Sungrow SG500MX Operation Manual
Read Online
Read the Sungrow SG500MX Operation Manual online using the built-in PDF viewer.
Text of the manual
About this Manual ............................................................................ 1
1.1 Foreword .......................................................................................................................................1
1.2 Validity ...........................................................................................................................................1
1.3 Contents ........................................................................................................................................1
1.4 Target Group ................................................................................................................................1
1.5 How to Use This Manual...........................................................................................................1
1.6 Symbols Explanation ................................................................................................................2
1.7 Symbols on the Inverter Body ...............................................................................................2
2
Safety Instructions ........................................................................... 4
2.1 Intended Usage ..........................................................................................................................4
2.2 Important Safety Instructions ................................................................................................4
2.3 During Operation .......................................................................................................................5
2.3.1 Manual .................................................................................................................................5
2.3.2 Qualified Personnel .........................................................................................................5
2.3.3 Markings on the Inverter ...............................................................................................5
2.3.4 Safety Warning Signs ......................................................................................................6
2.3.5 Emergency Escape Route..............................................................................................6
2.3.6 PV Arrays Hazards ............................................................................................................6
2.3.7 Live Line Measurement .................................................................................................6
2.3.8 Measuring Instrument ...................................................................................................6
2.3.9 LCD Parameter Setting ...................................................................................................7
2.3.10 ESD Protection ...............................................................................................................7
2.3.11 Moisture protection .....................................................................................................7
2.3.12 Maintenance and Service ...........................................................................................7
2.3.13 Disposal of Waste ..........................................................................................................7
2.3.14 Others ...............................................................................................................................8
3
Product Description ......................................................................... 9
3.1 Product Appearance .................................................................................................................9
3.1.1 Brief Introduction ............................................................................................................9
3.1.2 LED Indicators ...................................................................................................................9
3.1.3 LCD Display ..................................................................................................................... 10
3.1.4 Emergency Stop Button ............................................................................................. 10
3.1.5 Start/Stop Switch .......................................................................................................... 10
3.2 Communication Solution ..................................................................................................... 11
3.2.1 RS485 Communication Solution ............................................................................. 11
3.2.2 Ethernet Communication Solution ........................................................................ 12
4
Inverter Start/Stop ........................................................................ 13
4.1 Starting the Inverter............................................................................................................... 13
4.1.1 Inspection before starting the inverter ................................................................. 13
4.1.2 Steps to Starting the Inverter ................................................................................... 13
4.2 Stopping the Inverter ............................................................................................................ 13
4.2.1 Normal Stop ................................................................................................................... 14
4.2.2 Inverter Stops when a fault occurs ......................................................................... 14
5
Operation Mode ............................................................................. 15
5.1 Mode Change ........................................................................................................................... 15
5.2 Operation Modes .................................................................................................................... 15
6
LCD Menu Operation ..................................................................... 18
6.1 LCD Touch Screen ................................................................................................................... 18
6.2 Default Screen .......................................................................................................................... 18
6.2.1 Initialization .................................................................................................................... 18
6.2.2 Default Screen Introduction ..................................................................................... 19
6.2.3 Backlight and Screensaver ........................................................................................ 19
6.3 Overview of LCD Menu and Icon ....................................................................................... 19
6.3.1 Overview of Submenu and Icon .............................................................................. 19
6.3.2 Layout of the submenus ............................................................................................ 20
6.4 Entering Password .................................................................................................................. 20
6.5 Language Setting ................................................................................................................... 21
6.6 Date and Time Setting ........................................................................................................... 22
6.7 Running Information Checking ......................................................................................... 22
6.8 History Information Checking ............................................................................................ 23
6.8.1 History Event Checking .............................................................................................. 24
6.8.2 History Data Checking ................................................................................................ 24
6.8.3 History Fault Checking ............................................................................................... 24
6.8.4 History Alarm Checking ............................................................................................. 25
6.9 Present Fault Information Checking ................................................................................. 25
6.10
Starting/Stopping the Inverter .............................................................................. 26
6.10.1 Starting the Inverter ................................................................................................. 26
6.10.2 Stopping the Inverter ............................................................................................... 26
6.11
Energy Output Deviation Adjustment ................................................................ 26
Load Default ................................................................................................................. 27
6.13
Firmware Version Checking .................................................................................... 27
7
Parameters of LCD .......................................................................... 28
7.1 Communication Parameters ................................................................................................ 28
7.1.1 Serial Port Parameter Setting.................................................................................... 28
7.1.2 Ethernet Parameter Setting....................................................................................... 29
7.2 Running Parameters ............................................................................................................... 29
7.2.1 Setting Running Parameters ..................................................................................... 29
7.2.2 Description of Running Parameters ....................................................................... 29
7.3 Protection Parameter ............................................................................................................. 30
7.3.1 Setting Protection Parameter ................................................................................... 30
7.3.2 Description of Protection Parameters ................................................................... 31
8
Inverter Functions .......................................................................... 34
8.1 Perfect Control Strategy........................................................................................................ 34
8.2 Active Power Limitation ........................................................................................................ 34
8.2.1 Active Power Limitation Introduction ................................................................... 34
8.2.2 How to Realize Power Limitation ............................................................................ 35
8.3 Reactive Power Adjustment ................................................................................................ 35
8.4 LVRT ............................................................................................................................................. 36
8.5 High Voltage Ride Through (HVRT) ................................................................................... 36
8.6 Temperature Derating ........................................................................................................... 37
8.7 MPPT ............................................................................................................................................ 38
8.8 Intelligent Temperature-Control Technology ................................................................ 38
8.9 Anti-PID Effect Function (Optional) .................................................................................. 38
8.9.1 Introduction to PID Effect .......................................................................................... 38
8.9.2 Anti-PID Function Setting .......................................................................................... 39
8.9.3 PID Repair ........................................................................................................................ 39
8.10
Insulation Monitoring Function ............................................................................ 39
8.10.1 Introduction ................................................................................................................. 39
8.10.2 Simple Troubleshooting .......................................................................................... 40
8.11
Protection Function ................................................................................................... 40
9
Routine Maintenance..................................................................... 42
9.1 Safety Instructions .................................................................................................................. 42
9.1.1 Safety Rules ..................................................................................................................... 42
9.1.2 Five Safety Rules ............................................................................................................ 42
9.2 Maintenance and Interval .................................................................................................... 42
9.3 Filter checking and cleaning ............................................................................................... 44
9.4 Replacement of the electrical components ................................................................... 45
10 Troubleshooting ............................................................................ 46
10.1
Fault Checking ............................................................................................................ 46
10.2
Fault and Troubleshooting of LED ........................................................................ 46
10.3
Fault and Troubleshooting on the LCD screen ................................................. 47
10.4
LCD Display Alarm Information and Troubleshooting .................................. 49
10.5
Other Faults .................................................................................................................. 50
11 Appendix ........................................................................................ 52
11.1
Technical Data ............................................................................................................. 52
11.1.1 Electrical Parameters ................................................................................................ 52
11.1.2 Mechanical Parameters ............................................................................................ 52
11.1.3 System Parameters .................................................................................................... 52
11.1.4 Display and Communication ................................................................................. 53
11.2
Exclusion of Liability.................................................................................................. 53
11.3
About Us ....................................................................................................................... 53
11.4
Contact Information .................................................................................................. 54
1 About this Manual
1.1 Foreword
Thank you for purchasing the SG500MX PV grid-connected central inverter from Sungrow Power
Supply Co., Ltd.. We hope that the device will meet with your satisfaction when you use it with
your PV system. Your commands and feedbacks on the performance and function of the device
are very important for our further improvement.
1.2 Validity
This Installation Manual is valid for the following inverter types:
Central Inverter SG500MX
The Central InverterSG500MX is referred to as “inverter” hereinafter unless otherwise specified.
1.3 Contents
This manual contains the following information:
Safety instructions
Safety instructions for the operation and maintenance of the inverter.
Product description
Basic information about the inverter is described, including its structure, function,
classification and so on.
Use
Introduce the inverter operation and use of HMI.
Routine maintenance
Introduce the daily maintenance of the inverter and the replacement of the accessories.
Troubleshooting
Introduce the potential faults and troubleshooting of the inverter.
Others
Technical data of the inverter, exclusion of liability and the way to contact Sungrow.
1.4 Target Group
This manual is aimed at technical personnel who are responsible and qualified for the inverter
installation and commissioning in the PV power system.
1.5 How to Use This Manual
Read this manual and other related documents carefully before any work on the inverter.
1 About this Manual
Operation Manual
2
Documents must be stored carefully and available at all times. Additional documents are also
available to the users:
Installation Manual (in the scope of delivery)
Connection Requirements for Medium-voltage Transformers for Central Inverters without
Transformer
All rights reserved including the pictures, markings and symbols used. Any reproduction or
disclosure, even partially, of the contents of this manual is strictly forbidden without prior
written authorization of Sungrow.
For user’s convenience, there are a large number of pictures in this manual. These
pictures are indicative only. For details about the device, please refer to the actual
product you receive.
