YASKAWA SI-EN3 Technical Manual
Text of the manual
MANUAL NO. SIEP YEACOM 04A
Technical Manual
EtherNet/IP
Type SI-EN3
YASKAWA AC Drive 1000-Series Option
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
3
Table of Contents
1
PREFACE AND SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2
PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3
RECEIVING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4
OPTION COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5
INSTALLATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
6
OPTION RELATED DRIVE PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7
CONFIGURING MESSAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
8
OUTPUT ASSEMBLIES (DRIVE CONSUMES) . . . . . . . . . . . . . . . . . . . . . . . . .21
9
INPUT ASSEMBLIES (DRIVE PRODUCES) . . . . . . . . . . . . . . . . . . . . . . . . . . .31
10
GENERAL CLASS OBJECTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
11
VENDOR-SPECIFIC (YASKAWA) CLASS OBJECTS . . . . . . . . . . . . . . . . . . .53
12
WEB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
13
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
14
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Copyright © 2010 YASKAWA AMERICA, INC.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior
written permission of Yaskawa. No patent liability is assumed with respect to the use of the information
contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the
information contained in this manual is subject to change without notice. Every precaution has been taken in
the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any
liability assumed for damages resulting from the use of the information contained in this publication.
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
1 Preface and Safety
1
Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection
and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa
accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances
should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without
exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems
or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with
appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa
must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in
conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR
IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims
arising from misapplication of its products.
� Applicable Documentation
The following manuals are available for the SI-EN3 option:
� Terms
� Registered Trademarks
• EtherNet/IP is a trademark of the ODVA.
• All trademarks are the property of their respective owners.
SI-EN3 Option
Yaskawa AC Drive 1000-Series Option
SI-EN3 EtherNet/IP Installation Manual
Manual No: TOEP YEACOM 04�
Read this manual first.
The installation manual is packaged with the option and contains
information required to install the option and set up related drive
parameters.
Yaskawa AC Drive 1000-Series Option
SI-EN3 EtherNet/IP Technical Manual
Manual No: SIEP YEACOM 04�
The technical manual contains detailed information about the option.
In the U.S., access http://www.yaskawa.com to obtain the technical
manual. Customers in other areas should contact a Yaskawa
representative.
Yaskawa Drive
Yaskawa AC Drive
1000-Series Quick Start Guide
The drive manuals cover basic installation, wiring, operation procedures, functions,
troubleshooting, and maintenance information.
The manuals also include important information about parameter settings and drive
tuning.
Access these sites to obtain Yaskawa instruction manuals:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: contact a Yaskawa representative.
Yaskawa AC Drive
1000-Series Technical Manual
Note:
Indicates supplemental information that is not related to safety messages.
Drive:
Yaskawa AC Drive 1000-Series
Option: Yaskawa AC Drive 1000-Series SI-EN3 EtherNet/IP option
1 Preface and Safety
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
5
� Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. The option must be installed
according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could
result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
� General Safety
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
W ARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates an equipment damage message.
General Precautions
• The diagrams in this section may include options and drives without covers or safety shields to illustrate details. Be sure to reinstall covers or
shields before operating any devices. The option should be used according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this
manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve
the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa sales office and provide the manual number
shown on the front cover.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operator is responsible for injuries or equipment damage caused from failure to heed the warnings in the manual.
NOTICE
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the option.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
Do not modify the drive or option circuitry.
Failure to comply could result in damage to the drive or option and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
2 Product Overview
2
Product Overview
� About This Product
The SI-EN3 (option) provides a communications connection between the drive and an ODVA EtherNet/IP network. The
option connects the drive to an EtherNet/IP network and facilitates the exchange of data.
This manual explains the handling, installation and specifications of this product.
EtherNet/IP is a communications link to connect industrial devices (such as smart motor controllers, operator interfaces,
and variable frequency drives) as well as control devices (such as programmable controllers and computers) to a network.
EtherNet/IP is a simple, networking solution that reduces the cost and time to wire and install factory automation devices,
while providing interchangeability of like components from multiple vendors.
EtherNet/IP is an open device network standard.
By installing the option to a drive, it is possible to do the following from an EtherNet/IP master device:
• operate the drive
• monitor the operation status of the drive
• change parameter settings.
� Applicable Models
The option can be used with the drive models in Table 1.
Table 1 Applicable Models
Drive Series
Drive Model Number
Software Version <1>
<1> See “PRG” on the drive nameplate for the software version number.
A1000
CIMR-A�2A����
VSA90101�
CIMR-A�4A����
CIMR-A�5A����
VSA90504�
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
7
3
Receiving
Please perform the following tasks upon receipt of the option:
• Inspect the option for damage. Contact the shipper immediately if the option appears damaged upon receipt.
• Verify receipt of the correct model by checking the model number printed on the name plate of the option package.
• Contact your supplier if you have received the wrong model or the option does not function properly.
� Option Package Components
� Tools Required for Installation
• A Phillips screwdriver (M3 metric/#1, #2 U.S. standard size*) is required to install the option and remove drive front
covers.
• Diagonal cutting pliers. (required for some drive models)
• A small file or medium grit sandpaper. (required for certain drive models)
*Screw sizes vary by drive capacity. Select a screwdriver appropriate for the drive capacity.
Note:
Tools required to prepare option networking cables for wiring are not listed in this manual.
Description:
Option
Ground
Wire
Screws (M3)
LED Label
Installation Manual
_
Quantity:
1
1
3
1
1
NS
MS
MANUAL
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
4 Option Components
4
Option Components
� SI-EN3 EtherNet/IP Option
Figure 1
Figure 1 Option (Top View)
� Terminal CN1
The communication connector on the option is a modular RJ45 female connector designated CN1.
CN1 is the connection point for a customer supplied male Ethernet network communication cable.
Table 2 Male 8-way Ethernet Modular Connector (Customer Supplied)
A – EtherNet/IP Modular Female Connector (CN1)
E – Installation hole
B – Ground Terminal and installation hole <1>
<1> The ground wire provided in the option shipping package must be connected during installation
F – Connector (CN5)
C – LED (10/100) <2>
G – LED (NS) <2>
<2> Refer to Option LED Display on page 9 for details on the LEDs
D – LED (LINK/ACT) <2>
H – LED (MS) <2>
Male EtherNet 8-Way Modular Connector
Pin
Description
1 (Pair 2)
Transmit data (TXD) +
2 (Pair 2)
Transmit data (TXD) -
3 (Pair 3)
Receive data (RXD) +
4 (Pair 1)
Not used <1>
<1> Not used for 10 Mbps and 100 Mbps networks.
5 (Pair 1)
Not used <1>
6 (Pair 3)
Receive data (RXD) -
7 (Pair 4)
Not used <1>
8 (Pair 4)
Not used <1>
B
Underside
F
A
E
D
C
G H
4 Option Components
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
9
� Option LED Display
The option has four LEDs:
Bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Green Ethernet LEDs:
• Network speed-10/100 (MS) green
• Link status and network activity-Link/Act (NS) red/green
The operational states of the option LEDs after the power-up diagnostic LED sequence is completed are described in
Table 3. Wait at least 2 seconds for the power-up diagnostic process to complete before verifying the states of the LEDs.
Table 3 Option LED States
Table 4 Option LEDs
� Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After
the LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume
operational conditions as shown in Table 3.
Table 5 Power-Up Diagnostic LED Sequence
Name
Indication
Operating Status
Remarks
Color
Status
MS
(visible through
drive cover)
–
OFF
Power supply OFF
Power is not being supplied to the drive
Green
ON
Option operating
The option is operating normally
Green
Flashing
Option initializing
The option is configuring an IP address
Red
ON
Fatal error occurred
The option has detected a fatal (unrecoverable) error
Red
Flashing
Non-fatal error occurred
The option has detected a non-fatal (recoverable) error
Green/Red
Flashing
Option self-test
The option is in self-test mode
NS
(visible through
drive cover)
–
OFF
Offline or Power supply OFF
–
Green
ON
Online communications established
The option is online and has established connections
Green
Flashing
Online communications not established The option is online without an established connection
Red
ON
Communications error (fatal)
The option detected a duplicate IP address
Red
Flashing
Communications time-out (non-fatal)
A communications time-out occurred
Green/Red
Flashing
Option self-test
The option is in self-test mode
Name
Indication
Operating Status
Color
Status
10/100
(visible with front
cover removed)
Green
OFF
10 Mbps is established
Green
ON
100 Mbps is established
LINK/ACT
(visible with front
cover removed)
Green
OFF
Link is not established
Green
ON
Link is established
Green
Flashing
Link is established and there is network activity
Sequence
Module Status (MS)
Network Status (NS)
Time (ms)
1
Green
OFF
250
2
Red
OFF
250
3
Green
OFF
-
4
Green
Green
250
5
Green
Red
250
6
Green
OFF
-
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
5 Installation Procedure
5
Installation Procedure
� Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive, wait at least five minutes after all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal capacitor
remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus
voltage is below 50 Vdc.
W ARNING
Electrical Shock Hazard
Do not remove the front cover of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety shields to show details. Be sure to
reinstall covers or shields before operating any devices. The option should be used according to the instructions
described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of this product.
