPIOC
IP14506-1 v6
6.1.1
Identification
M14880-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous phase overcurrent
protection
PHPIOC
3I>>
SYMBOL-Z V1 EN-US
50
6.1.2
Application
M12911-3 v6
Long transmission lines often transfer great quantities of electric power from
generation to consumption areas. The unbalance of the produced and consumed
electric power at each end of the transmission line is very large. This means that a
fault on the line can easily endanger the stability of a complete system.
The transient stability of a power system depends mostly on three parameters (at
constant amount of transmitted electric power):
•
The type of the fault. Three-phase faults are the most dangerous, because no
power can be transmitted through the fault point during fault conditions.
•
The magnitude of the fault current. A high fault current indicates that the
decrease of transmitted power is high.
•
The total fault clearing time. The phase angles between the EMFs of the
generators on both sides of the transmission line increase over the permitted
stability limits if the total fault clearing time, which consists of the protection
operating time and the breaker opening time, is too long.
The fault current on long transmission lines depends mostly on the fault position
and decreases with the distance from the generation point. For this reason the
protection must operate very quickly for faults very close to the generation (and
relay) point, for which very high fault currents are characteristic.
The instantaneous phase overcurrent protection PHPIOC can operate in 10 ms for
faults characterized by very high currents.
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
71
Application manual
The parameters for instantaneous phase overcurrent protection PHPIOC are set via
the local HMI or PCM600.
This protection function must operate only in a selective way. So check all system
and transient conditions that could cause its unwanted operation.
Only detailed network studies can determine the operating conditions under which
the highest possible fault current is expected on the line. In most cases, this current
appears during three-phase fault conditions. But also examine single-phase-to-earth
and two-phase-to-earth conditions.
Also study transients that could cause a high increase of the line current for short
times. A typical example is a transmission line with a power transformer at the
remote end, which can cause high inrush current when connected to the network
and can thus also cause the operation of the built-in, instantaneous, overcurrent
protection.
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of base
values.
Operation: Set the protection to On/Off.
OpMode: This parameter can be set to 2 out of 3 or 1 out of 3. The setting controls
the minimum number of phase currents that must be larger than the set operate
current IP>> for operation. Normally this parameter is set to 1 out of 3and will
thus detect all fault types. If the protection is to be used mainly for multi phase
faults, 2 out of 3 should be chosen.
IP>>: Set operate current in % of IB.
IP>>Max and IP>>Min should only be changed if remote setting of operation
current level, IP>>, is used. The limits are used for decreasing the used range of
the IP>> setting. If IP>> is set outside IP>>Max and IP>>Min, the closest of the
limits to IP>> is used by the function. If IP>>Max is smaller than IP>>Min, the
limits are swapped.
StValMult: The set operate current can be changed by activation of the binary input
ENMULT to the set factor StValMult.
6.1.3.1
Meshed network without parallel line
M12915-9 v8
The following fault calculations have to be done for three-phase, single-phase-to-
earth and two-phase-to-earth faults. With reference to Figure 29, apply a fault in B
and then calculate the current through-fault phase current IfB. The calculation
Section 6
1MRK 505 383-UEN A
Current protection
72
Breaker protection REQ650 2.2 IEC
Application manual
should be done using the minimum source impedance values for ZA and the
maximum source impedance values for ZB in order to get the maximum through
fault current from A to B.
~
~
ZA
ZB
Z L
A
B
IED
I fB
Fault
IEC09000022-1-en.vsd
IEC09000022 V1 EN-US
Figure 29:
Through fault current from A to B: IfB
Then a fault in A has to be applied and the through fault current IfA has to be
calculated, Figure 30. In order to get the maximum through fault current, the
minimum value for ZB and the maximum value for ZA have to be considered.
IEC09000023-1-en.vsd
~
~
ZA
ZB
Z L
A
B
IED
I fA
Fault
IEC09000023 V1 EN-US
Figure 30:
Through fault current from B to A: IfA
The IED must not trip for any of the two through-fault currents. Hence the
minimum theoretical current setting (Imin) will be:
Imin
MAX IfA IfB
,
(
)
³
EQUATION78 V1 EN-US
(Equation 11)
A safety margin of 5% for the maximum protection static inaccuracy and a safety
margin of 5% for the maximum possible transient overreach have to be introduced.