1.6 Symbols Explanation
This manual contains important safety and operational instructions that must be accurately
understood and followed during the installation and maintenance of the equipment.
To ensure optimum use of this manual, note the following explanations of symbols used.
DANGER indicates a hazard with a high level of risk which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazard with a medium level of risk which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard with a low level of risk which, if not avoided, could result in
minor or moderate injury.
NOTICE indicates a situation which, if not avoided, could result in equipment or
property damage.
NOTE indicates additional information, emphasized contents or tips to help you
solve problems or save time.
1.7 Symbols on the Inverter Body
The symbols below may be pasted on the electrical parts of the inverter. Make sure to read the
following symbols and fully understand them before installing the equipment.
1 About this Manual
3
Symbols
Explanations
Risk of electric shock!
Hot surface!
Connection point for earth conductor
Protective conductor terminal
2 Safety Instructions
2.1 Intended Usage
The MX-series inverter (It will be referred to as inverter hereinafter unless otherwise specified), a
central inverter without transformer, is a crucial unit in a grid-connected PV power system.
Inverter is dedicated to converting direct current (DC) generated by the PV modules into
alternating current (AC), which conforms to parameters of local utility grid, and feeds the
alternating current into the utility grid.
With IP21 protection degree, the inverter must be installed indoors.
An example about intended usage of the inverter is shown below.
A
C
B
D
E
Fig. 2-1 Application of Inverter to the PV Power System
No.
Name
A
PV arrays
B
PV array combiner box
C
Inverter
D
Medium-voltage Transformer
E
Utility grid
The intended usage described in this section must be strictly observed. Any other or
additional usage other than the intended usage is not permitted.
Wiring and connections other than the contents described in this section may lead to
device damages and void warranty claims.
2.2 Important Safety Instructions
This section introduces the safety precautions during inverter installation and commissioning.
Read this manual carefully especially the safety instructions. For the detailed safety notices,
please refer to the corresponding installation and commissioning chapter.
Shock Hazard!
Death resulting from burns and electric shock upon touching the inverter live
components.
Do not touch the live components of the inverter or the utility grid.
Observe all safety regulations.
2 Safety Instructions
5
Lethal voltage inside the device!
Respect all warning labels on the product
Respect all safety instructions in this manual and other related documents.
Lethal Voltage!
Damage to the inverter or system fault may result in death by electric shock or fire!
Visual check if there is device damage or other dangers before operation.
Check if other external devices and circuit connection are safe.
Only operate the device when it is safe to do so.
After maintenance and service work to the inverter, power on the inverter following the
procedures described in this manual.
2.3 During Operation
2.3.1 Manual
Product manuals are indispensable part of the product.
Very important information about operation of the inverter is included in this manual. All the
descriptions in this manual, especially those safety-related items, must be complied with.
Please read all the instructions thoroughly prior to any operation work on the inverter.
This manual and relevant documents should be available for relevant persons at all times.
After maintenance or troubleshooting, no manual or paper should be left inside the inverter
cabinet.
2.3.2 Qualified Personnel
Only qualified electricians or personnel with professional knowledge can transport or install
the device.
Operators must be familiar with the whole power generation system and its working
principle.
Operators must be familiar with the Installation Manual and Operation Manual.
Operators must be familiar with country-specific standards and regulations.
2.3.3 Markings on the Inverter
Inverter enclosure and interior contains important warning and safety information. Do not
tear or damage it.
Nameplates located in the back panel and inside of the front door contain very important
parameter information. Do not tear or damage them.
2 Safety Instructions
Operation Manual
6
All safety instructions, warning labels and nameplate on the inverter body must be
clearly visible;
Replace the markings once they are damaged or unclear.
2.3.4 Safety Warning Signs
Please respect the followings during installation, daily maintenance or troubleshooting of the
inverter:
An obvious marking should be placed in the inverter upstream and downstream to keep the
switch from accidental reconnection;
A temporary warning sign or barrier must be posted around the installation area;
Remove the door keys and keep them appropriately after installation or maintenance work
is finished.
2.3.5 Emergency Escape Route
The emergency escape route is critical during an emergency situation.
Keep the escape route clear and unblocked at all times.
Never block or lock the emergency escape route
2.3.6 PV Arrays Hazards
High Voltages will exist between positive and negative polarities immediately when the PV
arrays are exposed to light. Electrical shock or arc may occur by accidental touch.
High voltage exists between the positive and negative polarity of the PV array.
Ensure complete disconnection between the inverter and the PV array
Avoid any accidental reconnections.
2.3.7 Live Line Measurement
High voltages are present in the device. Death resulting from burning and electric
shock upon touching the live components of the inverter. During live line
measurement,
use suitable protective equipment , for example dielectric gloves, and
accompany by other persons.
2.3.8 Measuring Instrument
Instrument for measurement of the electrical parameters should meet the requirements listed
below:
2 Safety Instructions
7
Instrument for measurement of the electrical parameters should be high quality
instrument with sufficient measuring range.
Make sure the connection and use of the instrument are correct to avoid arc and
other dangerous situations.
2.3.9 LCD Parameter Setting
Certain LCD settable parameters are closely related to the inverter operation, therefore these
parameters can only be set after reliable evaluation of the system and inverter.
Improper parameter setting may affect the functionality of the inverter.
Only qualified personnel can set the inverter parameter.
2.3.10 ESD Protection
The inverter may be damaged irreversibly by electrostatic discharge (ESD) at its
components.
During the operation of the inverter, please observe all the ESD-related safety
regulations!
Discharge electrostatic charge by touching the grounded conductor before
contacting any electronic components!
2.3.11 Moisture protection
Penetrating moisture may damage the inverter!
Don’t open inverter doors when relative humidity is above 95%.
Don’t install the inverter in rainy days.
2.3.12 Maintenance and Service
Wait at least 5 minutes for inner capacitors to discharge completely after stopping the
inverter before opening the inverter front door to maintain or service.
Before any service work, observe the following procedures.
Avoid any accidental re-connections.
Verify that no voltage or current is present with appropriate testing devices.
Ground and short-circuit whenever necessary.
Cover possible live parts to avoid accidental contact.
Ensure sufficient escape room.
2.3.13 Disposal of Waste
When the inverter is end of life, it cannot be disposed of together with household wastes. Please
contact the local authorized collection point.
2 Safety Instructions
Operation Manual
8
2.3.14 Others
Please observe country-specific standards and regulations.
Only service the device when it is voltage-free.
Never work alone when servicing this equipment. Two persons are required until the
inverter is properly shut down, de-energized and verified with a meter.
Other protective measures:
Use suitable protective equipment (for example safety goggles, earplugs, dielectric gloves,
insulating shoes) when maintaining or servicing the device.
Emergency aid should be prepared beforehand since the inverter is always installed far away
from the downtown area.
Every possible auxiliary method should be taken to ensure the safety of personnel and
device.
All the pictures and descriptions in this manual apply to the standard configuration
of the inverter. The actual product you receive may differ. Should you have any
specific requirements, please inform us.
This manual may not cover all possible situations. Should a specific problem occur
that is not explained in this manual, please contact Sungrow.
3 Product Description
3.1 Product Appearance
3.1.1 Brief Introduction
The front view and main external components of the inverter are shown below.
Fig. 3-1 Appearance of the Inverter
Item
Name
Description
A
LED Indicators
3 indicators: Power, Operation and Fault
B
LCD Touch Screen
Display data and perform control functions
C
Emergency Stop Button
Press down the button in emergency occasions and inverter
AC side power supply will be stopped immediately
D
Start/Stop Switch
Start/Stop the inverter
E
Door Lock
Three door locks, to lock/unlock front doors
3.1.2 LED Indicators
There are three LEDs at the upper left side of the front panel: POWER indicates the power is on;
OPERATION indicates the proper operation of the inverter; FAULT indicates a fault condition.
LED
Color
Description
POWER
Green
Control circuit power supply
OPERATION
Green
Inverter operates in the grid-connection mode.
FAULT
Red
A fault occurs and has not been removed.
The LED will be off when the fault is cleared.
3 Product Description
Operation Manual
10
Possible LED combinations and the meaning are listed in the following table:
LED status
Description
All three LEDs are on
System self-checking upon energization
(only
POWER
LED
is
on
after
the
self-checking)
“POWER” LED is on
Normal power supply, inverter not connect
to the grid
“POWER” is on
“OPERATION” is on
AC
and
DC
side
parameters
meet
grid-connection requirements. Inverter is
powering the grid.
“POWER” is on
“FAULT” is on
A fault occurs and not removed yet.
All LEDs are off
Inverter is disconnected from the power
supply.
3.1.3 LCD Display
LCD screen displays the operational information of the inverter and performs many functions as
follows:
Start or stop the inverter
Display real-time operating data
Display current faults and fault records
Adjust the running parameters
View history records
3.1.4 Emergency Stop Button
The inverter will be disconnected from the internal power supply immediately when pressing
down the emergency stop button.
Electrical shock hazards!
The pressing of the emergency stop button in no way implies that no voltage is
present in the electrical connection terminals inside the inverter.
Lethal voltages are present inside the inverter.