Do not touch circuit boards while the power to the drive is on.
Failure to comply could result in death or serious injury.
Do not use damaged wires, place excessive stress on wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option, drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
5 Installation Procedure
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
11
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option and connecting any other
devices.
Failure to comply may result in damage to the option.
NOTICE
5 Installation Procedure
12
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Prior to Installing the Option
Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive
functions normally without the option installed. Refer to the Quick Start Guide packaged with the drive for information
on wiring and connecting the drive.
Figure 2 shows an exploded view of the drive with the option and related components for reference.
Figure 2
Figure 2 Drive Components with Option
A – Connector CN5-C
H – LED label
B – Connector CN5-B
I – Drive terminal cover
C – Connector CN5-A
J – Removable tabs for wire routing
D – Insertion point for CN5 connector
K – Included screws
E – SI-EN3 option
L – Ground wire
F – Drive front cover
M – Option modular connector CN1
G – Digital operator
N – Drive grounding terminal (FE)
I
K
A
B
C
N
L
E
F
G
H
D
J
NS
MS
M
5 Installation Procedure
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
13
� Installing the Option
Remove the front covers of the drive before installing the option. Refer to the drive Quick Start Guide for directions on
removing the front covers. Cover removal varies depending on drive size. This option can be inserted only into the
CN5-A connector located on the drive control board.
1.
Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the digital
operator (G) and front covers (F, I). Front cover removal varies by model.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury. Before installing the option, disconnect all power to the drive. The internal capacitor remains charged even after the
power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric
shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit
boards. Failure to comply may result in ESD damage to circuitry.
Figure 3
Figure 3 Remove the Front Covers and Digital Operator
2.
With the front covers and digital operator removed, apply the LED label (H) in the appropriate position on the
drive top front cover (F).
Figure 4
Figure 4 Apply the LED Label
F
G
I
NS
MS
F
H
5 Installation Procedure
14
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
3.
Insert the option (E) into the CN5-A connector (C) located on the drive and fasten it using one of the included
screws (K).
Figure 5
Figure 5 Insert the Option
4.
Connect the ground wire (L) to the ground terminal (N) using one of the remaining provided screws (K). Connect
the other end of the ground wire (L) to the remaining ground terminal and installation hole on the option (E) using
the last remaining provided screw (K) and tighten both screws to 0.5 ~ 0.6 nm or (4.4 ~ 5.3 in lbs).
Figure 6
Figure 6 Connect the Ground Wire
Note:
There are two screw holes on the drive for use as ground terminals. When connecting three options, two ground wires will need to
share the same drive ground terminal.
NS MS
C
D
K
E
NS MS
K
L
N
E
5 Installation Procedure
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
15
� Wiring the Option
5.
Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to
the outside to provide adequate space for the wiring. In these cases, using diagonal cutting pliers, cut out the
perforated openings on the left side of the drive front cover. Sharp edges along the cut out should be smoothed
down with a file or sand paper to prevent any damage to the wires.
5.a Route the Ethernet cable inside the enclosure for drives that do not require routing through the front cover.
Refer to Table 6 and Figure 7 to determine the proper wire routing by drive model.
Table 6 Model-Specific Cable Routing
Figure 7
Figure 7 Wire Routing Examples
6.
Connect the Ethernet communication cable to the option modular connector (CN1).
To connect the option to a network, insert the RJ45 connector of the Cat 5e patch cable into the option modular
connector (CN1). Ensure the cable end is firmly connected (see Figure 7).
IGMP Snooping
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only
reveive the multicast packets in which they are interested.
Communication Cable Specifications
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP™). Using a cable not specifically
recommended may cause the option or drive to malfunction. Refer to the ODVA website for more information on network
cabling (http://www.odva.org).
Drive Series
Model
Wire Routing <1>
<1> Refer to Figure 7 for examples of the different wire routing techniques.
Through Front Cover
Inside Drive
A1000
CIMR-A�2A0004 to 0040; CIMR-A�4A0002 to 0023;
CIMR-A�5A0003 to 0011
Figure 7 (A)
-
A1000
CIMR-A�2A0056 and above; CIMR-A�4A0031 and above;
CIMR-A�5A0023 and above.
-
Figure 7 (B)
A – Route wires through the openings provided
on the left side of the front cover. <1>
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
B – Use the open space provided inside the drive
to route option wiring.
B
A
5 Installation Procedure
16
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Connection Diagram
Figure 8 Wiring Diagram
7.
Replace and secure the front covers of the drive (F, I) and replace the digital operator (G).
Figure 8
Figure 9 Replace the Front Covers and Digital Operator
Note:
Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure no cables are
pinched between the front covers and the drive when replacing the covers.
8.
Set drive parameters in Table 7 for proper option performance.
� EDS Files
For easy network implementation of drives equipped with the SI-EN3 option, an EDS file can be obtained from:
U.S.: http://www.yaskawa.com
Other areas: Contact a Yaskawa representative.
<1> The ground wire provided in the option shipping package must be connected during installation.
Drive
M
U
V
W
R
S
T
CN5
FE
<1>
EtherNet/IP Master
EtherNet/IP Cable
Motor
Power
SI-EN3
EtherNet/IP
Option
CN1
MS
MS
I
F
G
6 Option Related Drive Parameters
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
17
6
Option Related Drive Parameters
The following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be
found in the drive Quick Start Guide or Technical Manual.
Confirm proper setting of the all parameters in Table 7 before starting network communications.
Table 7 Related Parameter Settings
No.
(Addr.
Hex)
Name
Description
Values
b1-01
(180)
<1>
Frequency Reference Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)
Default: 1
Range: 0 to 4
(Set to 3)
b1-02
(181)
<1>
Run Command Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S�
2: MEMOBUS/Modbus communications
3: Option
Default: 1
Range: 0 to 3
(Set to 3)
F6-01
(3A2)
Operation Selection after
Communications Error
Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only <2>
Default: 1
Range: 0 to 3
F6-02
(3A3)
External Fault Detection
Conditions (EF0)
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
Default: 0
Range: 0, 1
F6-03
(3A4)
Stopping Method for External
Fault from the Communication
Option
Determines drive response for external fault input (EF0) detection during
option communications.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only <2>
Default: 1
Range: 0 to 3
F6-06
(3A7)
<3>
Torque Reference/Torque Limit
Selection from the Communication
Option
0: Torque Reference/Torque Limit via network communications are
disabled.
1: Torque Reference/Torque Limit via network communications are
enabled. <4>
Default: 0
Range: 0, 1
F6-07
(3A8)
NetRef/ComRef Selection
Function
0: Multi-step speed reference disabled, (F7 functionality)
1: Multi-step speed reference allowed (V7 functionality)
Default: 0
Range: 0, 1
F6-08
(36A)
Reset Communication Related
Parameters
Determines if communication-related parameters F6-�� and F7-�� are
set back to original default values when the drive is initialized using
parameter A1-03.
0: Do not reset parameters
1: Reset parameters
Default: 0
Range: 0, 1
F7-01
(3E5)
<6>
IP Address 1
Sets static IP address of network connection.
Parameter F7-01 sets the most significant octet.
Default: 192
Range: 0 to 255
F7-02
(3E6)
<6>
IP Address 2
Sets static IP address of network connection.
Parameter F7-02 sets the second most significant octet.
Default: 168
Range: 0 to 255
F7-03
(3E7
<6>
IP Address 3
Sets static IP address of network connection.
Parameter F7-03 sets the third most significant octet.
Default: 1
Range: 0 to 255
6 Option Related Drive Parameters
18
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
F7-04
(3E8)
<6>
IP Address 4
Sets static IP address of network connection.
Parameter F7-04 sets the fourth most significant octet.
Default: 20
Range: 0 to 255
F7-05
(3E9)
Subnet Mask 1
Sets static Subnet Mask of network connection.
Parameter F7-05 sets the most significant octet.
Default: 255
Range: 0 to 255
F7-06
(3EA)
Subnet Mask 2
Sets static Subnet Mask of network connection.
Parameter F7-06 sets the second most significant octet.
Default: 255
Range: 0 to 255
F7-07
(3EB)
Subnet Mask 3
Sets static Subnet Mask of network connection.
Parameter F7-07 sets the third most significant octet.
Default: 255
Range: 0 to 255
F7-08
(3EC)
Subnet Mask 4
Sets static Subnet Mask of network connection.
Parameter F7-08 sets the fourth most significant octet.
Default: 0
Range: 0 to 255
F7-09
(3ED)
Gateway Address 1
Sets static Gateway address of network connection.
Parameter F7-09 sets the most significant octet.
Default: 192
Range: 0 to 255
F7-10
(3EE)
Gateway Address 2
Sets static Gateway address of network connection.
Parameter F7-10 sets the second most significant octet.
Default: 168
Range: 0 to 255
F7-11
(3EF)
Gateway Address 3
Sets static Gateway address of network connection.
Parameter F7-11 sets the third most significant octet.
Default: 1
Range: 0 to 255
F7-12
(3E0)
Gateway Address 4
Sets static Gateway address of network connection.
Parameter F7-12 sets the fourth most significant octet.