An additional 20% is suggested due to the inaccuracy of the instrument
transformers under transient conditions and inaccuracy in the system data.
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
73
Application manual
The minimum primary setting (Is) for the instantaneous phase overcurrent
protection is then:
min
1.3
sI
I
³
×
EQUATION79 V3 EN-US
(Equation 12)
The protection function can be used for the specific application only if this setting
value is equal to or less than the maximum fault current that the IED has to clear, IF
in Figure 31.
IEC09000024-1-en.vsd
~
~
ZA
ZB
Z L
A
B
IED
I F
Fault
IEC09000024 V1 EN-US
Figure 31:
Fault current: IF
100
Is
IP
IBase
>>=
×
EQUATION1147 V3 EN-US
(Equation 13)
6.1.3.2
Meshed network with parallel line
M12915-34 v7
In case of parallel lines, the influence of the induced current from the parallel line
to the protected line has to be considered. One example is given in Figure 32,
where the two lines are connected to the same busbars. In this case the influence of
the induced fault current from the faulty line (line 1) to the healthy line (line 2) is
considered together with the two through fault currents IfA and IfB mentioned
previously. The maximal influence from the parallel line for the IED in Figure 32
will be with a fault at the C point with the C breaker open.
A fault in C has to be applied, and then the maximum current seen from the IED
(IM ) on the healthy line (this applies for single-phase-to-earth and two-phase-to-
earth faults) is calculated.
Section 6
1MRK 505 383-UEN A
Current protection
74
Breaker protection REQ650 2.2 IEC
Application manual
IEC09000025 V1 EN-US
Figure 32:
Two parallel lines. Influence from parallel line to the through fault
current: IM
The minimum theoretical current setting for the overcurrent protection function
(Imin) will be:
Imin
MAX IfA IfB IM
,
,
(
)
³
EQUATION82 V1 EN-US
(Equation 14)
Where IfA and IfB have been described in the previous paragraph. Considering the
safety margins mentioned previously, the minimum setting (Is) for the
instantaneous phase overcurrent protection 3-phase output is then:
Is ³1.3·Imin
EQUATION83 V2 EN-US
(Equation 15)
The protection function can be used for the specific application only if this setting
value is equal or less than the maximum phase fault current that the IED has to
clear.
The IED setting value IP>> is given in percentage of the primary base current
value, IBase. The value for IP>> is given from this formula:
100
Is
IP
IBase
>>=
×
EQUATION1147 V3 EN-US
(Equation 16)
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
75
Application manual
Directional phase overcurrent protection, four steps
OC4PTOC
SEMOD129998-1 v8
6.2.1
Identification
M14885-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional phase overcurrent
protection, four steps
OC4PTOC
TOC-REVA V2 EN-US
51_67
6.2.2
Application
M15335-3 v9
Directional phase overcurrent protection, four steps OC4PTOC is used in several
applications in the power system. Some applications are:
•
Short circuit protection of feeders in distribution and subtransmission systems.
Normally these feeders have a radial structure.
•
Back-up short circuit protection of transmission lines.
•
Back-up short circuit protection of power transformers.
•
Short circuit protection of different kinds of equipment connected to the power
system such as; shunt capacitor banks, shunt reactors, motors and others.
•
Back-up short circuit protection of power generators.
In many applications several steps with different current pickup levels and time
delays are needed. OC4PTOC can have up to four different, individually settable
steps. The following options are possible:
Non-directional / Directional function: In most applications the non-directional
functionality is used. This is mostly the case when no fault current can be fed from
the protected object itself. In order to achieve both selectivity and fast fault
clearance, the directional function can be necessary.
If VT inputs are not available or not connected, the setting
parameter DirModex (x = step 1, 2, 3 or 4) shall be left to the
default value Non-directional.
Choice of time delay characteristics: There are several types of time delay
characteristics available such as definite time delay and different types of inverse
time delay characteristics. The selectivity between different overcurrent protections
is normally enabled by co-ordination between the function time delays of the
different protections. To enable optimal co-ordination between all overcurrent
Section 6
1MRK 505 383-UEN A
Current protection
76
Breaker protection REQ650 2.2 IEC
Application manual
protections, they should have the same time delay characteristic. Therefore, a wide
range of standardized inverse time characteristics are available for IEC and ANSI.
It is also possible to tailor make the inverse time characteristic.