Use the emergency stop button to stop the inverter only in a time of crisis.
Improper or frequent use of the emergency stop button may lead to inverter damages.
Pressing the button with current carrying will lay great stress to the pertinent parts of
the inverter.
When you push this button, the inverter will disconnect immediately from the grid and the
button will be locked. You can restart the inverter by rotating the button clockwise to unlock it.
Open the AC switch first and then close it. Connect to the grid and the inverter will restart by the
LCD panel.
3.1.5 Start/Stop Switch
The Start/Stop Switch controls the start and stop of the inverter. Only when the start/stop switch
is put in the “start” position can user send effective start instruction through the LCD panel.
Otherwise, inverter will stay in Stop state.
3 Product Description
11
When you put the switch in the “stop” position, the inverter will stop through a stop command
sent to the control DSP.
3.2 Communication Solution
3.2.1 RS485 Communication Solution
SolarInfo Logger
Inverter can communicate with SolarInfo Logger via the RS485 standard serial port. SolarInfo
Logger can monitor the communication of single or multiple inverters.
Fig. 3-2 SolarInfo Logger Collects Data through RS485
PC
Inverter communicates with PC via RS485/RS232 converter. SolarInfo Insight is used to monitor
the communication of single or multiple inverters.
Fig. 3-3 PC collects data through RS485 Bus
SolarInfo Logger + PC
One or more inverters communicate with PC via SolarInfo Logger. SolarInfo Insight is used to
monitor the communication.
Fig. 3-4 SolarInfo Logger & PC Collect Data through RS485 Bus
3 Product Description
Operation Manual
12
3.2.2 Ethernet Communication Solution
Besides the standard RS485 communication, inverter also provides the optional Ethernet
communication solution. Please specify in your order if you need this communication solution.
Single inverter communication
If there is only one inverter, you can connect the RJ45 port of the inverter to the RJ45 port of
the PC directly. SolarInfo Insight is used to monitor the communication.
Fig. 3-5 Ethernet communication of one inverter
Multiple inverters communication
If there is more than one inverter, the Ethernet switch is required for communication.
SolarInfo Insight is used to monitor the communication.
Fig. 3-6 Ethernet communication of multiple inverters
The details of SolarInfo Logger and SolarInfo Insight are available on Sungrow’s
website. Please download the latest product materials when necessary.
4 Inverter Start/Stop
4.1 Starting the Inverter
4.1.1 Inspection before starting the inverter
After the maintenance or service work, you may start the inverter. Inspect the following
requirement before starting the inverter:
All connections are done by strictly following the installation manual and circuit diagram.
The coverings of the internal devices are fixed and secured.
The cabinet door is closed and the key is removed and stored by appointed personnel.
The emergency stop button is released and the Start/Stop switch is in the “Stop” position.
Turn the AC (Grid) Main Switch and the DC Main Switch to the “OFF” position.
Make sure, via suitable instruments, that there is no ground fault of the PV modules.
Measure the DC and AC current with multimeter to check if they fulfill the inverter startup
conditions and there is no overvoltage hazard.
After longtime storage, a thorough and professional test is necessary before starting
the inverter.
4.1.2 Steps to Starting the Inverter
When the abovementioned conditions are fulfilled, proceed as follows to start the inverter:
Step 1 Open the inverter AC cabinet door; Turn the AC switches to “ON” position; and lock the AC
cabinet door.
Step 2 Close the switches of inverter upstream combiner box;
Step 3 Open the DC cabinet door; Turn the DC switches to “ON” position; lock the DC cabinet door and
wait 1 minute.
Step 4 Turn the Start/Stop switch to the “START” position to start the inverter;
After startup, the inverter will automatically check if parameters of the DC and AC side meet the
grid-connection requirements. If so and the set time have been reached, the inverter will turn to
the OPERATION mode and feed the generated AC current to the grid.
Inverter needs no manual control in daily operation. Open the cabinet door only for
maintenance or troubleshooting and by qualified personnel only.
Keep the door closed and locked and store the keys of the door by appointed
personnel during normal operation.
4.2 Stopping the Inverter
Inverter stops during normal maintenance and service work or when a fault occurs.
4 Inverter Start/Stop
Operation Manual
14
4.2.1 Normal Stop
Proceed as follows to stop the inverter during normal maintenance and service work as follows:
Step 1 Stop the inverter through the stop operation on the LCD panel
Step 2 Turn the inverter Start/Stop switch to the “STOP” position
Step 3 Open the inverter AC cabinet door and disconnect the AC switch
Step 4 Disconnect the inverter downstream switches
Step 5 Open the inverter DC cabinet door and disconnect the DC switch
Step 6 Disconnect the inverter upstream switches
Step 7 Disconnect external power supply source if the inverter is in external power supply mode
Step 8 Inverter stops
During normal operation, disconnection of AC or DC switch is strictly forbidden.
Otherwise, the switch can be damaged and the inverter may also be damaged.
4.2.2 Inverter Stops when a fault occurs
Proceed as follows to stop the inverter when a fault or emergency occurs as follows:
Step 1 Push the emergency stop button or turn the start/stop switch to the “STOP” position
Step 2 Open the inverter AC cabinet door and disconnect the AC switch
Step 3 Disconnect the inverter downstream switches
Step 4 Open the inverter AC cabinet door and disconnect the AC switch
Step 5 Disconnect the inverter downstream switches
Step 6 Disconnect external power supply source if the inverter is in external power supply mode
Step 7 Inverter stops
Use the Start/Stop switch or emergency stop button only when emergency or a fault
occurs. Under normal conditions, stop the inverter by perform the stop command in the
LCD panel.
Push the emergency stop button directly in times of crisis to ensure timely response.
5 Operation Mode
5.1 Mode Change
After being energized, inverter can switch among different modes as shown in the figure below.
Fig. 5-1 Operation modes change
Upv is the DC input voltage of the inverter.
UpvStart is the inverter DC side startup voltage.
5.2 Operation Modes
Stop
This is the initial state of the inverter. The inverter DC and AC switches are in the “OFF” position;
the upstream and downstream connections are disconnected. The inverter is therefore
electricity-free.
Initial Standby
When the inverter upstream and downstream connections are connected and the AC/DC
switches are in the “ON” position, the inverter turns to the Initial Standby mode.
Inverter will continuously check if the PV array and the grid meet the grid-connection
requirements. If the inverter DC input voltage is higher than the inverter startup voltage and the
startup time is reached, whilst the requirements of the grid side parameter are satisfied, inverter
will turn from the Initial Standby mode into the Startup mode.
5 Operation Mode
Operation Manual
16
Startup
This is the transient process between the Initial Standby mode and the Run mode. Once the
Startup mode is complete, inverter will start powering the grid.
Run
In this mode, inverter converts the DC into AC and feeds it to the grid. Inverter tracks the PV
arrays’ maximum power point (MPP) to maximum the output energy.
Standby
In Run mode, inverter will enter into the Standby mode if the DC side current is as low as 0A for
a while.
Inverter will continuously check if the PV array meets the grid-connection requirements. If the
inverter DC startup voltage and the startup time are reached, inverter will turn into the Run
mode.
Fault
If a fault occurs during operation, inverter will automatically enter into the Fault mode. LCD
panel will display the fault type with the “Fault” indicator on until the fault is removed and
inverter turns into the Run mode.
During this period, if you want to start the inverter manually, first confirm the stop clear
protection program from the LCD panel and then start the inverter.
If the fault is unrecoverable, inverter must be stopped to perform maintenance work. Inverter
will automatically check if the fault is recoverable.
When there is a DSP fault or module fault, restart of the inverter through the LCD is
strictly forbidden. A power-off check is required before reenergizing the inverter.
Otherwise, the inverter may be damaged.
Emergency-stop
Stop the inverter by turning the Start/Stop Switch to the “STOP” position or push the emergency
stop button when a fault or emergency occurs.
If the inverter is stopped by the Start/Stop Switch, restart the inverter by
Step 1 Turning the Start/Stop switch to the START position.
Step 2 Perform Stop command from the LCD panel
Step 3 Perform Start command from the LCD panel
Step 2 is to remove the emergency stop protection program. Device will not
respond if you push Start directly without removing the stop protection program.
If the inverter is stopped by pushing the emergency stop button, the AC switch will trip and the
inverter will disconnect from the grid. Restart the inverter by
Step 1 Unlock the emergency stop button
Step 2 Turn the AC switch to the “OFF” position
Step 3 Turn the AC switch to the “ON” position
The inverter will be restarted automatically when the grid-connected requirements are met on
both DC and AC side.
5 Operation Mode
17
Key-stop
In Run mode, inverter will enter into the Key-stop mode by sending stop instruction via the LCD
panel if user needs to conduct maintenance or service work.
Alram Run
In Warning Run mode, inverter can keep running but send warning signal. User can check the
present warning information through the Working state on the LCD default screen or check the
latest 100 history warning information through Function/History information/his alarm. Inverter
automatically turns to Run mode when the alarm is removed.
6 LCD Menu Operation
6.1 LCD Touch Screen
The LCD touch screen, located at the eye-level in the front side of the inverter, is used for user to
view the data and set related parameters.