Default: 1
Range: 0 to 255
F7-13
(3F1)
Address Mode at Startup
Selects how the option address is set.
0: Static <5>
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
F7-14
(3F2)
Duplex Mode Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default: 1
Range: 0 to 2
F7-15
(3F3)
Communication Speed Selection
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
F7-16
(3F4)
Communication Loss Time-out
Sets the time-out value for communication loss detection in tenths of a
second. A value of 0 disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min.: 0
Max.: 300
F7-17
EtherNet/IP Speed Scaling Factor
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0
Min.: -15
Max.: 15
F7-18
EtherNet/IP Current Scaling Factor Sets the scaling factor for the output current monitor in EtherNet/IP Class
ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-19
EtherNet/IP Torque Scaling Factor Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0
Min.: -15
Max.: 15
F7-20
EtherNet/IP Power Scaling Factor
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0
Min.: -15
Max.: 15
F7-21
EtherNet/IP Voltage Scaling Factor Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID
2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0
Min.: -15
Max.: 15
No.
(Addr.
Hex)
Name
Description
Values
6 Option Related Drive Parameters
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
19
Table 8 Option Monitors
F7-23 to
F7-32
Dynamic Output Assembly
Parameters
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly
116 will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus
register.
Default: 0
F7-33 to
F7-42
Dynamic Input Assembly
Parameters
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will
be read from this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value sent for
Input Assembly 166 is not defined by the user, therefore the option default
register value will be returned.
Refer to Input Assemblies (Drive Produces) on page 31 for definitions of
the default MEMOBUS/Modbus registers.
Default: 0
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or set the “Net Control” bit in the
assemblies or Control Supervisor Object. To control the drive frequency reference of the drive via the master device, set b1-01 to 3 or set the Net
Reference bit in the assemblies or AC/DC Object.
<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop switch.
<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as the
Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In CLV/PM, this value is read as the Torque Limit.
<4> Default setting specifies that the Torque Reference or Torque Limit is to be provided via network communications (F6-06 = 1). The motor may
rotate if no torque reference or Torque Limit is supplied from the PLC.
<5> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.
<6> Cycle power for setting changes to take effect.
No.
Name
Description
Value Range
U6-80 to U6-83
Online IP Address
IP Address; U6-80 is the most significant octet
0 to 255
U6-84 to U6-87
Online Subnet
Subnet; U6-84 is the most significant octet
0 to 255
U6-88 to U6-91
Online Gateway
Gateway; U6-88 is the most significant octet
0 to 255
U6-92
Online Speed
Link Speed
10, 100
U6-93
Online Duplex
Duplex Setting
0: Half, 1: Full
U6-98
First Fault
First Option Fault
-
U6-99
Current Fault
Current Option Fault
-
No.
(Addr.
Hex)
Name
Description
Values
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
7 Configuring Messaging
7
Configuring Messaging
This section provides information on methods used to control the drive with the option installed.
� Drive Polled Configuration with SI-EN3
The assemblies in Table 9 are available for polled I/O:
Table 9 Supported Polled I/O Assemblies
Assembly Number
(decimal)
Description
Type
Bytes
Page
20
Basic Speed Control Output
Output
4
21
21
Extended Speed Control Output
Output
4
22
22
Speed and Torque Control Output
Output
6
23
23
Extended Speed and Torque Control Output
Output
6
24
70
Basic Speed Control Input
Input
4
31
71
Extended Speed Control Input
Input
4
32
72
Speed and Torque Control Input
Input
6
33
73
Extended Speed and Torque Control Input
Input
6
34
100
(Vendor Specific YE Assy)-MEMOBUS/Modbus Message Output
Output
5
25
101
(Vendor Specific YE Assy)-Speed/Torque Control Output
Output
8
26
116
(Vendor Specific YE Assy)-High Speed/Torque Control Output
Output
44
28
150
(Vendor Specific YE Assy)-MEMOBUS/Modbus Message Input
Input
5
35
151
(Vendor Specific YE Assy)-Speed/Torque Status Input
Input
8
36
166
(Vendor Specific YE Assy)-High Speed/Torque Status Input
Input
44
38
8 Output Assemblies (Drive Consumes)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
21
8
Output Assemblies (Drive Consumes)
Note:
The convention in this manual is from the PLC perspective. As such, an assembly is called an “Output Assembly” when outputted
from the PLC and received by this node. This section details “Output Assemblies” that are “Consumed” by this drive.
� Basic Speed Control Output - 20 (0x14)
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
20
0
–
–
–
–
–
Fault
Reset
–
Run
Fwd
1
-
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex or 10.24 Hz
Unit depends on o1-03.
8 Output Assemblies (Drive Consumes)
22
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Extended Speed Control Output - 21 (0x15)
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
21
0
–
NetRef
NetCtrl
–
–
Fault
Reset
Run
Rev
Run
Fwd
1
–
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
NetCtrl
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
NetRef
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400
Unit depends on o1-03.
8 Output Assemblies (Drive Consumes)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
23
� Speed and Torque Control Output - 22 (0x16)
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
22
0
–
–
–
–
–
Fault
Reset
–
Run
Fwd
1
–
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference/Torque Limit (Low Byte)
5
Torque Reference/Torque Limit (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400
Unit depends on o1-03.
Torque Reference/Torque Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
8 Output Assemblies (Drive Consumes)
24
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Extended Speed and Torque Control Output - 23 (0x17)
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
23
0
–
NetRef
NetCtrl
–
–
Fault
Reset
Run
Rev
Run
Fwd
1
–
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference/Torque Limit (Low Byte)
5
Torque Reference/Torque Limit (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
NetCtrl
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
NetRef
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400
Unit depends on o1-03.
Torque Reference/Torque Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
8 Output Assemblies (Drive Consumes)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
25
� MEMOBUS/Modbus Message Output (Vendor Specific YE Assy) - 100 (0x64)
Note:
This is a paired assembly (100/150).
Table 10 Function Code Decode Table
Note:
Refer to the MEMOBUS/Modbus Data Table in Appendix C of the Technical Manual for a list of monitor data using the
MEMOBUS/Modbus message area.
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
100
0
Function Code
1
Register Number (High Byte)
2
Register Number (Low Byte)
3
Register Data (High Byte)
4
Register Data (Low Byte)
Name
Description
Function Code
MEMOBUS/Modbus Function Code.
Register Number
MEMOBUS/Modbus Register Number
Register Data
MEMOBUS/Modbus Register Data
Function Code
MEMOBUS/Modbus Function
0x00
No Operation
0x03
Read Register
0x10
Write Register
8 Output Assemblies (Drive Consumes)
26
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Speed/Torque Control Output (Vendor Specific YE Assy) - 101 (0x65)
Output
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
101
0
Multi-Function
Input 8
Multi-Function
Input 7
Multi-Function
Input 6
Multi-Function
Input 5
Multi-Function
Input 4
Multi-Function
Input 3
Run
Rev
Run
Fwd
1
Multi-Function
Photo Coupler
2
Multi-Function
Photo Coupler
1
Multi-Function
Digital Output
–
–
–
Fault
Reset
External
Fault
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference/Torque Limit (Low Byte)
5
Torque Reference/Torque Limit (High Byte)
6
Torque Compensation (Low Byte)
7
Torque Compensation (High Byte)
Output Instance
Byte
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Multi-Function Input 3
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Multi-Function Input 4
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Multi-Function Input 5
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Multi-Function Input 7
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Multi-Function Input 8
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
External Fault
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
Multi-Function Digital Output
Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
This function is enabled only when H2-01 is set to F.
Multi-Function Photo Coupler 1
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
8 Output Assemblies (Drive Consumes)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
27
Multi-Function Photo Coupler 2
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Reference
Speed Command
Sets drive speed reference.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Torque Reference/Torque Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
Torque Compensation
Sets the amount of Torque Compensation
Sets in units of 0.1%.
Output Instance
Byte
8 Output Assemblies (Drive Consumes)
28
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� High Speed/Torque Control Output (Vendor Specific YEA Assy) - 116 (0x74)
This assembly is dynamic and can be configured as to what parameters are used. The first 20 Bytes (0-19) are fixed and
the next 20 Bytes can be configured using parameters F7-23 to F7-32. If an error occurs while trying to write to the
dynamic parameters, the appropriate error bit in Assembly 166 will be set. If more information is needed as to the nature
of the error, the extended error status can be read explicitly through Class 0xA6, Instance 1, Attribute 0x64. This will
return 20 Bytes with each dynamic parameter in Assembly 116 having a Byte dedicated to its extended error status. Refer
to Input Assemblies (Drive Produces) on page 31 for more information.