Normally, it is required that the phase overcurrent protection shall reset as fast as
possible when the current level gets lower than the operation level. In some cases
some sort of delayed reset is required. Therefore, different kinds of reset
characteristics can be used.
For some protection applications, there can be a need to change the current pick-up
level for some time. A typical case is when the protection will measure the current
to a large motor. At the start up sequence of a motor the start current can be
significantly larger than the rated current of the motor. Therefore, there is a
possibility to give a setting of a multiplication factor to the current pick-up level.
This multiplication factor is activated from a binary input signal to the function.
Power transformers can have a large inrush current, when being energized. This
phenomenon is due to saturation of the transformer magnetic core during parts of
the period. There is a risk that inrush current will reach levels above the pick-up
current of the phase overcurrent protection. The inrush current has a large 2nd
harmonic content. This can be used to avoid unwanted operation of the protection
function. Therefore, OC4PTOC has a possibility of 2nd harmonic restrain if the
level of 2nd harmonic current reaches a value above a set percent of the
fundamental current.
The phase overcurrent protection is often used as a protection for two and three
phase short circuits. In some cases, it is not wanted to detect single-phase earth
faults by the phase overcurrent protection. This fault type is detected and cleared
after operation of earth fault protection. Therefore, it is possible to make a choice
how many phases, at minimum, that have to have current above the pick-up level,
to enable operation. If set 1 of 3 it is sufficient to have high current in one phase
only. If set 2 of 3 or 3 of 3 single-phase earth faults are not detected.
6.2.3
Setting guidelines
IP14982-1 v1
M12982-4 v13
When inverse time overcurrent characteristic is selected, the
operate time of the stage will be the sum of the inverse time delay
and the set definite time delay. Thus, if only the inverse time delay
is required, it is important to set the definite time delay for that
stage to zero.
The parameters for the directional phase overcurrent protection, four steps
OC4PTOC are set via the local HMI or PCM600.
The following settings can be done for OC4PTOC.
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
77
Application manual
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of base
values.
MeasType: Selection of discrete Fourier filtered (DFT) or true RMS filtered (RMS)
signals. RMS is used when the harmonic contents are to be considered, for example
in applications with shunt capacitors.
Operation: The protection can be set to On or Off.
AngleRCA: Protection characteristic angle set in degrees. If the angle of the fault
loop current has the angle RCA, the direction to the fault is forward.
AngleROA: Angle value, given in degrees, to define the angle sector of the
directional function, shown in Figure 33.
StartPhSel: Number of phases, with high current, required for operation. The
setting possibilities are: 1 out of 3, 2 out of 3 and 3 out of 3. The default setting is 1
out of 3.
IMinOpPhSel: Minimum current setting level for releasing the directional start
signals in % of IB. This setting should be less than the lowest step setting. The
default setting is 7% of IB.
2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is 5 - 100% in steps of 1%. The default
setting is 20%.
Section 6
1MRK 505 383-UEN A
Current protection
78
Breaker protection REQ650 2.2 IEC
Application manual
IEC09000636 V2 EN-US
Figure 33:
Directional function characteristic
1.
RCA = Relay characteristic angle
2.
ROA = Relay operating angle
3.
Reverse
4.
Forward
6.2.3.1
Settings for each step
M12982-19 v10
x means step 1, 2, 3 and 4.
DirModex: The directional mode of step x. Possible settings are Off/Non-
directional/Forward/Reverse.
Characteristx: Selection of time characteristic for step x. Definite time delay and
different types of inverse time characteristics are available according to Table 9.
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
79
Application manual
Inverse time characteristics
Curve name
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG or RD (logarithmic)
The different characteristics are described in Technical manual.
Ix>: Operate phase current level for step x given in % of IB.
Ix>Max and Ix>Min should only be changed if remote setting of operation current
level, Ix>, is used. The limits are used for decreasing the used range of the Ix>
setting. If Ix> is set outside Ix>Max and Ix>Min, the closest of the limits to Ix> is
used by the function. If Ix>Max is smaller than Ix>Min, the limits are swapped.
tx: Definite time delay for step x. The definite time tx is added to the inverse time
when inverse time characteristic is selected. Note that the value set is the time
between activation of the start and the trip outputs.
kx: Time multiplier for inverse time delay for step x.
IMinx: Minimum operate current in % of IB for all inverse time characteristics,
below which no operation takes place.