The LCD consists of two parts as shown in the following figure. The LEDs indicate the present
working state.
Fig. 6-1 Location and appearance of the LCD display
Item
Description
A
Run indicator, red at power on and green in normal operation
B
Data display and operation area
For user’s convenience, there are a large number of pictures about the LCD interface
in this chapter. The parameters and other details in those pictures are indicative
only. The actual product you receive may differ.
If the time shown on the LCD panel is different from the actual local time after time
calibration, please check and replace the button cells on the back of the LCD panel.
6.2 Default Screen
6.2.1 Initialization
The LCD is initialized when inverter is energized and then enters into the starting menu.
6 LCD Menu Operation
19
Initialization
Appears every time the inverter is energized. After
initialization, the default screen follows.
6.2.2 Default Screen Introduction
A
B
C
D
E
G
H
F
Item
Description
A
Yield data. The first line from the top is
the present active power; work state is
the transient state of the inverter.
B
Today’s active power curve to indicate
the power percentage (power value
divides the inverter nominal power
value).
C
DC side voltage and current
D
AC side line-to-line voltage and phase
current
E
Language selection button. Click to
change
among
English,
Chinese,
French, and Italian.
F
Present date and time
G
Success rate of the inverter internal
communication
H
Success
rate
of
communication
between the inverter and PC
Accessing to submenus mentioned below starts from the default menu.
LCD screen contains lots of parameters pertinent to the inverter operation. All
parameter configurations must be done by appointed personnel. DO NOT modify any
parameters before you fully understand this manual or consult the staff from Sungrow.
6.2.3 Backlight and Screensaver
If there is no operation to the screen for 5 minutes or more, the backlight will be off. Activate the
backlight by tapping the display and the display will return to the menu operated previously.
6.3 Overview of LCD Menu and Icon
6.3.1 Overview of Submenu and Icon
There are three buttons on the lower left side of the touch panel for user to operate
“Start/Stop”
, “Home”,
, “Function”
. The logical structures of these menus are
shown below:
6 LCD Menu Operation
Operation Manual
20
Main Menu
First sub-menu
Second sub-menu
Third sub-menu
Start/Stop
Start
-
-
Stop
-
-
Home
-
-
-
Function
Run-information
Real Time Data
-
Power curve
-
E-histogram
-
History-information
His-event
His-fault
-
His-data
-
His-alarn
Start/Stop
Start
-
Stop
-
Set-parameter
Sys-parameter
Language
&
Firmware
Ver.
Time
E-total adjust
Remote/Local control
Load default
Run-parameter
-
Pro-parameter
-
Com-parameter
Serial-port param.
Ethernet param.
6.3.2 Layout of the submenus
The layout of submenus is the same as that shown below except for the default menu.
Item
Description
A
Title bar
The first line from the top is the present success rate of communication.
The left side of the second line is the name of the present page, while the right side is
the present date and time.
B
Data display or parameter configuration.
C
From left to right: the three main icons; the return button to return to the previous
menu by tapping it.
For convenience’s sake, the operations on the menus are referred to as the menu name with
quotation marks. For example, the
menu will be referred to as “Set-parameter”.
6.4 Entering Password
Inverter is protected by password. User can enter into the “Set-parameter” sub-menu only after
entering the correct password. Proceed as follows to enter the password:
6 LCD Menu Operation
21
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter” and the password entering window pops out;
Tap the white edit box and a keypad pops out.
Enter the password through the keypad.
−
←: backspace key, delete the digit input
−
Clr: clear the digitals input
−
Esc: escape and close the keypad
−
Enter: confirm the password input
−
Max./Min.: the maximum and minimum value can be input; digital outside this range is
invalid
If the input password is 1111, user can enter into the normal parameter setting page and set
the system parameters, running parameters, protection parameters and communication
parameters.
Step 3 Press “Enter” to confirm the password input.
Step 4 If the password is incorrect, an “Error password” window will appear. Tap “Enter” and re-enter the
password.
6.5 Language Setting
User can set the language by either of the following two ways:
Conventional Way
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
6 LCD Menu Operation
Operation Manual
22
Step 4 Tap “Language & Firmware Ver.” and enter into the language and firmware version sub-menu;
Step 5 Select the target language.
Shortcut
The language setting shortcut (A) is at the lower right side of the Home menu. Select either
language by tapping the language button.
By tapping the button, the language will switch among English, Chinese, French and Italian.
Language on the button is the present display language of the display.
A
6.6 Date and Time Setting
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
Step 4 Tap “Time” and enter into the date and time setting sub-menu;
Step 5 Set the “Year”, “Month”, “Date”, “Hour”, “Minute” and “Second”. Tap the corresponding cell and the
keypad will appear;
Step 6 Set the time and date by tapping the keypad and confirm setting by Tapping “Enter”.
6.7 Running Information Checking
Running information contains all data pertinent to the inverter operation:
6 LCD Menu Operation
23
Real-time data
The work state, power supply mode, output power, DC voltage current, grid frequency,
power factor, internal temperature, module temperature, efficiency, positive insulation
resistance to the ground, AC and DC main switches states are included.
Internal statistics
The total power yields, amount of CO2 reduction, monthly power yields, total running hours
and the running time in minutes per day are included.
Output power curve
The output power curve shows the power yield on that particular day in percentage of the
nominal power. The data are updated every several seconds and the total diagram data will
be cleared at the beginning of a new day.
Proceed as follow to view the running information:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Run-information” and switch among “Real Time Data”, “Power curve” and “E-histogram”. The
default display is “Real Time Data”;
Step 3 Tap “Power curve” and enter into the power curve sub-menu;
Step 4 Tap “E-histogram” and enter into the electricity histogram sub-menu.
The display value is directive only and must not be used as a basis for invoicing.
6.8 History Information Checking
There are four kinds of history information: History event, history fault, history data and history
6 LCD Menu Operation
Operation Manual
24
alarm.
6.8.1 History Event Checking
Step 1 Tap “Function” from the default menu;
Step 2 Tap “History-information” and enter into the history information sub-menu;
Step 3 Tap “His-event” and enter into the history event sub-menu.
Up to 100 history events can be viewed from this sub-menu, with up to 5 records can be
shown in one page. The upper left side of the event table is the total number of the current
event records. Tap “Prev” or “Next” to turn pages up or down.
6.8.2 History Data Checking
System can record the inverter running information for the latest 90 days with the records
updated every 15 minutes.
History data displays the data related to the power yields and the electric quantity of the inverter.
Proceed as follows to check the history information:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “History-information” and enter into the history information sub-menu;
Step 3 Tap “His-data” and enter into the history data sub-menu.
Tap “Prev” or “Next” to turn pages up or down.
6.8.3 History Fault Checking
When a fault occurs, user can view the fault via the LCD screen and the history fault records as
follows:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “History-information” and enter into the history information sub-menu;
Step 3 Tap “His-fault” and enter into the history fault sub-menu.
6 LCD Menu Operation
25
Up to 100 history faults can be viewed from this sub-menu, with up to 5 records can be shown in
one page. The upper left side of the event table is the total number of the current fault records.
Tap “Prev” or “Next” to turn pages up or down.
6.8.4 History Alarm Checking
Proceed as follows to check the history warn information:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “History-information” and enter into the history information sub-menu;
Step 3 Tap “his-alarm” and enter into the history alarm sub-menu.
Up to 100 history alarms can be viewed from this sub-menu, with up to 5 records can be shown
in one page. The upper left side of the event table is the total number of the current warn
records. Tap “Prev” or “Next” to turn pages up or down.
6.9 Present Fault Information Checking
There may be one or more than one fault occurs to the inverter at the same time which can be
viewed through the LCD screen. Follow the description in this chapter to view the fault
information when faults occur.
Fault A
Tap the cell (A) on the right of the “Work Status” from
the Home menu.
The fault window will appear with the
present fault in red.
6 LCD Menu Operation
Operation Manual
26
6.10 Starting/Stopping the Inverter
Usually, the inverter will start automatically when the grid-connected requirements
are met.
Follow either of the two ways below to start/stop the inverter through the LCD screen:
Tap “Start/Stop” from the default menu.
Tap “Start/Stop” from the Function menu.
6.10.1 Starting the Inverter
In Start/Stop screen, click Start and a “Confirm start” window appears.
Tap “Enter” to start the inverter while tap “Cancel” to cancel the operation.
6.10.2 Stopping the Inverter
In Start/Stop screen, click Stop and a “Confirm stop” window appears.
Tap “Enter” to stop the inverter while tap “Cancel” to cancel the operation.
6.11 Energy Output Deviation Adjustment
Energy output deviation adjustment is useful when the total power output displayed in LCD
(E-total) is different from the reading value of the external power measuring device (e.g. an
ammeter).
(Energy-adj value)= (Real measured value)-(E-tot reading value).
To adjust the date or time, proceed as follow:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
Step 4 Tap “E-total adjust” and enter into the energy output deviation adjustment sub-menu;
6 LCD Menu Operation
27
Tap the cell below the “Compensation” and the keypad appears. Enter the energy compensation
by tapping the keypad;
Step 5 Tap “Enter” to confirm the setting.