Output
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
116
0
Multi-
Function
Input 8
Multi-
Function
Input 7
Multi-
Function
Input 6
Multi-
Function
Input 5
Multi-
Function
Input 4
Multi-
Function
Input 3
Run
Rev
Run
Fwd
1
Multi-
Function
Photo
Coupler 2
Multi-
Function
Photo
Coupler 1
Multi-
Function
Digital
Output
–
–
–
Fault
Reset
External
Fault
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference/Torque Limit (Low Byte)
5
Torque Reference/Torque Limit (High Byte)
6
Torque Compensation (Low Byte)
7
Torque Compensation (High Byte)
8
(Reserved)
9
Multi-
Function
Input 12
Multi-
Function
Input 11
Multi-
Function
Input 10
Multi-
Function
Input 9
10
–
–
–
–
–
–
NetCtrl
NetRef
11
–
–
–
–
–
–
–
–
12
Analog Output 1 (Low Byte)
13
Analog Output 1 (High Byte)
14
Analog Output 2 (Low Byte)
15
Analog Output 2 (High Byte)
16
Digital Outputs (Low Byte)
17
Digital Outputs (High Byte)
18
Reserved for Future Use
19
Reserved for Future Use
20 - 21
Defined by F7-23
Default: Not Used
22 -23
Defined by F7-24
Default: Not Used
24 - 25
Defined by F7-25
Default: Not Used
26 - 27
Defined by F7-26
Default: Not Used
28 - 29
Defined by F7-27
Default: Not Used
30 - 31
Defined by F7-28
Default: Not Used
32 - 33
Defined by F7-29
Default: Not Used
34 - 35
Defined by F7-30
Default: Not Used
8 Output Assemblies (Drive Consumes)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
29
116
36 - 37
Defined by F7-31
Default: Not Used
38 - 39
Defined by F7-32
Default: Not Used
40 - 43
Not Used
Parameter
Data
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Multi-Function Input 3
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Multi-Function Input 4
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Multi-Function Input 5
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Multi-Function Input 7
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
External Fault
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
Multi-Function Digital Output
Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
This function is enabled only when H2-01 is set to F
Multi-Function Photo Coupler 1
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F
Multi-Function Photo Coupler 2
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F
Speed Reference
Speed Reference [RPM or o1-03]
Torque Reference/Torque Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
Torque Compensation
Sets the amount of Torque Compensation
Sets in units of 0.1%.
Digital Inputs
MEMOBUS/Modbus (0x49). Monitor parameter U1-10
Output
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
8 Output Assemblies (Drive Consumes)
30
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
NetReference
Option sets reference
NetCtrl
Option sets control
Analog Output 1
MEMOBUS/Modbus (0x0007)
Analog Output 2
MEMOBUS/Modbus (0x0008)
Digital Outputs
MEMOBUS/Modbus (0x0009)
Programmable Bytes
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. A value
of 0 in the given parameter means it is not used, therefore the value received for this given parameter will
not be written to any MEMOBUS/Modbus register. If the PPA is Input Assembly 166, then any errors
occurring during a write will be flagged. Refer to High Speed/Torque Status Input (Vendor Specific YEA
Assy) - 166 (0xA6) on page 38.
Parameter
Data
9 Input Assemblies (Drive Produces)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
31
9
Input Assemblies (Drive Produces)
Note:
The convention in this manual is from the PLC perspective. An “Input Assembly” is outputted from this node and read by the
PLC. This section details “Input Assemblies” that are “Produced” by this drive.
� Basic Speed Control Input - 70 (0x46)
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
0
–
–
–
–
–
Running 1
(FWD)
–
Faulted
1
–
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Parameter
Data
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
9 Input Assemblies (Drive Produces)
32
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Extended Speed Control Input - 71 (0x47)
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
71
0
At Speed
Ref from Net
Ctrl from Net
Ready
Running 2
(REV)
Running 1
(FWD)
Warning
Faulted
1
Drive State
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Warning
Warning
0: No Warning Occurred
1: Warning Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Running 2 (REV)
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Ready
Drive Ready
0: Not Ready
1: Ready
Ctrl from Net
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Ref from Net
Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network
At Speed
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
Drive State
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
9 Input Assemblies (Drive Produces)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
33
� Speed and Torque Control Input - 72 (0x48)
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
72
0
–
–
–
–
–
Running 1
(FWD)
–
Faulted
1
–
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Torque Actual (Low Byte)
5
Torque Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Torque Actual
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
9 Input Assemblies (Drive Produces)
34
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Extended Speed and Torque Control Input - 73 (0x49)
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
73
0
At Speed
Ref from Net
Ctrl from Net
Ready
Running 2
(REV)
Running 1
(FWD)
Warning
Faulted
1
Drive State
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Torque Actual (Low Byte)
5
Torque Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Warning
Warning
0: No Warning Occurred
1: Warning Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Running 2 (REV)
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Ready
Drive Ready
0: Not Ready
1: Ready
Ctrl from Net
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Ref from Net
Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network
At Speed
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
Drive State
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Torque Actual
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
9 Input Assemblies (Drive Produces)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
35
� MEMOBUS/Modbus Message Input (Vendor Specific YE Assy) - 150 (0x96)
Note:
This is a paired assembly (100/150).
Table 11 Reply Mapping - 150
Table 12 Error Replies - 150
Note:
Refer to the MEMOBUS/Modbus Data Table in Appendix C of the drive Technical Manual for a list of monitor data using the
MEMOBUS/Modbus message area.
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
150
0
Function Code
1
Register Number (High Byte)
2
Register Number (Low Byte)
3
Register Data (High Byte)
4
Register Data (Low Byte)
Byte
Write Success
Read Success
Write Failure
Read Failure
Invalid Function
Code
Function
Code
Equals
Zero
0
0x10
0x03
0x90
0x83
Function Code Or-ed
with 0x80
0
1
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
0
2
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
0
3
0
Read Data (High Byte)
0
0
0
0
4
0
Read Data (Low Byte)
Error Code
Error Code
1
0
Error Code
Description
0x01
Invalid Function Code
0x02
Invalid Register Number
0x21
Upper/Lower Limit Error
0x22
Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done yet.
Writing “Enter” when drive is running.
Attempt to write data that is read only.
Attempt to write a constant when drive is running.
During a CPF03 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.
0x23
Attempting to write during a drive undervoltage (Uv) event.
0x24
Attempting to write while the drive is storing data.
9 Input Assemblies (Drive Produces)
36
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Speed/Torque Status Input (Vendor Specific YE Assy) - 151 (0x97)
Output
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
151
0
FAULT
ALARM
READY
Speed
Agree
Reset
REV
Running
ZSP
Running
1
ZSV
–
Multi-Function
Photo Coupler
2
Multi-Function
Photo Coupler
1
Multi-
Function
Digital Output
LOCAL/
REMOTE
UV
OPE
2
Output Frequency (Low Byte)
3
Output Frequency (High Byte)
4
Torque Actual (Low Byte)
5
Torque Actual (High Byte)
6
Actual Current (Low Byte)
7
Actual Current (High Byte)
Parameter
Data
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
Reset
0: No Reset
1: Reset
Speed Agree
Speed Agree
0: No Speed Agree
1: Speed Actual at speed reference
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
OPE
OPE Fault
0: No OPExx Fault
1: OPExx
UV
Under Voltage
0: No Under Voltage
1: Under Voltage
Local/Remote
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output
Terminal MA/MB
0: Terminal MA/MB OFF
1: Terminal MA/MB ON
Multi-Function Photo Coupler 1
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
9 Input Assemblies (Drive Produces)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
37
Multi-Function Photo Coupler 2
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
ZSV
Zero Servo Completed
0: —
1: Completed
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Torque Actual
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
Actual Current
Actual Output Current
Monitors drive output current.
Unit is 0.01 A.
Unit is not affected by Current Scale CS.
Parameter
Data
9 Input Assemblies (Drive Produces)
38
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� High Speed/Torque Status Input (Vendor Specific YEA Assy) - 166 (0xA6)
If an error occurs while trying to read from the dynamic parameters, the appropriate error bit in Assembly 166 will be set.
If more information about the nature of the error is needed, the extended error status can be read explicitly through Class
0xA6, Instance 1, Attribute 0x64. This will return 20 Bytes with each dynamic parameter in Assembly 166 having a Byte
dedicated to its extended error status.