IMinx: Minimum operate current for step x in % of IBase. Set IMinx below Ix> for
every step to achieve ANSI reset characteristic according to standard. If IMinx is
set above Ix> for any step the ANSI reset works as if current is zero when current
drops below IMinx.
Section 6
1MRK 505 383-UEN A
Current protection
80
Breaker protection REQ650 2.2 IEC
Application manual
txMin: Minimum operate time for all inverse time characteristics. At high currents
the inverse time characteristic might give a very short operation time. By setting
this parameter the operation time of the step can never be shorter than the setting.
Setting range: 0.000 - 60.000s in steps of 0.001s.
IxMult: Multiplier for scaling of the current setting value. If a binary input signal
ENMULTx (enableMultiplier) is activated the current operation level is increased
by this setting constant. Setting range: 1.0-10.0
IMinx
Operate time
Current
tx
txMin
IEC10000058
IEC10000058 V2 EN-US
Figure 34:
Minimum operate current and operate time for inverse time
characteristics
In order to fully comply with the definition of the curve, the setting parameter
txMin shall be set to a value equal to the operating time of the selected inverse
curve for twenty times the set current pickup value. Note that the operate time is
dependent on the selected time multiplier setting kx.
ResetTypeCrvx: The reset of the delay timer can be made as shown in Table 10.
Table 10:
Reset possibilities
Curve name
Curve index no.
Instantaneous
1
IEC Reset (constant time)
2
ANSI Reset (inverse time)
3
The delay characteristics are described in Technical manual. There are some
restrictions regarding the choice of the reset delay.
For the definite time delay characteristics, the possible delay time setting
instantaneous (1) and IEC (2 = set constant time reset).
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
81
Application manual
For ANSI inverse time characteristics, all three types of reset time characteristics
are available: instantaneous (1), IEC (2 = set constant time reset) and ANSI (3 =
current dependent reset time).
For IEC inverse time characteristics, the possible delay time settings are
instantaneous (1) and IEC (2 = set constant time reset).
For the customer tailor-made inverse time delay characteristics (type 17), all three
types of reset time characteristics are available: instantaneous (1), IEC (2 = set
constant time reset) and ANSI (3 = current dependent reset time). If the current-
dependent type is used, settings pr, tr and cr must be given.
tResetx: Constant reset time delay in seconds for step x.
tPCrvx, tACrvx, tBCrvx, tCCrvx: These parameters are used by the customer to
create the inverse time characteristic curve. See equation 17 for the time
characteristic equation. For more information, refer to Technical manual.
[ ]
>
p
A
t s
B
IxMult
i
C
in
=
+
×
-
æ
ö
ç
÷
ç
÷
ç
÷
æ
ö
ç
÷
ç
÷
è
ø
è
ø
EQUATION1261 V2 EN-US
(Equation 17)
tPRCrvx, tTRCrvx, tCRCrvx: These parameters are used by the customer to create
the inverse reset time characteristic curve. For more information, refer to Technical
manual.
HarmRestrainx: Enables the block of step x from the harmonic restrain function
(2nd harmonic). This function should be used when there is a risk of an unwanted
trip caused by power transformer inrush currents. It can be set to Off/On.
6.2.3.2
Setting example
GUID-20729467-24AB-42F0-9FD1-D2959028732E v1
Directional phase overcurrent protection, four steps can be used in different ways,
depending on the application where the protection is used. A general description is
given below.
The operating current setting of the inverse time protection, or the lowest current
step of the definite time protection, must be defined so that the highest possible
load current does not cause protection operation. The protection reset current must
also be considered so that a short peak of overcurrent does not cause the operation
of a protection even when the overcurrent has ceased. This phenomenon is
described in Figure 35.
Section 6
1MRK 505 383-UEN A
Current protection
82
Breaker protection REQ650 2.2 IEC
Application manual
The IED does not reset
Line phase current
Time (s)
Reset current
IEC05000203-en-2.vsd
IEC05000203 V4 EN-US
Figure 35:
Operate and reset current for an overcurrent protection
The lowest setting value can be written according to Equation 18.
Imax
Ipu
1.2
k
³
×
EQUATION1262 V2 EN-US
(Equation 18)
where:
1.2
is a safety factor
k
is the reset ratio of the protection
Imax
is the maximum load current
The load current up to the present situation can be found from operation statistics.