6.12 Load Default
Proceed as follows to perform the load default:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
Step 4 Tap “Load default” and the password inputting window appears;
The password is “1111”. The system will be reset after entering the password.
6.13 Firmware Version Checking
User can view the firmware version of LCD and DSP as follows:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
Step 4 Tap “Language & Firmware Ver.” and enter into the language and firmware version sub-menu;
Step 5 The firmware version of LCD and DSP is shown at the bottom of the page.
7 Parameters of LCD
7.1 Communication Parameters
Improper
communication
parameter
configuration
may
lead
to
inverter
communication failure!
Follow strictly the instructions of the plant staff to configure the communication
parameters.
There are the standard RS485 communication and Network communication. User can set the
communication address and protocol through the LCD screen when the hardware connection is
complete and the inverter is energized.
Proceed as follows to set the communication parameters:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Com-parameter” after entering the correct password.
Set parameter from the Serial Port Parameter interface for RS485 serial communication;
Set parameter from the Network Parameter interface for Network communication
7.1.1 Serial Port Parameter Setting
Click “Serial port param” to enter the following interface.
Three parameters pertinent to RS485 serial port communication can be set according to the
parameter range shown on the display.
“Address” is prescribed by the plant staff and the address for each inverter must be unique when
there is more than one inverter. “Baud” and “protocol” are selected according to the
communication method adopted.
Enter the device address with the aid of the pop-up keypad while select the Baud rate and
communication protocol through the pull-down list.
7 Parameters of LCD
29
7.1.2 Ethernet Parameter Setting
Click Network Parameter to enter the following interface.
Seven parameters pertinent to the Network communication can be set. DNS address 1 and DNS
address 2 can be set to the default value. Other parameters are assigned by plant staff.
Set parameter with the aid of the pop-up keypad.
7.2 Running Parameters
7.2.1 Setting Running Parameters
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Run-parameter” after entering the correct password.
Step 4 Set the running parameter by tapping the pop-up keypad and tap ENTER to confirm setting. Tap
“Prev” or “Next” to turn pages up or down.
7.2.2 Description of Running Parameters
Descriptions of the running parameters are shown in the following table.
Parameter
Description
Vmppt-max (V)
Unavailable
Vmppt-min (V)
Unavailable
T-start-wait (s)
The time from the AC/DC parameters meet the grid-connection
conditions to the inverter begins to generate power.
T-stop-delay (s)
The time from the LCD display or upper computer sends stop
command to inverter performs the stop command
stop slope (%/s)
Active power decline rate from inverter performs stop command to
inverter stops
P-rise rate (%/s)
Percentage that the active power rise per second accounted for
the nominal power (%/s)
P-decline rate (%/s)
Percentage that the active power decline per second accounted for
the nominal power (%/s)
Limit Power (%)
Percentage of active power output in nominal output power (%)
Pf
cosφ
Q-limit (%)
Percentage that the reactive power rise accounted for the nominal
power (%)
Q-adjust switch
Refer to 8.3
7 Parameters of LCD
Operation Manual
30
Parameter
Description
Power-off saved (Pf)
If the power factor setting can be saved when the LCD screen is
powered off
Power-off saved (P-limited)
If the limit power(%) setting can be saved when the LCD screen is
powered off
SVG switch
If the reactive power compensation is activated or deactivated
T-recover (s)
Automatic recovery time when fault occurs
Setting ranges and default values of the running parameters are described in the following
table.
Parameter
Range
Default
Vmppt-max (V)*
460~850
850
Vmppt-min (V)*
460~850
460
T-start-wait (s)
0~600
60
T-stop-delay (s)
0~600
0
stop slope (%/s)
0.1~100
100
P-rise rate (%/s)
0.01~10
10
P-decline rate (%/s)
0.01~10
10
Limit Power (%)
0~110
110
Pf
-0.9~-1/0.9~1
1
Q-limit (%)
-100~100
0
Q-adjust switch
Close/Pf/Q-limit
Pf can be adjusted
Power-off saved (Pf)
Save/Not Save
Save
Power-off saved (P-limited)
Save/Not Save
Not Save
SVG switch**
Enable/Disable
Disable
T-recover (s)
20~600
60
Note: * non-settable
** at night when the inverter enters standby mode (but not enters the deep standby mode with
lower power consumption), the SVG function needs to be activated: first stop the inverter by the
LCD button and then start; set the SVG switch to “Enable”. The SVG is an optional function for this
inverter.
Improper parameter configuration may affect the normal operation of the inverter!
Only authorized personnel can configure these parameters.
Should any question or doubt occurs, please contact Sungrow.
Please refer to the LCD screen for the specific setting ranges of these parameters.
7.3 Protection Parameter
7.3.1 Setting Protection Parameter
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Pro-parameter” after entering the correct password.
7 Parameters of LCD
31
Set the protection parameter by tapping the pop-up keypad and tap ENTER to confirm setting.
Tap “Prev” or “Next” to turn pages up or down.
Improper parameter configuration may affect the normal operation of the inverter!
Only authorized personnel can configure these parameters.
Should any question or doubt occurs, please contact Sungrow.
7.3.2 Description of Protection Parameters
Descriptions of the protective parameters are shown in the following table.
Parameter
Description
Ⅰ_Vgrid-max(V)
Set the grid over-voltage protection I value. Protection is
activated when voltage exceeds this value.
Ⅱ_Vgrid-max(V)
Set the grid over-voltage protection II value. Protection is
activated when voltage exceeds this value.
Ⅰ_T-Vhigh trip(ms)
Set the protection time of grid over-voltage protection I
Ⅱ_T-Vhigh trip (ms)
Set the protection time of grid over-voltage protection II
Recover_Vgrid-max(V)
Inverter recovers normal operation when grid voltage is below
this value
Ⅰ_Vgrid-min(V)
Set the grid under-voltage protection I value. Protection is
activated when voltage is below this value.
Ⅱ_Vgrid-min(V)
Set the grid under-voltage protection II value. Protection is
activated when voltage is below this value.
Ⅰ_T-Vlow trip(ms)
Set the grid under-voltage I tripping protection time
Ⅱ_T-Vlow trip (ms)
Set the grid under-voltage II tripping protection time
Recover_Vgrid-min(V)
Inverter recovers normal operation when grid voltage exceeds
this value
Ⅰ_Fgrid-max((Hz)
Set the grid over-frequency protection I value. Protection is
activated when frequency exceeds this value
Ⅱ_Fgrid-max((Hz)
Set the grid over-frequency protection II value. Protection is
activated when frequency exceeds this value
Ⅰ_T-Fhigh trip(ms)
Set the grid over-frequency I tripping time
Ⅱ_T-Fhigh trip (ms)
Set the grid over-frequency II tripping time
Recover_Fgrid-max(Hz)
Inverter recovers normal operation when grid frequency is below
this value
Ⅰ_Fgrid-min((Hz)
Set the grid under-frequency protection I value. Protection is
activated when frequency exceeds this value
Ⅱ_Fgrid-min((Hz)
Set the grid under-frequency protection II value. Protection is
activated when frequency exceeds this value
Ⅰ_T-Flow trip(ms)
Set the grid under-frequency I tripping time
Ⅱ_T-Flow trip (ms)
Set the grid under-frequency II tripping time
Recover_Fgrid-min((Hz)
Inverter recovers normal operation when grid frequency exceeds
this value
LVRT switch
Enable or disable the LVRT switch
LVRT normal vol min(V)
Refer to Fig. 8-1Lower voltage withstand requirements, U1
7 Parameters of LCD
Operation Manual
32
Parameter
Description
Unavailable
LVRT tolera vol min(V)
Refer to Fig. 8-1Lower voltage withstand requirements, U2
Unavailable
LVRT T1(ms)
Refer to Fig. 8-1Lower voltage withstand requirements, T1
LVRT T2(ms)
Refer to Fig. 8-1Lower voltage withstand requirements, T2
LVRT dynamic Kf factor
Ratio of reactive power compensation and voltage dropping
depth during LVRT
HVRT switch
Enable or disable the HVRT switch
HVRT normal vol max(%)
Refer to Fig. 8-2High voltage withstand requirements, U2
Unavailable
HVRT tolera vol max (%)
Refer to Fig. 8-2High voltage withstand requirements, U1
Unavailable
Tmax-HVRT normal(ms)
Refer to Fig. 8-2High voltage withstand requirements, T2
Tmax-HVRT tolera(ms)
Refer to Fig. 8-2High voltage withstand requirements, T1
Active Islanding
Enable or disable the Anti-islanding function
I leakage-pro(A)
Set the current leakage protection value
Anti-PID mode
If Anti-PID mode is enabled, you may set the Anti-PID mode
(Invalid, Suppression and Repair)
Ins monitor measure time (S)
Set the insulation monitor measure time
Ins
monitor
protect
threshold(K)
Set the threshold value of the insulation monitor resistance
Setting ranges and default values of the protective parameters are described in the following
table.