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
166
0
Fault
Alarm
Ready
Speed Agree
Fault Reset
REV Running
Zero Speed
Running
1
ZSV
–
Multi-
Function
Photo-
Coupler 2
Multi-
Function
Photo-
Coupler 1
Multi-
Function
Digital Output
LOCAL/
REMOTE
Uv
oPE
2
Motor Speed (Low Byte)
3
Motor Speed (High Byte)
4
Torque Actual (Low Byte)
5
Torque Actual (High Byte)
6
PG Count Value (Low Byte)
7
PG Count Value (High Byte)
8
Frequency Command (Low Byte)
9
Frequency Command (High Byte)
10
Output Frequency (Low Byte)
11
Output Frequency (High Byte)
12
Output Current (Low Byte)
13
Output Current (High Byte)
14
INV Terminal A1 Input (Low Byte)
15
INV Terminal A1 Input (High Byte)
16
Main Circuit DC Voltage (Low Byte)
17
Main Circuit DC Voltage (High Byte)
18
Error Code (Low Byte)
19
Error Code (High Byte)
20
Parameter F7-33 Default: Alarm Code (Low Byte)
21
Parameter F7-33 Default: Alarm Code (High Byte)
22
Parameter F7-34 Default: Output Power (Low Byte)
23
Parameter F7-34 Default: Output Power (High Byte)
24
Parameter F7-35 Default: INV Terminal A2 Input (Low Byte)
25
Parameter F7-35 Default: INV Terminal A2 Input (High Byte)
26
Parameter F7-36 Default: INV Terminal 1..12 Input (Low Byte)
27
Parameter F7-36 Default: INV Terminal 1..12 Input (High Byte)
28
Parameter F7-37 Default: INV Terminal A3 Input (Low Byte)
29
Parameter F7-37 Default: INV Terminal A3 Input (High Byte)
30
Parameter F7-38 Default: PG Counter (Ch2) (Low Byte)
31
Parameter F7-38 Default: PG Counter (CH2) (High Byte)
32
Parameter F7-39 Default: NetRef and NetCtrl (Low Byte)
–
–
–
–
–
–
NetCtrl
NetRef
33
Parameter F7-39 Default: NetRef and NetCtrl
34
Parameter F7-40 Default: Drive Software Version (Low Byte)
35
Parameter F7-40 Default: Drive Software Version (High Byte)
36
Parameter F7-41 Default: Not Used
37
Parameter F7-33 Default: Not Used
38
Parameter F7-33 Default: Not Used
39
Parameter F7-42 Default: Not Used
9 Input Assemblies (Drive Produces)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
39
166
40
-
-
-
-
-
-
Assy. 116
F7-32 Error
Assy. 116
F7-31 Error
41
Assy. 116
F7-30 Error
Assy. 116
F7-29 Error
Assy. 116
F7-28 Error
Assy. 116
F7-27 Error
Assy. 116
F7-26 Error
Assy. 116
F7-25 Error
Assy. 116
F7-24 Error
Assy. 116
F7-23 Error
42
-
-
-
-
-
-
Assy. 166
F7-42 Error
Assy. 166
F7-41 Error
43
Assy. 166
F7-40 Error
Assy. 166
F7-39 Error
Assy. 166
F7-38 Error
Assy. 166
F7-37 Error
Assy. 166
F7-36 Error
Assy. 166
F7-35 Error
Assy. 166
F7-34 Error
Assy. 166
F7-33 Error
Parameter
Data
Running
Running
0: Stop
1: Forward or Reverse Running
Zero Speed
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Fault Reset
Fault Reset command from Network
0: Fault Reset command is not from network
1: Fault Reset command is from network
Speed Agree
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
OPE
OPE Fault
0: No OPExx fault
1: OPExx
Uv
Under Voltage
0: No Under Voltage
1: Under Voltage
Local/Remote
Status of Run command from Network
0: Run command is not from Network
1: Run Command is from Network
Multi-Function Digital Output
Terminal MA/MB
0: Terminal MA/MB OFF
1: Terminal MA/MB ON
Multi-Function Photo Coupler 1
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
Multi-Function Photo Coupler 2
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
ZSV
Zero Servo Completed
0: —
1: Completed
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
9 Input Assemblies (Drive Produces)
40
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
Motor Speed
Monitor parameter U1-05
Torque Actual
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
PG Count Value
Contained MEMOBUS/Modbus Address
Frequency Command
Monitor parameter U1-01
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Output Current
Actual Output Current
Monitors drive output current.
Unit is 0.01 A
Unit is not affected by Current Scale CS.
INV Terminal A1 Input
MEMOBUS/Modbus (0x46)
Monitor parameter U1-13
Main DC Voltage
Main Circuit DC Voltage
Monitor parameter U1-07
Error Code
U2-01 converted using fault code table
F7-33 Alarm Code
Programmable: MEMOBUS/Modbus (0x7F)
F7-34 Output Power
Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
F7-35 Terminal A2 Input
Programmable: MEMOBUS/Modbus (0x4F)
Monitor parameter U1-14
F7-36 INV Terminal 1-12
Programmable: MEMOBUS/Modbus (0x49)
Monitor parameter U1-10
F7-37 Terminal A3 Input
Programmable: MEMOBUS/Modbus (0x50)
F7-38 PG Count Value (CH 2)
Programmable: MEMOBUS/Modbus (0xF1)
Serial interface Control Response
F7-39 NetRef (Status)
Status of reference command from Network
0: Reference command is not from network
1: Reference command is from network
F7-40 Drive Software Version
Programmable: MEMOBUS/Modbus (0x4D)
Monitor parameter U1-25
Parameter
Data
9 Input Assemblies (Drive Produces)
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
41
Possible extended error codes are listed in Table 13 and Table 14. On Assembly 116, the only error that can be declared is
0x02.
Table 13 Extended Error Codes for Assembly 116/166
Table 14 Extended Error Codes in Class 0x04 Instance 0xA6 Attribute 0x64
Error Code
Description
0x00
No Error
0x01
Sub function code failure
0x02
Register number failure
0x21
Limit check error failure
0x22
Write failure
0x23
Write failure at Uv
0x24
Write failure at busy
Dynamic Parameter
Byte Containing Extended Error Code
F7-23
Byte 0
F7-24
Byte 1
F7-25
Byte 2
F7-26
Byte 3
F7-27
Byte 4
F7-28
Byte 5
F7-29
Byte 6
F7-30
Byte 7
F7-31
Byte 8
F7-32
Byte 9
F7-33
Byte 10
F7-34
Byte 11
F7-35
Byte 12
F7-36
Byte 13
F7-37
Byte 14
F7-38
Byte 15
F7-39
Byte 16
F7-40
Byte 17
F7-41
Byte 18
F7-42
Byte 19
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
10 General Class Objects
10
General Class Objects
� Identity Object 1 (Class 0x01)
� Services Supported
� Attributes Supported
Note:
*1 Product code is 2 Bytes. The first Byte is the drive type and the second Byte is the model number of the drive.
Service Code No. (hex)
Service Name
01
Get Attribute All
05
Reset
0E
Get Attribute Single
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
0
1
Object
Software
Revision
Identity Object software revision
O
-
Word
1
1
1
Vendor ID
Manufacturer code.
44 (2C Hex): Yaskawa Electric
O
-
Word
44 (Yaskawa)
1
2
Device Type
Device profile.
The profile for this product is an AC drive.
2: AC drive
O
-
Word
2 (AC drives)
1
3
Product Code Product codes determined by the
manufacturer.
O
-
Word
*1
1
4
Revision
Software revision for the option.
O
-
Word
Depends on software
1
5
Status
Shows the communication status for the
drive.
O
-
Word
0
1
6
Serial
Number
Option serial number.
O
-
Long
Each unit is unique
1
7
Product Name Product Name
O
-
String
(14 Bytes)
Product dependent
(i.e., CIMR-X)
1
8
State
Operation status of the drive.
3: Drive ready
4: Fault
O
-
Byte
3
10 General Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
43
� Assembly Object 4 (Class 0x04)
� Services Supported
� Attributes Supported
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
0
1
Object
Software
Revision
Show the EtherNet Object software revision.
O
-
Word
2
20
3
Data
Same function as the Basic Speed Control
(Output Assembly)
O
O
Array 4
Bytes
00 00 00 00
21
3
Data
Same function as the Extended Speed Control
(Output Assembly)
O
O
Array 4
Bytes
00 00 00 00
22
3
Data
Same function as the Speed and Torque
Control (Output Assembly)
O
O
Array 6
Bytes
00 00 00 00 00 00
23
3
Data
Same function as the Extended Speed and
Torque Control (Output Assembly)
O
O
Array 6
Bytes
00 00 00 00 00 00
70
3
Data
Same function as the Basic Speed Control
(Input Assembly)
O
-
Array 4
Bytes
00 00 00 00
71
3
Data
Same function as the Extended Speed Control
(Input Assembly)
O
-
Array 4
Bytes
00 00 00 00
72
3
Data
Same function as the Extended Speed and
Torque Control (Input Assembly)
O
-
Array 6
Bytes
00 00 00 00 00 00
73
3
Data
Same function as the Speed Control
(Input Assembly)
O
-
Array 6
Bytes
00 00 00 00 00 00
100
3
Data
Same function as the MEMOBUS/Modbus
Message Command (Output Assembly)
O
O
Array 5
Bytes
00 00 00 00 00
101
3
Data
Same function as the Standard Control
(Output Assembly)
O
O
Array 8
Bytes
00 00 00 00 00 00 00 00
116
3
Data
Same function as the High Speed/Torque
Control (Output Assembly)
O
O
Array 44
Bytes
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
150
3
Data
Same function as the MEMOBUS/Modbus
Message Command (Input Assembly)
O
-
Array 5
Bytes
00 00 00 00 00
151
3
Data
Same function as the Standard Status
(Input Assembly)
O
-
Array 8
Bytes
00 00 00 00 00 00 00 00
166
3
Data
Same function as the High Speed/Torque
Status (Input Assembly)
O
-
Array 44
bytes
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
10 General Class Objects
44
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Motor Data Object 40 (Class 0x28)
� Services Supported
� Attributes Supported
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
0
1
Object
Software
Revision
Motor Data Object software revision.
O
-
Word
1
1
3
Motor Type
Differs by the motor control mode that is
selected. When set for Open Loop Vector for
PM motors (A1-02 = 5), value becomes 3
(PM motor). When the drive is set for V/f
Control (A1-02 = 0) or Open Loop Vector
(A1-02 = 2), value becomes 7 (squirrel cage
motor).