The current setting must remain valid for several years. In most cases, the setting
values are updated once every five years or less often. Investigate the maximum
load current that the equipment on the line can withstand. Study components, such
as line conductors, current transformers, circuit breakers, and disconnectors. The
manufacturer of the equipment normally gives the maximum thermal load current
of the equipment.
The maximum load current on the line has to be estimated. There is also a demand
that all faults within the zone that the protection shall cover must be detected by the
phase overcurrent protection. The minimum fault current Iscmin to be detected by
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
83
Application manual
the protection must be calculated. Taking this value as a base, the highest pickup
current setting can be written according to Equation 19.
Ipu
£ 0.7 Iscmin
×
EQUATION1263 V2 EN-US
(Equation 19)
where:
0.7
is a safety factor
Iscmin
is the smallest fault current to be detected by the overcurrent protection.
As a summary, the operating current shall be chosen within the interval stated in
Equation 20.
1.2 Imax
Ipu
0.7 Iscmin
k
×
£
£
×
EQUATION1264 V2 EN-US
(Equation 20)
The high current function of the overcurrent protection, which only has a short-
delay trip time, must be given a current setting so that the protection is selective to
other protection functions in the power system. It is desirable to have rapid tripping
of faults within a large part of the power system to be protected by the protection
(primary protected zone). A fault current calculation gives the largest current of
faults, Iscmax, at the most remote part of the primary protected zone. The risk of
transient overreach must be considered, due to a possible DC component of the
short circuit current. The lowest current setting of the fastest stage can be written
according to
max
1.2
t
sc
Ihigh
k
I
³
×
×
EQUATION1265 V1 EN-US
(Equation 21)
where:
1.2
is a safety factor
kt
is a factor that takes care of the transient overreach due to the DC component of the fault
current and can be considered to be less than 1.05
Iscmax
is the largest fault current at a fault at the most remote point of the primary protection zone.
The operate time of the phase overcurrent protection has to be chosen so that the
fault time is short enough that the protected equipment will not be destroyed due to
thermal overload while, at the same time, selectivity is assured. For overcurrent
protection in a radial fed network, the time setting can be chosen in a graphical
way. This is mostly used in the case of inverse time overcurrent protection. Figure
36 shows how the time-versus-current curves are plotted in a diagram. The time
setting is chosen to get the shortest fault time with maintained selectivity.
Section 6
1MRK 505 383-UEN A
Current protection
84
Breaker protection REQ650 2.2 IEC
Application manual
Selectivity is assured if the time difference between the curves is larger than a
critical time difference.
Time-current curves
Fault Current
10
10
0.01
10000
en05000204.ai
Str
tfunc1
n
n
tfunc2
Trip time
n
IEC05000204 V2 EN-US
Figure 36:
Fault time with maintained selectivity
The operation time can be set individually for each overcurrent protection.
To assure selectivity between different protection functions in the radial network,
there has to be a minimum time difference Dt between the time delays of two
protections. To determine the shortest possible time difference, the operation time
of the protection, the breaker opening time and the protection resetting time must
be known. These time delays can vary significantly between different protective
equipment. The following time delays can be estimated:
Protection operation
time:
15-60 ms
Protection resetting time:
15-60 ms
Breaker opening time:
20-120 ms
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
85
Application manual
Example for time coordination
Assume two substations A and B directly connected to each other via one line, as
shown in the Figure 37. Consider a fault located at another line from the station B.
The fault current to the overcurrent protection of IED B1 has a magnitude so that
the overcurrent protection will start and subsequently trip, and the overcurrent
protection of IED A1 must have a delayed operation in order to avoid
maloperation. The sequence of events during the fault can be described using a
time axis shown in Figure 37.
I>
I>
A1
B1
Feeder
Time axis
t=0
t=t2
t=t3
The fault
occurs
B1 trips and
A1 starts
Breaker at
B1 opens
=IEC05000205=2=en=Original.vsd
Fault
t=t4
Protection
A1 resets
t=t1
B1 and A1
start
IEC05000205 V2 EN-US
Figure 37:
Sequence of events during fault
where:
t=0
is when the fault occurs
t=t1
is when protection IED B1 and protection IED A1 start
t=t2
is when the trip signal from the overcurrent protection at IED B1 is sent to the circuit breaker.
t=t3
is when the circuit breaker at IED B1 opens. The circuit breaker opening time is t3 - t2
t=t4
is when the overcurrent protection at IED A1 resets. The protection resetting time is t4 - t3.