Parameter
Range
Default
Ⅰ_Vgrid-max(V)
346.5~472.5
362
Ⅱ_Vgrid-max(V)
346.5~472.5
409.5
Ⅰ_T-Vhigh trip(ms)
40~600000
2000
Ⅱ_T-Vhigh trip (ms)
40~600000
100
Recover_Vgrid-max(V)
346.5~472.5
346.5
Ⅰ_Vgrid-min(V)
31.5~283.5
252
Ⅱ_Vgrid-min(V)
31.5~283.5
157.5
Ⅰ_T-Vlow trip(ms)
40~600000
2000
Ⅱ_T-Vlow trip (ms)
40~600000
100
Recover_Vgrid-min(V)
31.5~283.5
283.5
Ⅰ_Fgrid-max((Hz)
50.2~53/60.2~63
50.5/61.5
Ⅱ_Fgrid-max((Hz)
50.2~53/60.2~63
50.5/62
Ⅰ_T-Fhigh trip(ms)
40~600000
160
Ⅱ_T-Fhigh trip (ms)
40~600000
160
Recover_Fgrid-max(Hz)
50~53/60~63
50.2/60.2
Ⅰ_Fgrid-min((Hz)
46~50/56~60
47.5/57.5
Ⅱ_Fgrid-min((Hz)
46~50/56~60
47.5/57.5
Ⅰ_T-Flow trip(ms)
40~600000
160
Ⅱ_T-Flow trip (ms)
40~600000
160
Recover_Fgrid-min((Hz)
46~50/56~60
49.5/59.9
LVRT switch
Enable/Disable
Enable
LVRT normal vol min(V)
270~283.5
283.5
LVRT tolera vol min(V)
15.7~126
63
LVRT T1(ms)
500~1500
1000
LVRT T2(ms)
2500~3500
3000
LVRT dynamic Kf factor
0~3
1.5
HVRT switch
Enable/Disable
Enable
7 Parameters of LCD
33
Parameter
Range
Default
HVRT normal vol max(%)
110~120
110
HVRT tolera vol max (%)
120~140
130
Tmax-HVRT normal(ms)
100~20000
10000
Tmax-HVRT tolera(ms)
100~5000
500
Active Islanding
Enable/Disable
Disable
I leakage-pro(A)
1~8
5
Anti-PID mode
Invalid/Suppression/Repair
Invalid (mode disabled)/
Suppression
(mode
enabled)
Ins monitor measure time (S)
30/150/300/600
150
Ins
monitor
protect
threshold(K)
15~100
33
Note: * non-settable
Please refer to the LCD screen for the specific setting ranges of these parameters.
8 Inverter Functions
8.1 Perfect Control Strategy
The following three control strategies are provided for user to perform control functions and
configure relevant parameters.
“Remote”: The control codes can be sent only by the remote control machine.
“Local”: The control codes can be sent only by the LCD screen.
“Remote/Local”: Both “Remote” and “Local” codes are effective.
Proceed to set the control strategy on the LCD screen as follows:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password.
Step 4 Tap “Remote/Local control” and enter into the Remote/Local control sub-menu.
Step 5 Select the control method through the pull-down list.
8.2 Active Power Limitation
8.2.1 Active Power Limitation Introduction
Situations, call for power limitation, are listed below:
Potential threatens to the inverter safety operation
Over-load of the grid branch connected to the inverter
Islanding
Factors affecting the stability of the stable grid status and dynamic grid status
Frequency rising affects the system stability
Grid maintenance
Grid management
8 Inverter Functions
35
8.2.2 How to Realize Power Limitation
Improper parameter configuration may affect the normal operation of the inverter!
Only authorized personnel can configure these parameters.
Should any question or doubt occurs, please contact Sungrow.
User can adjust the active power output through the LCD display:
Step 1 Tap “ Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Run-parameter” after entering the correct password;
Step 4 Set the “Limit Power (%)” parameter by tapping the pop-up keypad;
Step 5 Tap “Enter” to confirm setting.
Parameters related to power limitation (P-rise rate (%/s) and P-decline rate (%/s)) are
also included in the running parameter setting sub-menu and can be set
accordingly.
8.3 Reactive Power Adjustment
Inverter can provide reactive power output. User can open or close the reactive power
adjustment switch and set the reactive power output through the LCD screen.
Reactive power limitation is performed through the running information sub-menu as follows:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Run-parameter” after entering the correct password;
Step 4 Turn the page down to select the “Q-adjust switch”. Tap the pull-down list and there are three
options:
Close: reactive power cannot be adjusted
Pf: adjust the reactive power by setting power factor
Q-limit: adjust the reactive power by setting reactive power percentage
Step 5 If Pf is selected, the power factor can be set in the “Run-information” sub-menu; if “Q-limit” is
selected, the “Q-limit (%)” can be set in the “Run-information” sub-menu.
8 Inverter Functions
Operation Manual
36
Improper parameter configuration may affect the normal operation of the inverter!
Only authorized personnel can configure these parameters.
Should any question or doubt occurs, please contact Sungrow.
8.4 LVRT
LVRT requires: PV plant can operate normally within certain voltage drop range and duration
when the voltage of the grid-connected point drops due to the power system failure or
disturbance; PV plant can provide the dynamic reactive power support during the period.
Active power recovery
If the power station still connects to the grid during power system failure, the active power will
recover from the moment the fault is removed at the speed of at least 30% nominal
power/second.
Dynamic reactive current support
During LVRT, power station should feed reactive current to the power system as per
requirements. For a station whose 500kV or 750kV voltage is stepped up from the 220kV or
330kV voltage and then connects to the power station group, it should feed reactive current to
the grid when a short-circuit occurs and the voltage drops.
Zero voltage ride through
When the grid-connection point voltage drops to zero, power station can operation normally for
0.15 second.
Fig. 8-1 Lower voltage withstand requirements
The inverter meets the abovementioned requirements.
8.5 High Voltage Ride Through (HVRT)
The detailed requirements of HVRT is shown in the following table:
Grid-connection pint voltage
Requirements
1.1Upu
8 Inverter Functions
37
Grid-connection�point�
voltage�(Upu)
Fig. 8-2 High voltage withstand requirements
The inverter meets the abovementioned requirements.
8.6 Temperature Derating
When the ambient temperature is below 50℃, inverter can operates at 110% of the overload
condition. When the ambient temperature reaches 55℃, inverter can keep the nominal power
output. When the ambient temperature is above 65℃, inverter enters into protection mode.
Temperature(℃)
1.0
1.1
0
55
25
50
Nominal�value
65
1.2
L1�=�10kW/℃
L2�=�50kW/℃
-30
Fig. 8-3 Inverter temperature derating function
Ambient temp. T
Inverter operation situation
T<-30℃
Inverter starts with the aid of auxiliary heater
-30℃65℃
Enter protection mode;
Automatically restart when temperature drops below 55℃
8 Inverter Functions
Operation Manual
38
8.7 MPPT
Maximum Power Point Tracking (MPPT) is a technique that the inverter uses to get the maximum
power from the PV arrays. PV arrays have a complex relationship between solar irradiation,
temperature and total resistance that produces a non-linear output efficiency known as the I-V
curve.
Fig. 8-4 I-V curve
8.8 Intelligent Temperature-Control Technology
Inverter will continuously detect the IGBT temperature and adjust the fan speed accordingly.
When the module temperature is low, inverter will decrease the fan speed to lower the device
noise and decrease the device operation consumption. As the module temperature increases,
inverter will increase the fan speed for well ventilation.
The intelligent temperature-control technology can synchronize the speed of fan and
temperature of the IGBT module and thus optimize the module temperature and other
conditions.
8.9 Anti-PID Effect Function (Optional)
8.9.1 Introduction to PID Effect
Potential Induced Degradation (PID) of the solar modules is a performance degradation caused
by high negative voltage. The PID effect can occur with all crystalline silicon solar cells that are
embedded in glass-foil modules, leakage currents can result under unfavorable conditions
(accelerated by high humidity and temperature) where the module joins with the frame and
causes short-circuits that lower the overall performance of the system.
This inverter is equipped with optional anti-PID function to effectively prevent the PID at the
station side.
8 Inverter Functions
39
8.9.2 Anti-PID Function Setting
For inverter with optional anti-PID function, the enable and disable of this function can
only be performed by personnel from Sungrow. Please contact Sungrow if you need to
switch this function.
Proceed as follows to set the mode if the Anti-PID mode is enabled:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Pro-parameter” after entering the correct password;
Step 4 Click Next to find the page with “Anti-PID mode” and select the mode by the drop-down list
(Suppression/Repair)
Step 5 Select according to the on-site situation.
8.9.3 PID Repair
Please make sure the “Anti-PID mode” in the protection parameter of the inverter is
“Repair” when enabling the PID repair function.
If the inverter is in deep standby state or the repair process is interrupted, user can enable the
repair function manually from the LCD as follows:
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Pro-parameter” after entering the correct password;
Step 4 Click Next to find the page with “PID repair” and click to enable the manual repair.