O
-
Byte
Depends on A1-02, Control Method
Selection
1
6
Rated Current
[0.1 A]
Motor rated current.
Displayed in 0.1 A units. Changes according
to the current scale (CS).
O
O
Byte
Depends on capacity
1
7
Rated Voltage
[1V]
Motor rated voltage.
Displayed in 1 V units. Changes according to
the voltage scale (VS).
O
O
Byte
Depends on capacity
10 General Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
45
� Control Supervisor Object 41 (Class 0x29)
� Services Supported
� Attributes Supported
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
05
Reset
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
0
1
Object
Software
Revision
Revision number of the Control Supervisor
Object.
O
-
Word
1
1
3
Run 1
(Forward Run
Command)
Forward Running
0: Stop
1: Forward Running
O
O
Byte
0
1
4
Run 2
(Reverse Run
Command)
Reverse Running
0: Stop
1: Reverse Running
O
O
Byte
0
1
5
NetCtrl
(Command)
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
O
O
Byte
0
1
6
State
Drive Status.
2: Not Ready
3: Ready (Stopped)
4: Enabled (Run command present)
5: Deceleration to Stop
6: Fault Stop
7: Fault
O
-
Byte
3
1
7
Running 1
(FWD)
Forward Running
0: Stop
1: Forward Running
O
-
Byte
0
1
8
Running 1
(REV)
Reverse Running
0: Stop
1: Reverse Running
O
-
Byte
0
1
9
Ready
Drive Ready
0: Not Ready
1: Ready
O
-
Byte
1
1
10
Fault
Drive Fault
0: No Drive Fault
1: Fault
O
-
Byte
0
1
11
Warning
Warning
0: No Warning
1: Warning
O
-
Byte
0
1
12
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
O
O
Byte
0
1
13
Fault Code
Current Fault Refer to Option Fault Code
Conversion Table for details
O
-
Word
0000
1
15
Control from
Net (Status)
Run Command from the option
0: The run command is not from the option
1: Enables the run command from option
O
-
Byte
0
1
16
EtherNet/IP
Fault Mode
Normal 2 (Vendor Specific)
O
-
Byte
2
10 General Class Objects
46
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
1
17
Force Fault
External Fault
0: No External Fault
1: External Fault (EF0)
Triggered by the rising edge of the signal.
O
O
Byte
0
1
18
Force Reset
External Fault status
0: No External Fault
1: External Fault (EF0)
Triggered by the rising edge of the signal.
O
-
Byte
0
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
10 General Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
47
� Option Fault Code Conversion Table
Drive Fault Code (Dec)
(MEMOBUS/Modbus #0080 hex)
Option Fault Code (hex)
Description
0
0000
None
2
3220
DC Bus Undervolt (Uv1)
3
5110
CTL PS Undervolt (Uv2)
4
3222
MC Answerback (Uv3)
6
2120
Ground Fault (GF)
7
2300
Over Current (oC)
8
3210
DC Bus Overvolt (ov)
9
4200
Heatsink Overtemp (oH)
10
4210
Heatsink Max Temp (oH1)
11
2220
Motor Overload (oL1)
12
2200
Inv Overload (oL2)
13
2221
Overtorque Det 1 (oL3)
14
2222
Overtorque Det 2 (oL4)
15
7110
DynBrk Transistor (rr)
16
7112
DynBrk Resistor (rH)
17
9000
External Fault 3 (EF3)
18
9000
External Fault 4 (EF4)
19
9000
External Fault 5 (EF5)
20
9000
External Fault 6 (EF6)
21
9000
External Fault 7(EF7)
24
7310
Overspeed Det (oS)
25
7310
Speed Deviation (dEv)
26
7301
PG Open (PGo)
27
3130
Input Phase Loss (PF)
28
3130
Output Phase Loss (LF)
30
5300
Operator Disconnected (oPr)
31
6320
EEPROM R/W Error (Err)
33
7500
MEMBOUS/Modbus Com Fault (CE)
34
7500
EtherNet/IP Communication Error (bUS)
37
8321
Out of Control (CF)
39
9000
External Fault 0 (EF0)
40
8000
PID Feedback Loss (FbL)
41
8000
Undertorque Detection 1 (UL3)
42
8000
Undertorque Detection 2 (UL4)
43
8000
High Slip Braking oL (oL7)
50
8000
Z Pulse Fall Detection (dv1)
51
8000
Z Pulse Noise Fault Detection (dv2)
52
8000
Inversion Detection (dv3)
53
8000
Inversion Prevention Detection (dv4)
54
8000
Current Imbalance (LF2)
55
8000
Pull-Out Detection (STo)
56
7000
PG Hardware Fault (PGoH)
59
1000
Too Many Speed Search Restarts (SEr)
65
8000
Excessive PID Feedback (FbH)
66
9000
External Fault (input terminal S1) (EF1)
67
9000
External Fault (input terminal S2) (EF2)
68
8000
Mechanical Weakening Detection 1 (oL5)
69
8000
Mechanical Weakening Detection 2 (UL5)
70
5000
Current Offset Fault (CoF)
10 General Class Objects
48
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
73
8000
DriveWorksEZ Fault (dwFL)
77
5000
Output Voltage Detection Fault (voF)
78
7000
Braking Resistor Fault (rF)
79
7000
Braking Transistor Overload Fault (boL)
—
1000
Other faults
Drive Fault Code (Dec)
(MEMOBUS/Modbus #0080 hex)
Option Fault Code (hex)
Description
10 General Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
49
� AC/DC Drive Object 42 (Class 0x2A)
� Services Supported
� Attributes Supported
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
0
1
Object
Software
Revision
Revision number of AC/DC drive object
O
-
Word
1
1
3
Speed Agree
Speed Agree
0: —
1: Speed Agree
O
-
Byte
0
1
4
NetRef
(Command)
Status of reference command from EtherNet/
IP
0: Reference command from the option
1: Reference command not from option
O
-
Byte
0
1
6
Drive Mode
Drive control mode.
0: OLV
0: OLV for PM motors (Read Only)
0: Advanced OLV for PM motors (Read
Only)
1: V/f Control
2: V/f Control with PG
3: CLV
3: CLV for PM motors (Read Only)
O
O
Byte
0
1
7
Speed Actual Actual drive speed.
Unit is not affected by Speed Scale (SS).
O
-
Word
3
1
8
Speed
Reference
Frequency Reference.
Monitors the drive’s frequency reference.
Unit is not affected by Speed Scale (SS).
O
O
Word
0
1
9
Current
Actual
Actual Output Current.
Unit is 0.01 A for drives set up to 11 kW in
Heavy Duty or Normal Duty and 0.1 A for
drives set up for 15 kW and above.
Unit is not affected by Current Scale (CS).
O
-
Word
0
1
11
Torque Actual Drive Output Torque Unit is affected by
Torque Scale (TS)
O
-
Word
0
1
12
Torque
References/
Torque Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit. The
units are determined by the Torque Scale.
Sets the Torque Reference when using Torque
Control (d5-01 = 1).
Sets the Torque Limit when using Speed
Control (d5-01 = 0)
The Torque Reference/Torque Limit are
disabled when F6-06 = 0.
O
O
Word
0
1
15
Power Actual
(W)
Drive Output Power Unit is affected by
Power Scale (PS).
O
-
Word
0
1
16
Input Voltage
(V)
Drive Input Voltage
Unit is affected by Voltage Scale (VS).
O
-
Word
Depends on Capacity
1
17
Output
Voltage (V)
Drive Output Voltage
Unit is affected by Voltage Scale (VS).
O
-
Word
0
10 General Class Objects
50
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
1
18
Accel Time
(ms)
Acceleration Time 1 (C1-01)
Units set in parameter C1-10.
Unit is affected by Time Scale (TS).
O
O
Word
2710 h
1
19
Decel Time
(ms)
Acceleration Time 1 (C1-02)
Units set in parameter C1-10.
Unit is affected by Time Scale (TS).
O
O
Word
2710 h
1
20
Low Speed
Limit Percent
of Max Speed
Frequency Reference Lower Limit (d2-02)
O
O
Word
0
1
21
High Speed
Limit Percent
of Max Speed
Frequency Reference Upper Limit (d2-01)
O
O
Word
3E8 h
1
22
Speed Scale
(-15 ~ 15)
Setting for F6-56, scale of units for speed
related data.
O
O
Byte
0
1
23
Current Scale
(-15 ~ 15)
Setting for F6-57, scale of units for current
related data.
O
O
Byte
0
1
24
Torque Scale
(-15 ~ 15)
Setting for F6-58, scale of units for torque
related data.
O
O
Byte
0
1
26
Power Scale
(-15 ~ 15)
Setting for F6-59, scale of units for power
related data.
O
O
Byte
0
1
27
Voltage Scale
(-15 ~ 15)
Setting for F6-60, scale of units for voltage
related data.
O
O
Byte
0
1
28
Time Scale
(-15 ~ 15)
Setting for F6-61, scale of units for speed
related data.
O
O
Byte
0
1
29
Reference
from Net
(Status)
Status of Reference Command (1 = Network).