To ensure that the overcurrent protection at IED A1 is selective to the overcurrent
protection at IED B1, the minimum time difference must be larger than the time t3.
There are uncertainties in the values of protection operation time, breaker opening
time and protection resetting time. Therefore a safety margin has to be included.
With normal values the needed time difference can be calculated according to
Equation 22.
Section 6
1MRK 505 383-UEN A
Current protection
86
Breaker protection REQ650 2.2 IEC
Application manual
EQUATION1266 V1 EN-US
(Equation 22)
where it is considered that:
the operate time of overcurrent protection B1
is 40 ms
the breaker open time
is 100 ms
the resetting time of protection A1
is 40 ms and
the additional margin
is 40 ms
6.3
Instantaneous residual overcurrent protection
EFPIOC
IP14508-1 v3
6.3.1
Identification
M14887-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN-US
50N
6.3.2
Application
M12699-3 v5
In many applications, when fault current is limited to a defined value by the object
impedance, an instantaneous earth-fault protection can provide fast and selective
tripping.
The Instantaneous residual overcurrent EFPIOC, which can operate in 15 ms (50
Hz nominal system frequency) for faults characterized by very high currents, is
included in the IED.
6.3.3
Setting guidelines
IP14985-1 v1
M12762-44 v2
M12762-4 v4
The parameters for the Instantaneous residual overcurrent protection EFPIOC are
set via the local HMI or PCM600.
Some guidelines for the choice of setting parameter for EFPIOC is given.
M12762-6 v8
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in the global base values for settings function
GBASVAL.
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
87
Application manual
GlobalBaseSel: This is used to select GBASVAL function for reference of base
values.
The basic requirement is to assure selectivity, that is EFPIOC shall not be allowed
to operate for faults at other objects than the protected object (line).
For a normal line in a meshed system single phase-to-earth faults and phase-to-
phase-to-earth faults shall be calculated as shown in Figure 38 and Figure 39. The
residual currents (3I0) to the protection are calculated. For a fault at the remote line
end this fault current is IfB. In this calculation the operational state with high source
impedance ZA and low source impedance ZB should be used. For the fault at the
home busbar this fault current is IfA. In this calculation the operational state with
low source impedance ZA and high source impedance ZB should be used.
~
~
ZA
ZB
Z L
A
B
IED
I fB
Fault
IEC09000022-1-en.vsd
IEC09000022 V1 EN-US
Figure 38:
Through fault current from A to B: IfB
IEC09000023-1-en.vsd
~
~
ZA
ZB
Z L
A
B
IED
I fA
Fault
IEC09000023 V1 EN-US
Figure 39:
Through fault current from B to A: IfA
The function shall not operate for any of the calculated currents to the protection.
The minimum theoretical current setting (Imin) will be:
Im
fA,
fB
in
MAX I
I
EQUATION284 V2 EN-US
(Equation 23)
Section 6
1MRK 505 383-UEN A
Current protection
88
Breaker protection REQ650 2.2 IEC
Application manual
A safety margin of 5% for the maximum static inaccuracy and a safety margin of
5% for maximum possible transient overreach have to be introduced. An additional
20% is suggested due to inaccuracy of instrument transformers under transient
conditions and inaccuracy in the system data.
The minimum primary current setting (Is) is:
Is = 1.3 × Imin
EQUATION285 V3 EN-US
(Equation 24)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel
line, as shown in Figure 40, should be calculated.
IEC09000025-1-en.vsd
~
~
ZA
ZB
ZL1
A
B
I M
Fault
IED
ZL2
M
C
Line 1
Line 2
IEC09000025 V1 EN-US
Figure 40:
Two parallel lines. Influence from parallel line to the through fault
current: IM
The minimum theoretical current setting (Imin) will in this case be:
Imin
M AX IfA IfB IM
,
,
(
)
³
EQUATION287 V1 EN-US
(Equation 25)
Where:
IfA and IfB
have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
Is = 1.3 × Imin
EQUATION288 V3 EN-US
(Equation 26)
The IED setting value IN>> is given in percent of the primary base current value,
IBase. The value for IN>> is given by the formula:
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
89
Application manual
IECEQUATION17003 V1 EN-US
(Equation 27)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (IBase).
