Fire Control Panel MAG2/4 - User Manual

CONTENTs Guarantee ...................................................................................................................3 1. Using the MAG2/4 controls ...................................................................................4 1.1 Operation modes ..........................................

Fire Control Panel MAG2/4 - User Manual

3 GUARANTEE The guarantee terms are determined by the serial number (barcode) of the electronic device! During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective product when it is returned to the factory. All parts replaced and/or repaired shall

Fire Control Panel MAG2/4 - User Manual

1. Using the MAG2/4 control Description of the front panels elements:  LED indication for the zones status: MAG2 - 2 zones MAG4 - 4 zones  Buttons for programming and operation, see item 1.5.  LED indication for the system status, see item 1.4.  LED indication for the technical troubles - see item 1

Fire Control Panel MAG2/4 - User Manual

5 1.1 Operation modes: MODE Indication Normal • The green LED next to the ‘power Supply 230V AC’ will be illuminated. Fire • The integrated red status FIRE LED and a zone identification LED will flash together on receipt of a FIRE condition and become steady after the SILENCE ALARM butto

Fire Control Panel MAG2/4 - User Manual

1.4 LED indication for the system status: LED Indication FIRE (red) Fire in the premises. GENERAL FAULT* (yellow) Main Fault indicator. sOUNDER FAULT/DIsABLE* (yellow) Trouble in the sounder circuit - open or short circuit; reverse connected sounder. ENABLE / DIsABLE (yellow) Lights permanently at disabled zone

Fire Control Panel MAG2/4 - User Manual

7 1.7 sound signalization signal Description short beeps After pressing the “RESET” button and upon the initial start-up of the panel. Continuous beep Fire and/ or Fault operating mode. The signal can be stopped by pressing the “SILENCE BUZZER” button, but the LED indication remains. Int

Fire Control Panel MAG2/4 - User Manual

3. Testing the MAG2/4 fire panels ! ATTENTION: It has been assumed that prior to making the connection at the panel, the integrity of the system ALL wiring has been comprehensively tested, including insulation to earth. • Switch on the mains power supply. • Connect the battery leads from the black power sup

Fire Control Panel MAG2/4 - User Manual

9 • Operate ALL detection devices applicable to this zone, to ensure correct receipt of a fire signal and the correct operation of the panel controls. Refer to the User Instructions on the inside of the panel. • Repeat the connection process for the other zones stated above. ENSURE the sup