0: As set by the drive parameters (i.e., b1-01)
1: Network
O
-
Byte
0
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
10 General Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
51
� TCP/IP Object 245 (Class 0xF5)
� Services Supported
� Attributes Supported
Note:
“Get Attributes All” Service shall report in attribute ascending order.
Service Code No. (hex)
Service Name
01
Get Attribute All
0E
Get Attribute Single
10
Set Attribute Single
Instance
ID
Attribute
Name
Description
Get
Set
Size
Range
Default
0
1
Object
Software
Revision
Revision number of the TCP/IP
Object
O
—
Word
—
1
1
1
Status
Bits 0-3 = Interface Status
0: Interface has not been
configured
1: Interface Configuration is
valid, obtained from BOOTP,
DHCP, or NVRAM
2: Interface Configuration is valid
and obtained from hardware
settings
3: Reserved
Bit 4 = Multicast Pending
Bits 5-31 = Reserved
O
—
DWord
—
—
1
2
Configuration
Capability
Bit 0 = BOOTP Client
Bit 1 = DNS Client
Bit 2 = DHCP Client
Bit 3 = DHCP-DNS Update
Bit 4 = Configuration Settable
Bits 5-31 = Reserved
O
—
DWord
—
—
1
3
Configuration
Control
Bits 0-3 = Startup Configuration
0: NVRAM
1: BOOTP
2: DHCP
3: Reserved
Bit 4 =DNS Enabled (not
supported)
Bits 5-31 = Reserved
O
O
DWord
0 - 2h
—
1
4
Physical Link
Struct of:
Path Size: Word
Path: EPATH
O
—
Struct
—
02h 00h 20h F6h 24h 01h
1
5
Interface
Configuration
Struct of:
IP Address = Long
Subnet Mask = Long
Gateway Address = Long
Name Server1 = Long
Name Server2 = Long
Domain Name = STRING
O
O
Struct
—
—
1
6
Host Name
Host Name
O
O
STRING
64
Characters
Null
10 General Class Objects
52
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Ethernet Link Object 246 (Class 0xF6)
� Services Supported
� Attributes Supported
Note:
“Get Attributes All” Service shall report in attribute ascending order.
Service Code No. (hex)
Service Name
01
Get Attribute All
0E
Get Attribute Single
10
Set Attribute Single
Instance
ID
Attribute
Name
Name
Get
Set
Size
Range
Default
0
1
Object
Software
Revision
Revision number of the Ethernet
Link Object
O
-
Word
—
3
1
1
Interface
Speed
Interface speed currently in use
O
-
UDINT
—
—
1
2
Interface
Flags
Bit 0 = Link Status
Bit 1 = Duplex (0: Half/1: Full)
Bits 2-4 = Negotiation Status
0: In progress
1: Auto-negotiate failed
2: Speed found, duplex not found-
-no defaulted duplex
3: Successful
4: Not attempted
Bit 5 = Manual Setting requires
restart
Bit 6 = Local hardware fault
Bits 7-31 = Reserved
O
-
DWord
—
—
1
3
Physical
Address
(MAC)
MAC layer address
O
-
Array of 6
Bytes
—
—
1
6
Interface
Control
Struct of:
Control Bits: Word
Bit 0 = Auto-negotiate
Bit 1 = Forced Duplex Mode
Bits 2-15 = Reserved
Forced Int Speed: Word
-
O
Struct
—
—
11 Vendor-Specific (Yaskawa) Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
53
11
Vendor-Specific (Yaskawa) Class Objects
� Yaskawa Drive Parameters Object 100 (Class 0x64)
� Services Supported
This is a dynamic explicit Class Object. With this Class object any drive parameter with a MEMOBUS/Modbus address
greater than 0x00FF can be accessed. The mapping of Class Object instance/attribute to MEMOBUS/Modbus address is
as follows.
Given a typical MEMOBUS/Modbus Address of 0xXXYY
The EtherNet/IP Instance value is equal to XX
The EtherNet/IP Attribute value is equal to YY
As an example, to access parameter b5-12 (MEMOBUS/Modbus Address =0x01B0)
Class Object is 100 (0x64) (Always for this Class Object)
Instance = 0x01
Attribute = 0xB0
� Storing Changed Parameters
Writing a zero to 0x0900 (Enter) stores changed parameters to the non-volatile memory of the drive. Writing a 0 to
0x0910 (Accept) allows the drive to use the changed parameters. Reading Enter Command 0x0900 or Accept Command
0x910 will always return a value of 0x0001.
Performing a RAM-ENTER to Store Register Data
Parameter H5-11 is used to decide whether a RAM-ENTER will be done on the writes to registers in the drive. If H5-11 =
1 (default), the option will issue the RAM-ENTER with the parameter writes. If H5-11 = 0, no RAM-ENTER is issued
and an ENTER command must be explicitly sent by the user for the parameter to be activated after a write.
Explicit writes to RAM-ENTER (0x910) and ROM-ENTER (0x900) are handled as special cases. If a user writes a 0 to
RAM-ENTER or ROM-ENTER, the command will be executed in the drive. If a user writes a 1 to those registers, the
command will not be executed but returns a success to the explicit write on the network. Writing a value other than 0 or 1
will result in an error response of Invalid Attribute Value on the network.
Note:
Performing the RAM-ENTER increases the processing time of the writes and increases the response time to explicit writes.
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
11 Vendor-Specific (Yaskawa) Class Objects
54
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Attributes Supported
Note: 1. Attempting to set a read-only parameter results in a EtherNet/IP error code of 0x0E, Attribute Not Settable.
2. Attempting to access an invalid parameter results in a EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in Appendix C of the drive Technical Manual for a list of monitor data using the
MEMOBUS/Modbus message area.
Instance
ID
Attribute
Name
Description
Get
Set
Size
Default
0
1
Object
Software
Revision
Yaskawa Drive Parameters object software
revision
O
-
Word
1
1
00
MEMOBUS/
Modbus
Register
0x0100
Language selection
O
O
Word
1
1
01
MEMOBUS/
Modbus
Register
0x0101
Parameter access level
O
O
Word
2
1
YY
MEMOBUS/
Modbus
Registers
0x0100 ~
0x01FF
MEMOBUS/Modbus Registers 0x0100 ~
0x01FF
O
O
Word
—
2
YY
MEMOBUS/
Modbus
Registers
0x0200 ~
0x02FF
MEMOBUS/Modbus Registers 0x0200 ~
0x02FF
O
O
Word
—
...
...
...
...
...
O
Word
—
255
YY
MEMOBUS/
Modbus
Registers
0xFF00 ~
0xFFFF
MEMOBUS/Modbus Registers
0xFF00 ~ 0xFFFF
O
O
Word
—
11 Vendor-Specific (Yaskawa) Class Objects
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
55
� Yaskawa Monitor/Control Object 125 (Class 0x7D)
� Services Supported
This is a dynamic explicit Class Object. With this Class object any parameter with a MEMOBUS/Modbus address less
than 0x0100 can be accessed. This class is similar to the Drive Parameters Object Class 100, except the most significant
Byte of MEMOBUS/Modbus address is always zero, the instance in this class remains at 1.
Given a typical MEMOBUS/Modbus Address 0f 0x00YY
The EtherNet/IP Instance value is equal to 0x01
The EtherNet/IP Attribute value is equal to YY
As an example, to access Drive Status (MEMOBUS/Modbus Address = 0x002C)
Class Object is 125 (0x7D) (Always for this Class Object)
Instance = 0x01
Attribute = 0x2C
� Attributes Supported
Note: 1. Attempting to set a read-only parameter results in a EtherNet/IP error code of 0x0E, Attribute Not Settable.
2. Attempting to access an invalid parameter results in a EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in Appendix C of the drive Technical Manual for a list of monitor data using the
MEMOBUS/Modbus message area.
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
Instance ID
Attribute
MEMOBUS/Modbus
Address
Description
Get
Set
Size
0
1
-
Object Software Revision
O
-
Word
1
1
0x0001
Drive Command Bits
O
O
Word
1
2
0x0002
Frequency Instruction
O
O
Word
..
..
..
..
O
O
Word
1
255
0x00FF
Unused
O
O
Word
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
12 Web Interface
12
Web Interface
The web server interface to the option allows management of diagnostic information through a standard web browser.
The embedded web pages include:
• Main page
• Drive Status page
• Network Monitor page
• Documentation page
� Main Page
The embedded main page shows basic option information such as vendor ID, serial number, MAC address, and firmware
version. This page also shows the status of the option and provides links to the other embedded web pages.
Figure 9
Figure 10 Main Page View
12 Web Interface
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
57
� Drive Status Page
The embedded drive status page shows basic I/O information and drive state information.
Figure 10
Figure 11 Drive Status Page View
� Network Monitor Page
The embedded network monitor page shows the status of the option network traffic and open I/O connections.
Figure 11
Figure 12 Network Monitor Page View
12 Web Interface
58
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Documentation Page
The embedded documentation page contains links to option documentation on the Yaskawa website.
Figure 12
Figure 13 Documentation Page View
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
59
13
Troubleshooting
� Drive-Side Error Codes
Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed in
Table 15. For additional error codes that may appear on the drive digital operator, refer to the drive Technical Manual.