Operation: set the protection to On or Off.
IN>>: Set operate current in % of IB.
IN>>Max and IN>>Min should only be changed if remote setting of operation
current level, IN>>, is used. The limits are used for decreasing the used range of
the IN>> setting. If IN>> is set outside IN>>Max and IN>>Min, the closest of the
limits to IN>> is used by the function. If IN>>Max is smaller than IN>>Min, the
limits are swapped.
StValMult: The set operate current can be changed by activation of the binary input
ENMULT to the set factor StValMult.
6.4
Directional residual overcurrent protection, four
steps EF4PTOC
IP14509-1 v8
6.4.1
Identification
M14881-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
6.4.2
Setting guidelines
IP14988-1 v1
M15282-3 v11
When inverse time overcurrent characteristic is selected, the
operate time of the stage will be the sum of the inverse time delay
and the set definite time delay. Thus, if only the inverse time delay
is required, it is important to set the definite time delay for that
stage to zero.
The parameters for the four step residual overcurrent protection are set via the local
HMI or PCM600. The following settings can be done for the function.
Section 6
1MRK 505 383-UEN A
Current protection
90
Breaker protection REQ650 2.2 IEC
Application manual
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of base
values.
SeqTypeUPol: This is used to select the type of voltage polarising quantity i.e. Zero
seq and Neg seq for direction detection.
SeqTypeIPol: This is used to select the type of current polarising quantity i.e. Zero
seq and Neg seq for direction detection.
SeqTypeIDir: This is used to select the type of operating current quantity i.e. Zero
seq and Neg seq for direction detection.
6.4.2.1
Common settings for all steps
M15282-81 v10
AngleRCA: Relay characteristic angle given in degree. This angle is defined as
shown in Figure 41. The angle is defined positive when the residual current lags
the reference voltage (Upol = 3U0 or U2)
Upol = -3U0 or
IN>Dir
RCA
Operation
-3U2
IEC05000135-5-en.vsdx
IEC05000135 V5 EN-US
Figure 41:
Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°. The setting
range is -180° to +180°.
polMethod: Defines if the directional polarization is from
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
91
Application manual
Voltage (3U0 or U2)
•
Current (3I0 · ZNpol or 3I2 ·ZNpol where ZNpol is RNpol + jXNpol), or
•
both currents and voltage, Dual (dual polarizing, (3U0 + 3I0 · ZNpol) or (U2 +
I2 · ZNpol)).
Normally voltage polarizing from the internally calculated residual sum or an
external open delta is used.
Current polarizing is useful when the local source is strong and a high sensitivity is
required. In such cases the polarizing voltage (3U0) can be below 1% and it is then
necessary to use current polarizing or dual polarizing. Multiply the required set
current (primary) with the minimum impedance (ZNpol) and check that the
percentage of the phase-to-earth voltage is definitely higher than 1% (minimum
3U0>UPolMin setting) as a verification.
RNPol, XNPol: The zero-sequence source is set in primary ohms as base for the
current polarizing. The polarizing voltage is then achieved as 3I0 · ZNpol. The
ZNpol can be defined as (ZS1-ZS0)/3, that is the earth return impedance of the
source behind the protection. The maximum earth-fault current at the local source
can be used to calculate the value of ZN as U/(√3 · 3I0) Typically, the minimum
ZNPol (3 · zero sequence source) is set. The setting is in primary ohms.
When the dual polarizing method is used, it is important that the setting INx> or
the product 3I0 · ZNpol is not greater than 3U0. If so, there is a risk for incorrect
operation for faults in the reverse direction.
IPolMin: is the minimum earth-fault current accepted for directional evaluation.
For smaller currents than this value, the operation will be blocked. A typical setting
is 5-10% of IB.
UPolMin: Minimum polarization (reference) polarizing voltage for the directional
function, given in % of UBase/√3.
IN>Dir: Operate residual current release level in % of IB for directional
comparison scheme. The setting is given in % of IB and must be set below the
lowest INx> setting, set for the directional measurement. The output signals,
STFW and STRV can be used in a teleprotection scheme. The appropriate signal
should be configured to the communication scheme block.
6.4.2.2
2nd harmonic restrain
M15282-90 v6
If a power transformer is energized there is a risk that the current transformer core
will saturate during part of the period, resulting in a transformer inrush current.