If this function is enabled, the Work state in the main screen will show “Anti-PID run”. User may
find the “Negative Vgnd” is about 500V from “Function/Run-information/Real Time Data”
If there is Key stop or Emergency stop or a device fault during the repair process, the
repair process will automatically stop.
8.10 Insulation Monitoring Function
8.10.1 Introduction
Insulation resistance is an important parameter related to safety operation. If the insulation
resistance is low, the direct contact protection and indirect contact protection may be failed;
meanwhile the fault current against the ground and the short circuit caused by low insulation
resistance may lead to electric fire, device damage or even physical hazards. Sungrow inverter is
8 Inverter Functions
Operation Manual
40
equipped with insulation resistance monitoring function to detect the system insulation
resistance in real time. If the resistance is detected to be low, it will send alarm at the first time to
remind the user and prevent potential hazards.
The insulation monitoring function can be divided into two kinds:
For inverter without the anti-PID function or inverter is equipped with this function but it is
disabled, both the negative insulation resistance and positive insulation resistance against
the ground should be detected.
For inverter with the anti-PID function and this function is enabled, the DC negative and the
ground is equipotential. Therefore, only the positive insulation resistance to the ground
needs to be detected.
8.10.2 Simple Troubleshooting
Regardless of the inverter setting, when the insulation resistance is below the threshold (settable
from the LCD display), inverter will send alarm signal and the Operation LED will turn to yellow.
After receiving the “low insulation resistance” alarm signal, user should stop the device and
check the specific insulation resistance from the LCD screen “Function/Run-information/Real
time data”.
If the insulation resistance recovers to normal, the fault loop is in the AC side.
If the insulation resistance is still low, the fault loop is in the DC side.
No matter the fault is in the DC side or in the AC side, a thorough checking and troubleshooting
after the system is power down is necessary.
8.11 Protection Function
Inverter has perfect protection functions to protect itself when input voltage or grid is abnormal
until the anomaly is removed and the inverter can operate normally.
DC over-voltage protection
When the DC voltage of the PV array exceeds the max. DC voltage, inverter will stop operating,
send warning signal and display the fault type on the LCD screen.
Inverter can detect the abnormal voltage and respond quickly.
AC over/under-voltage protection
When the inverter AC output voltage exceeds the allowable range, inverter will stop feeding the
grid, send warning signal and display the fault type on the LCD screen.
Inverter can detect the abnormal voltage and respond quickly.
Frequency anomaly protection
When the grid frequency exceeds the allowable range, inverter will stop feeding the grid, send
warning signal and display the fault type on the LCD screen.
Inverter can detect the abnormal frequency and respond quickly.
Islanding protection
Islanding is a condition that can occur if the utility grid is disconnected while the inverter is
operating and the local load of the inverter is similar to the present output power.
8 Inverter Functions
41
“Islanding” is a potential threaten to devices and operators.
If the inverter continues power supply after the grid is out of power supply, death or injury
may occur to the maintainers during maintenance.
When power grid fails, the inverter continues power supply. Once the grid resumes, a surge
current may occur and damage devices.
Inverter is equipped with anti-islanding protection function.
In anti-islanding protection state, high voltage is still present. Disconnect the main
switch and discharge before testing or maintenance.
Reverse polarity protection
When the PV array inputs’ polarities are connected reversely, inverter will stop and protect itself
against damage and resume normal operation after the connection is corrected.
Overload protection
When the PV array output power exceeds the inverter permissible maximum input power,
inverter will limit the power yield at maximum AC power point. If the temperature exceeds the
permissible value, inverter will automatically stop operating unless the condition resumes
normal.
Ground protection
The grounding cables are equipped with the leakage current sensor. When the leakage current is
detected to exceed the setting value (default value is 5A, can be set from the LCD screen) ,
system will send instruction to stop the inverter and display the fault type on the LCD screen.
Module over-temperature protection
IGBT modules inside the inverter uses thermal sensor with high-precision to monitor the
real-time module temperature. Once the module temperature is detected to be high, DSP will
send direction to stop the inverter or derate the output.
Internal over-temperature protection
The inverter is equipped with high-precision thermal sensor to monitor the internal temperature
of the inverter. Once the over-temperature is detected, DSP will help to maintain the safe
operation of the inverter by sending instruction to stop the inverter or derate the power output.
9 Routine Maintenance
Due to the effect of ambient temperature, humidity, dust and vibration, the inner components
of the inverter will be aging and worn out. To ensure the system safety and maintain the
efficiency of the inverter, it is necessary to carry out routine and periodic maintenance.
All measures, which can help the in inverter be in good working conditions, are within the
maintenance scope.
9.1 Safety Instructions
9.1.1 Safety Rules
Only qualified personnel can perform the work described in this chapter.
Do not leave any screws, washers or other metallic parts inside the inverter to avoid
damages to the inverter.
Disconnection of the switches in no way implies that there is no voltage of the cable
connection terminals inside the AC and DC cabinet. To avoid the risk of electric shock
before opening the cabinet door,
Disconnect the switches;
Disconnect the upstream and downstream switch of the PCS.
Wait at least 5 minutes after inverter stops before any work on the inverter.
9.1.2 Five Safety Rules
Respect the following five rules during maintenance or service on the inverter to ensure the
safety of the maintainer.
Disconnect the inverter from all the external connections and internal power supplies.
Ensure that the inverter will not be started accidentally.
Verify that the inverter interior is discharged completely with a multimeter.
Necessary ground and short circuit connect.
Cover the adjacent electrical components with insulation cloth during operation.
9.2 Maintenance and Interval
Recommended routine maintenance work and maintenance interval are shown in the following
table.
9 Routine Maintenance
43
Item
Method
Interval
Save
software
data
Read out SolarInfo Logger data;
Save running data, parameters and logs to a disk or
a file;
Check each parameter setting;
Update software
Once a month
System general
running
status
and
environment
Check the inverter for visible damages or
deformation;
Check the inverter for any abnormal noise during
running;
Check each parameter of the inverter during
normal operation;
Check the principal components;
Check if the enclosure temperature is normal with
the thermal imager;
Check the air inlet and outlet;
Check the ambient humidity, dust and air inlet
filter;
Notice! Check the air inlet and outlet. The equipment
may be damaged by overheating.
Every six months
System cleaning
Check whether the circuit board and the
component are clean;
Check the temperature and dust of the heat-sink.
Use vacuum cleaner to clean the module if necessary;
Replace the air filter.
From
every
six
months to annually
depending on the
dust deposits.
Power
circuit
connection
Check whether the power cable connections are
loose. Retighten them with the torque specified in
the manual if necessary;
Check if the power cables and control cables,
especially the surface in contact with the metal are
damaged;
Check if the wrap belt of the connection terminals
is strip-off.
Six
months
after
commissioning
for
the first time and
then once every six
month to a year
Terminal
and
cable
connection
Check whether the screws of the control terminals
are loose. Refasten them with screwdriver if
necessary;
check whether the terminals of the main circuit are
in poor contact and whether the screws are hot;
check if the connection busbar or screws are
discoloring.
Visual check the wiring copper bus or bolt for
discoloration;
Once per year
Fan
maintenance
and
replacement
check if there is crack in the fan blade;
Check if there is abnormal noise during the
running of the fan;
Replace the fan if necessary.
Once per year
Device
maintenance
routine check of the corrosion of the metal
components (once six months)
annually check the contactors (auxiliary switches
and micro-switches) to ensure the optimal operation;
Check the running parameters (Voltage and
insulation especially)
From
every
six
months to annually
Safety function
Check the emergency stop button and the LCD
stop function;
Simulation shutdown and check the shutdown
signal communication signal;
Check the warning labels and other markings for
damage or unclearness. Replace them if necessary.
From
every
six
months to annually
Software
maintenance
Optimize software
Check each parameter setting
From
every
six
months to annually
9 Routine Maintenance
Operation Manual
44
Item
Method
Interval
LCD
time
display
Check if the time displayed on the LCD display is
correct;
Replace the button cells on the back of the LCD
panel if time is incorrect after calibration.
Everyone and a half
year
Check the module fans inside the cabinet periodically and the fans on top of the
cabinet for abnormal operation and abnormal noise. If so, there may be dust
penetrating inside the inverter. Stop the inverter and clean the dust.
Wait at least 5 minutes after the inverter discharge completely. Before cleaning, make
sure, with multimeter, the inverter internal is discharged completely to avoid electric
shock.
Almost all maintenance work needs to remove the internal protective grid during
maintenance. Make sure to reassembly the grid and fasten all the screws after the
maintenance work.
Make sure all bolts are securely fixed.
The frequency of maintenance operations could be increased according to the
environmental conditions of the place where the inverter is suited, plant capacity
and on-site situations.
9.3 Filter checking and cleaning
It is recommended to check and clean the inverter filter at least once every six
months.
The maintenance interval should be shortened to once every three months or
shorter if the dust deposition is heavy.
Cool air comes into the inverter from the front and hot air is exhausted from the inverter from
the top. There are two air inlet windows on the lower front side of the inverter cabinet (as
marked by item “A” in the following figure). Proceed as follows to clean or replace the filter
periodically.
