Siemens SINAMICS G130 Operating Instructions Manual
Read Online
Read the Siemens SINAMICS G130 Operating Instructions Manual online using the built-in PDF viewer.
Key Pages of Document
03/2013 A5E00331462A Safety information 1 General 2 Mechanical installation 3 Electrical installation 4 Technical specifications 5 ...
90026 NÜRNBERG GERMANY A5E00331462A Ⓟ 05/2013 Technical data subject to change Copyright © Siemens AG 2004 - 2013. All rights reserved Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notic ...
3 Table of contents 1 Safety information...................................................................................................................................... 5 1.1 Warnings........................................................................................................................................5 1.2 Safety and application instructions ................................. ...
5 Safety information 1 1.1 Warnings WARNING Dangerous electrical voltage Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. These personnel must be thoroughly familiar with all the warnings and mainten ...
Line reactors 6 Operating Instructions, 03/2013, A5E00331462A 1.2 Safety and application instructions DANGER Dangerous electrical voltage This equipment is used in industrial high-voltage installations. During operation, this equipment contains live, bare parts. For this reason, they could cause severe injury or significant material damage if the required covers are removed, if they are used or ope ...
7 General 2 Description Line reactors limit low-frequency line-side harmonics to permissible values. NOTICE Maintain ventilation clearances The 100 mm cooling clearances above and to the side of the components must be observed. Note Cable lengths The connecting cables to the Power Module must be kept as short as possible. NOTICE Use only approved line reactors When using line reactors that have no ...
Assignment of line reactor and Power Module Table 2- 1 Assignment of line reactor and Power Module Power Module Unit rating of the Power Module Suitable line reactor Line voltage 380 – 480 V 3 AC 6SL3310-1GE32-1AAx 110 kW 6SL3000-0CE32-3AA0 6SL3310-1GE32-6AAx 132 kW 6SL3000-0CE32-8AA0 6SL3310-1GE33-1AAx 160 kW 6SL3000-0CE33-3AA0 6SL3310-1GE33-8AAx 200 kW 6SL3000-0CE35-1AA0 6SL3310-1GE3 ...
9 Mechanical installation 3 Dimension drawing ������������� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� Figure 3-1 Dimension drawing of line reactor ...
Table 3- 1 Dimensions of line reactor, 380 V – 480 V 3 AC (all values in mm) 6SL3000- 0CE32-3AA0 0CE32-8AA0 0CE33-3AA0 0CE35-1AA0 0CE36-3AA0 0CE37-7AA0 0CE38-7AA0 0CE41-0AA0 a2 25 30 40 50 a3 5 6 8 8 a4 12.5 15 20 25 a5 11 14 14 14 I4 270 300 350 350 I5 88 100 120 120 h1 - - 392 397 h2 150 180 252 252 h3 60 60 120 120 h4 248 269 321 321 n1 1) 101 118 138 138 n2 1) 200 ...
11 Table 3- 3 Dimensions of line reactor, 660 V – 690 V 3 AC (all values in mm) 6SL3000- 0CH31-1AA0 0CH31-6AA0 0CH32-2AA0 0CH32-7AA0 0CH33-4AA0 0CH34-8AA0 0CH36-0AA0 0CH38-4AA0 a2 25 30 40 a3 5 6 8 a4 12.5 15 20 a5 11 14 14 l4 270 350 410 l5 88 120 135 h1 - - 392 h2 150 198 252 h3 60 75 120 h4 248 321 385 n1 1) 101 138 141 n2 1) 200 264 316 n3 200 232.5 224 n4 84.5 81 56. ...
13 Electrical installation 4 Important safety precautions WARNING Dangerous electrical voltage The devices are operated with high voltages. All connection work must be carried out when the cabinet is de-energized. All work on the device must be carried out by trained personnel only. Non-observance of these warnings can result in death, serious personal injury, or substantial property damage. Work ...
Connection When connecting the line filter and line reactor, you must take into account the following conditions to ensure that they function correctly: ● Use shielded control cables. The shield must be connected at both ends. ● With analog control cables, connecting the shield at both ends can result in coupled-in noise. To prevent this, the shield must only be conn ...
15 Technical specifications 5 General technical data Table 5- 1 General technical data Line frequency 47 to 63 Hz Product standard EN 61800-5-1 Ambient conditions Storage Transport Operation Ambient temperature -25 to +70 °C -25 to +70 °C 0 to +50 °C Relative air humidity 1) (condensation not permissible) corresponds to class 5 to 95 % 1K4 acc. to EN 60721-3-1 5 to 95% at 40 °C 2K3 to EN 60721 ...
Detailed technical data Table 5- 2 Technical data of line reactors, 380 V – 480 V 3 AC, part 1 Order number 6SL3000- 0CE32-3AA0 0CE32-8AA0 0CE33-3AA0 0CE35-1AA0 Suitable for Power Module 6SL3310- 1GE32-1AAx 1GE32-6AAx 1GE33-1AAx 1GE33-8AAx Type rating of the Power Module kW 110 132 160 200 Rated voltage V 3 AC 380 –10% to 3 AC 480 +10% (-15% < 1 min) Ithmax A 224 27 ...
17 Table 5- 4 Technical data of line reactors, 380 V – 480 V 3 AC, part 3 Order number 6SL3000- 0CE41-0AA0 Suitable for Power Module 6SL3310- 1GE41-0AAx Type rating of the Power Module kW 560 Rated voltage V 3 AC 380 –10% to 3 AC 480 +10% (-15% < 1 min) Ithmax A 1022 Power loss kW 0.498 Line/load connection 1U1, 1V1, 1W1, 1U2, 1V2, 1W2 M12 connecting lugs Degree of pro ...
Table 5- 6 Technical data of line reactors, 500 V – 600 V 3 AC, part 2 Order number 6SL3000- 0CH34-8AA0 0CH34-8AA0 0CH36-0AA0 0CH38-4AA0 Suitable for Power Module 6SL3310- 1GF34-1AAx 1GF34-7AAx 1GF35-8AAx 1GF37-4AAx Type rating of the Power Module kW 250 315 400 500 Rated voltage V 3 AC 500 –10% to 3 AC 600 +10% (-15% < 1 min) Ithmax A 482 482 597 840 Power loss kW ...