guidelines, and options for selection and application of SAM-e and Mini SAM-e Short Absorption Manifolds 1503529-F | 22 JUNE 2015 Your guide to selecting and specifying Nortec SAM-e Short Absorption Manifolds! ...

Thank you for choosing Nortec.

Proprietary Notice This document and the information disclosed herein are proprietary data of NORTEC. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of NORTEC., except to the extent required for installation or maintenance of recipien ...

Determining the Steam

Absorption Distance 7 Static Air Pressure 7 Condensate Losses 8 Correct Choice of Product Applications 15 Product Selection 16 Step 1 Header Selection 24 Step 2 Steam Tube Selection 27 Step 3 SAM-e Steam Inlet Configuration Selection 30 Select Options 35 Installation Drawings 45 Specification 51 ...

1 | SAM-e Engineering

Nortec Short Absorption Manifold (SAM-e) The SAM-e is Nortec‟s best performing steam absorption system for use in Air Handling Units and duct systems where short steam absorption distance is critical. Precisely controlled clean steam is distributed uniformly into the air stream by the SAM-e without any condensate spray. Steam distrib ...

3 | SAM-e Engineering

Determining the Steam Absorption Distance A certain amount of time is required for complete absorption when injecting steam into the air. During this time, steam moves a fixed distance from the distribution manifold before it is fully absorbed into a moving air stream. The absorption distance is the distance required for steam to be ful ...

SAM-e Engineering | 4

Static Air Pressure Table 1 shows the static pressure loss created by a SAM-e in various velocities. Table 1: Air Pressure Loss in AHU / Duct Air Velocity [ fpm (m/s) ] Air Pressure Loss [ in(mm) of water column ] SAM-e Tube Spacing 3” (762 mm) 6” (152 mm) 9” (229 mm) 12” (305 mm) 500 (2.5) 0.01 (0.3) 0.01 (0.3) No measurable d ...

5 | SAM-e Engineering

The SAM-e is available with optional stainless steel insulation for headers and tubes. Insulation is desirable to reduce air-stream heat gain, reduce condensate losses, and improve energy efficiency. Please refer to Table 3 when estimating condensate losses with insulated SAM-e‟s. Table 3: Condensate Loss for Insulated SAM-e Air Vel ...

7 | SAM-e Engineering

Table 4: SAM-e Dimensions – Width Duct Width Dimension A Frame Width - Bottom Dimension B Frame Width - Top Dimension C Header Assembly Width in mm in mm in mm in mm 18 457 13.1 333 14.9 378 16.3 413 24 610 19.1 486 20.9 530 22.3 57 30 762 25.1 638 26.9 683 28.3 72 36 914 31.1 791 32.9 835 34.3 87 42 1067 37.1 943 38.9 987 40.3 102 4 ...