This will give a declining residual current in the network, as the inrush current is
deviating between the phases. There is a risk that the residual overcurrent function
will give an unwanted trip. The inrush current has a relatively large ratio of 2nd
harmonic component. This component can be used to create a restrain signal to
prevent this unwanted function.
Section 6
1MRK 505 383-UEN A
Current protection
92
Breaker protection REQ650 2.2 IEC
Application manual
At current transformer saturation a false residual current can be measured by the
protection. Here the 2nd harmonic restrain can prevent unwanted operation as well.
2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2nd
harmonic restrain signal. The setting is given in % of the fundamental frequency
residual current.
6.4.2.3
Parallel transformer inrush current logic
M15282-97 v6
In case of parallel transformers there is a risk of sympathetic inrush current. If one
of the transformers is in operation, and the parallel transformer is switched in, the
asymmetric inrush current of the switched-in transformer will cause partial
saturation of the transformer already in service. This is called transferred
saturation. The 2nd harmonic of the inrush currents of the two transformers will be
in phase opposition. The summation of the two currents will thus give a small 2nd
harmonic current. The residual fundamental current will however be significant.
The inrush current of the transformer in service before the parallel transformer
energizing, will be a little delayed compared to the first transformer. Therefore, we
will have high 2nd harmonic current initially. After a short period this current will
however be small and the normal 2nd harmonic blocking will reset.
en05000136.vsd
Power System
IN>
IN>
IEC05000136 V1 EN-US
Figure 42:
Application for parallel transformer inrush current logic
If the BlkParTransf function is activated, the 2nd harmonic restrain signal will latch
as long as the residual current measured by the relay is larger than a selected step
current level. Assume that step 4 is chosen to be the most sensitive step of the four
step residual overcurrent protection function EF4PTOC. The harmonic restrain
blocking is enabled for this step. Also the same current setting as this step is chosen
for the blocking at parallel transformer energizing.
The settings for the parallel transformer logic are described below.
BlkParTransf: This is used to On blocking at energising of parallel transformers.
UseStartValue: Gives which current level should be used for the activation of the
blocking signal. This is given as one of the settings of the steps: Step 1/2/3/4.
Normally, the step having the lowest operation current level should be set.
1MRK 505 383-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
93
Application manual
Switch onto fault logic
M15282-106 v4
In case of energizing a faulty object there is a risk of having a long fault clearance
time, if the fault current is too small to give fast operation of the protection. The
switch on to fault function can be activated from auxiliary signals from the circuit
breaker, either the close command or the open/close position (change of position).
This logic can be used to issue a fast trip if one breaker pole does not close
properly at a manual or automatic closing.
SOTF and under time are similar functions to achieve fast clearance at
asymmetrical closing based on requirements from different utilities.
The function is divided into two parts. The SOTF function will give operation from
step 2 or 3 during a set time after change in the position of the circuit breaker. The
SOTF function has a set time delay. The under time function, which has 2nd
harmonic restrain blocking, will give operation from step 4. The 2nd harmonic
restrain will prevent unwanted function in case of transformer inrush current. The
under time function has a set time delay.
Below the settings for switch on to fault logics are described.
SOTF: This parameter can be set: Off/SOTF/Under Time/SOTF+Under Time.
ActivationSOTF: This setting will select the signal to activate SOTF function; CB
position open/CB position closed/CB close command.
StepForSOTF: If this parameter is set on step 3, the step 3 start signal will be used
as current set level. If set on step 2, the step 2 start signal will be used as current set
level.
HarmBlkSOTF: This is used to On/Off harmonic restrain during SOTF conditions.
tSOTF: Time delay for operation of the SOTF function. The setting range is 0.000 -
60.000 s in step of 0.001 s. The default setting is 0.100 s
t4U: Time interval when the SOTF function is active after breaker closing. The
setting range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 1.000 s.
ActUnderTime: Describes the mode to activate the sensitive undertime function.
The function can be activated by Circuit breaker position (change) or Circuit
breaker command.
tUnderTime: Time delay for operation of the sensitive undertime function. The
setting range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 0.300 s
6.4.2.5
Settings for each step (x = 1, 2, 3 and 4)
M15282-9 v12
Operation: Sets the protection to On or Off.
Section 6
1MRK 505 383-UEN A
Current protection
94
Breaker protection REQ650 2.2 IEC
Application manual