� Faults
Both bUS (SI-EN3 option communication error) and EF0 (External fault input from the SI-EN3 option) can appear as an
alarm or as a fault. When a fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED
flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Table 15 Fault Display and Possible Solutions
LED Operator Display
Fault Name
bUS
Option Communication Error.
• After establishing initial communication, the connection was lost
• Only detected when the run command or frequency reference is assigned to the option
(b1-01 = 3 or b1-02 = 3)
Cause
Possible Solution
Master controller (PLC) has stopped
communicating
• Check that power is supplied to the PLC
• Check that PLC is not in program mode
Communication cable is not connected properly
• Check for faulty wiring
• Correct any wiring problems
A data error occurred due to noise
• Inspect items that can minimize the effects of electrical noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to the
contactor coil
• Make sure the cable used meets the EtherNet/IP requirements
• Make sure the option ground wire is connected between option FE terminal and the drive
ground terminal connected to earth ground
Option is damaged
If there are no problems with the wiring and the error continues to occur, replace the option.
Connection Time-out
• The option Requested Packet Interval (RPI) timer timed out
• Make sure that RPI time is set properly
Duplicate IP Address
The option shares IP Address with at least one other node.
LED Operator Display
Fault Name
EF0
External Fault Input from option.
The alarm function for an external device has been triggered.
Cause
Corrective Action
An external fault is being sent from the upper
controller (PLC)
• Remove the cause of the external fault
• Reset the external fault input from the PLC device
Problem with the PLC program
Check the program used by the PLC and make the appropriate corrections.
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
LED Operator Display
Fault Name
oFA00
Option fault.
Option is not properly connected.
Cause
Possible Solution
Non-compatible option connected to the drive
Connect an option that is compatible with the drive.
LED Operator Display
Fault Name
oFA01
Option fault.
Option is not properly connected.
Cause
Possible Solution
Problem with the connectors between the drive
and option
Turn the power off and check the connectors between the drive and option.
LED Operator Display
Fault Name
oFA03
Option fault.
Option self-diagnostics error.
Cause
Possible Solution
Option hardware fault
Replace the option.
LED Operator Display
Fault Name
oFA04
Option fault.
Option flash write mode.
Cause
Possible Solution
Option hardware fault
Replace the option.
LED Operator Display
Fault Name
to
oFA30 to oFA43
Option Fault (Port A).
Communication ID error.
Cause
Possible Solution
Option hardware fault
Replace the option.
LED Operator Display
Fault Name
oFb00
Option Fault (CN5-B).
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option connected to the drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFb02
Option Fault (CN5-B).
Two identical options are connected at the same time.
Cause
Possible Solution
Options AI-A3 or DI-A3 are connected to the
CN5-B port with an option connected to CN5-A.
• Only one type of AI-A3 or DI-A3 option can be connected to the drive
• The SI-EN3 option can only be connected to CN5-A
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
61
� Minor Faults and Alarms
� Explicit Message Communications Errors
When there is a problem with a request message sent from the master in explicit communications, the drive will return
one of the following error codes.
Note:
Refer to the MEMOBUS/Modbus Data Table in the Technical Manual for a list of monitor data using the MEMOBUS/Modbus
message area.
LED Operator Display
Fault Name
oFc00
Option Fault (CN5-C).
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option connected to the drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFc02
Option Fault.
Option Flash write mode.
Cause
Possible Solution
Options AI-A3 or DI-A3 are connected to the
CN5-B port while an option connected to
CN5-A.
• Only one type of AI-A3 or DI-A3 option can be connected to the drive
• The SI-EN3 option can only be connected to CN5-A
LED Operator Display
Minor Fault Name
CALL
Serial communication transmission error.
Communication is not established.
Cause
Possible Solution
Minor Fault
(H2-�� = 10)
Communication wiring is faulty, there is a short
circuit, or improper connection.
Check for wiring errors:
• Correct the wiring
• Remove ground shorts and reconnect loose wires
YES
Programming error on the master side.
Check communications at start-up and correct programming errors.
Communication circuitry is damaged.
• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur
Error
Code
(hex)
Description
Cause
Possible Solution
08
Service not supported
The service code is incorrect.
Correct the service code.
09
Invalid attribute value
The attribute is incorrect.
Correct the attribute.
0C
Object state conflict
Attempted to change an drive constant that cannot be changed
while the drive is running.
Stop the drive.
0E
Attribute not settable
Attempted to change a read-only attribute.
Correct the service code or attribute setting.
13
Not enough data
The data size is incorrect.
Correct the data size.
14
Attribute not supported Attempted to execute a service not defined for the attribute.
Correct the service code or attribute setting.
15
Too much data
The data size is incorrect.
Correct the data size.
16
Object does not exist
An unsupported object was specified.
Correct the class or instance setting.
1F
Vendor-specific error
Attempted to change a drive constant that cannot be changed
while the drive is running.
Attempted to change a drive constant to a value outside the
setting range.
Stop the drive.
Specify a value within the setting range.
20
Invalid parameter
Attempted to change to a data value outside the setting range.
Specify a data value within the setting range.
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Option Error Codes
� Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in
Table 16.
Table 16 Option Fault Monitor Descriptions
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
� Option Compatibility
A limited number of options may be simultaneously connected to the drive depending on the type of option. Refer to
Table 17 for more information. More details can be found in the Options and Peripheral Devices chapter of the drive
Technical Manual.
Table 17 Option Installation Compatibility
Fault Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault
n/a
0
No faults.
Force Fault
EF0
3
Network sent a message to force this node to the fault state.
Network Link Down
BUS ERROR
1100
No network link to option.
Connection Time-out
BUS ERROR
1101
The node timer (Requested Packet Interval) timed out.
Duplicate IP Address
BUS ERROR
1102
This node and at least one other node have the same IP Address.
Default MAC Address
None
1103
Factory default MAC Address programmed into the option. Return for
reprogramming.
Option
<1> When installed in CN5-A, the AI-A3 and DI-A3 options can be used to set the frequency reference or replace the drive analog inputs with higher
resolution. When installed in CN5-B or CN5-C, these options can only be used for monitoring; their input levels will be displayed in U1-17 or
U1-21 to U1-23.
<2> Use the CN5-C connector when connecting only one option to the drive; use both CN5-B and CN5-C when connecting two options.
Connector
Number of Possible Options
SI-C3, SI-N3, SI-P3, SI-S3, SI-EN3 <1>
CN5-A
1
PG-B3, PG-X3
CN5-B, C
2 <2>
DO-A3, AO-A3, AI-A3, DI-A3
CN5-A, B, C
1
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
63
14
Specifications
� Specifications
Table 18 Option Specifications
Item
Specification
Model
SI-EN3 (PCB model: UTC000280)
SI-EN3 Supported Messages
• Explicit: Explicit Class 3, Unconnected
• I/O: Class 1, Listen Only, Input Only
I/O Assembly Instance
• Input: 7 types (4~44 Bytes)
• Output: 7 types (4~44 Bytes)
SI-EN3 Specification
Conformance Level A6: Passed
SI-EN3 Profile
AC Drive
Connector Type
RJ45 8-pin Straight Connector STP Cat 5e cable
Physical Layer Type
• Isolated Physical Layer
• TCP Protocol Transformer Isolated
IP Address Setting
Programmable from drive keypad or network
Communication Speed
Programmable from drive keypad or network:
10/100 Mbps, auto-negotiate
Number of Connections
• I/O: 2
• Explicit: 6
Duplex Mode
Half-forced, Auto-negotiate, Full-forced
Address Startup Mode
Static, BOOTP, DHCP
Ambient Temperature
-10 °C to +50 °C (14 °F to 122 °F)
Humidity
95% RH or lower with no condensation
Storage Temperature
-20 °C to +60 °C (-4 °F to 140 °F) allowed for short-term transport of the product
Area of Use
Indoor (free of corrosive gas, airborne particles, etc.)
Altitude
1000 m (3280 ft.) or lower
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
� Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
Date of Publication
Revision
Number
Section
Revised Content
August 2009
−
−
First edition
October 2009
<1>
Entire document Edited for clarity.
June 2010
<2>
Sections 5 & 6
F7-14 default and IGMP Snooping note.
MANUAL NO.�SIEP YEACOM 04A
Published in U.S.A. June 2010 09-08
Date of
publication
Date of original
publication
Minor revision number
Major revision letter
2
YASKAWA SIEP YEACOM 04A 1000-Series Option SI-EN3 EtherNet/IP Technical Manual
65
Published in U.S.A. June 2010 09-8 2
MANUAL NO. SIEP YEACOM 04A
09-08-1
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2010 YASKAWA AMERICA, INC. All rights reserved.
Technical Manual
EtherNet/IP
YASKAWA AC Drive Option
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: 1-847-887-7000 or (800)YASKAWA (800-927-5292) Fax: 1-847-887-7310
Internet: http://www.yaskawa.com
Type SI-EN3
YASKAWA ELETRICO DO BRASIL LTDA.
Avenida Fagundes Filho, 620 Sao Paulo-SP CEP 04304-000, Brazil
Phone 55-11-3585-1100 Fax 55-11-5581-8795