9 Routine Maintenance
45
A
Proceed as follows to clean or replace the filter:
Step 1 Remove the six screws used to fix the frame of the air inlet windows.
Step 2 Remove the filters and clean them with warm water and detergent, and wait until it is
completely dry; if the filter needs to be replaced, remove the old filter and place the new one.
Step 3 Reassemble the filter according to the reverse procedure shown above.
Contact Sungrow to order the filter. User can cut proper filters out of the larger filter.
9.4 Replacement of the electrical components
The electrical components inside the inverter must be replaced by the same
components from the same manufacturer and with the same model number.
The model number can be acquired from the marking of the inverter or the component
itself. If otherwise, please contact Sungrow.
If the field work needs to replace the components with products from other
manufacturer and with different model number, a prior analysis and confirmation by
Sungrow is needed.
Failure to follow this procedure may lead to physical injury or death and void all
warranty from Sungrow.
Lethal voltages are present inside the inverter when a fault occurs.
Only qualified personnel can perform the troubleshooting described in this chapter.
Qualified means that the operator has received professional training on devices
troubleshooting.
Do not perform any troubleshooting other than that specified in this manual.
Respect all safety instructions during troubleshooting.
Disconnect all AC and DC Switches and external power supplies before
troubleshooting.
Should any questions or doubts arise that are not covered by this manual, please contact us.
If you provide our customer service assistant the following information, it will be of great help
for us to diagnose and solve the problem in your system:
Type of inverter
Serial number of the inverter
Manufacturer, model and configuration of the PV arrays connected to the inverter
Inverter communication solution
Fault and brief description of the fault phenomenon
A picture of the fault if necessary
10.1 Fault Checking
If any power output anomaly is observed, you may check the following items before contacting
Sungrow.
Open-circuit voltage of the PV arrays
State of the emergency stop button
Power limitation state
10.2 Fault and Troubleshooting of LED
LED state
Description
No LED is on
Disconnect the AC/DC voltage for 5 minutes. Reconnect the AC/DC
voltage.
If the LEDs keep off, repair or replace them.
Contact Sungrow if the malfunction cannot be removed following
these instructions.
POWER is off
No power supply to the inverter.
First ensure the power supply and the grid-connection are normal.
Disconnect the AC/DC voltage for 5 minutes and reconnect them.
If the LED keeps off, please contact Sungrow.
OPERATION is off
The grid is not in grid-connection state.
First check all the AC/DC connection. Make sure, using multimeter,
that the DC input voltage exceeds the inverter startup voltage.
Make sure the grid and parameters meet the requirements of safe
operation.
If the malfunction cannot be removed by following these
instructions, please contact Sungrow.
FAULT is on
A fault is not removed yet.
Please refer to the touch screen for the detailed fault information and
take corresponding troubleshooting.
If the malfunction cannot be removed by following these
instructions, please contact Sungrow.
10.3 Fault and Troubleshooting on the LCD screen
This section is dedicated to the faults shown on the LCD, possible reasons and troubleshooting.
In case the fault cannot be removed following the instructions in this section, please contact
Sungrow.
Fault
Vdc-high
Possible
reason
DC voltage exceeds the max. DC voltage
Measure
Check the configuration of the PV array and reduce the open-circuit voltage of the PV
array
Note
Please contact the installers of the PV arrays
Fault
Vac-high
Possible
reason
The grid voltage is above the maximum grid voltage
Measure
Check the grid voltage (or if the grid-connected wire is too thin)
Remark
Inverter automatically reconnects to the grid once the grid voltage recovers normal
Fault
Vac-low
Possible
reason
The grid voltage is below the minimum grid voltage
Measure
Check the grid voltage
Check if the AC cables are securely connected.
Remark
Inverter automatically reconnects to the grid once the grid voltage recovers normal
Fault
PV pol-rev
Possible
reason
The positive and negative poles of the DC side are connected reversely.
Measure
Check the DC connection to for reverse connection after inverter voltage-free
Remark
-
The grid frequency is outside the permitted range
Measure
Check grid frequency
Check if the AC cables are securely connected.
Remark
Inverter automatically reconnects to the grid once the grid voltage recovers normal
Fault
Gnd-flt
Possible
reason
Inverter AC side leakage current to the ground exceeds the set value (default: 5A)
Measure
-
Remark
Inverter automatically reconnects to the grid once the leakage current recovers
Fault
Iac-high
Possible
reason
Internal short-circuit or internal components damages
Measure
Check the AC side cable connection and the control circuit board.
Remark
Contact Sungrow
Fault
Temp-flt
Possible
reason
Inverter internal temperature exceeds the permitted value
Measure
Check functionality of fan after the device is voltage-free
Remark
Stop the inverter if this fault occurs 10 times per day
Fault
PM-high
Possible
reason
Module temperature exceeds the permitted value
Measure
Check the module and ventilation after the device is voltage-free
Remark
Stop the inverter if this fault occurs 5 times per day
Fault
L over-temp
Possible
reason
Reactor temperature exceeds the permitted value
Measure
Check the reactor after the device is voltage-free
Remark
-
Fault
PDP-pro
Possible
reason
Internal fault
Measure
Wait 5 minutes for inverter auto-reconnection or disconnect first and then connect
the AC main switch
Contact Sungrow if the fault insists
Remark
Stop the inverter if this fault occurs 5 times per day
Fault
Cntr-flt
Possible
reason
Contactor connected to the gird failure
Measure
Check the contactor after the device is voltage-free
Remark
Stop the inverter if this fault occurs 5 times per day。
Inverter internal fan fault
Measure
Check the functionality of fan after the device is voltage-free
Remark
Contact Sungrow
Fault
DC SPD flt
Possible
reason
DC SPD tripping, over-voltage protection
Measure
Replace the SPD with the same model after the device is voltage-free
Remark
Contact Sungrow
Fault
AC SPD flt
Possible
reason
AC SPD tripping, over-voltage protection
Measure
Replace the SPD with the same model after the device is voltage-free
Remark
Contact Sungrow
Fault
Mism-ac
Possible
reason
Sensor is damaged
Measure
Replace the sensor with the same model after the device is voltage-free
Remark
Contact Sungrow
Fault
Island
Possible
reason
Islanding detected
Measure
Inverter enters into anti-islanding protection state automatically
Remark
Inverter automatically reconnects to the grid once the grid becomes normal
Fault
Ctrol power supply-flt
Possible
reason
CPS (Control power supply) inside the inverter cannot work normally
Measure
-
Remark
Inverter automatically reconnects to the grid once the CPS reverts to normal and the
grid-connection requirements are fulfilled
Fault
Ctrol cabt. Temp-flt
Possible
reason
Inverter control cabinet fans fault
Measure
Check and maintain the control cabinet fan when device is voltage-free
Remark
Contact Sungrow
10.4 LCD Display Alarm Information and Troubleshooting
During warn running state, inverter can operate normally and send warn signal. User can check
the warn information through the Work state on the default menu or through the
Function->History-information->His-alarm interface to check the latest 100 history alarm
information. Inverter will recover normal operation once the alarm is removed.
Grid voltage is below 0.9Un and the LVRT function is enabled
Measure
Warn will disappear automatically when grid voltage recover normal
Remark
-
Fault
CT-Unbalanced
Possible
reason
Current transformer (CT) on the inverter control cabinet is abnormal
Measure
Check and service the CT on the measuring board when inverter is voltage-free
Remark
-
Fault
RISO-low
Possible
reason
Inverter DC side insulation resistance is lower than the set value.
Measure
-
Remark
Only alarm display. Inverter can operate normally.
Fault
DC Sensor-err
Possible
reason
Inverter DC sensor abnormal
Measure
Check and service the DC sensor when inverter is voltage-free
Remark
-
10.5 Other Faults
Inverter Shuts Down Shortly After Start-Up
Possible reason: DC input voltage just reaches the inverter start-up voltage. Voltage will decrease
and inverter will stop when it is under load.
Solution: design the serial and parallel connection in accordance with the open circuit voltage;
increase the input DC voltage; avoid adopting the critical voltage.
Hear-Sink is Over-Temperature
Possible reason: cooling fan failure; over-temperature of the air inlet; bad ventilation of the
switch room, etc..
Solution: check and replace the cooling fan; reduce the temperature of the switch room; clean
the air duct and widen the air duct.
Noise is Too Loud during Inverter Operation
Possible reason: abnormal operation of the inverter and transformer; fan failure.
Solution: check if the power is within the permissible range; measure if the grid-connected
current and voltage waveform are normal (if not, the noise will be loud and the transformer will
be overheating); check and replace the fan.
LCD Display Cannot Start or Stop Inverter
Possible reason: communication malfunction between the LCD display and the DSP; LCD power
supply malfunction.
Solution: check the connection between the LCD display and the DSP.
Communication Failure with PC
Check if the address and the Baud rate of the LCD are the same with that of PC.
Check to ensure the circuits are properly connected and A/B is connected correctly.
Check if the converters are matched. Communicate again after replacing the converter.
The monitor disk is installed incorrectly. It is recommended to reinstall the disk.
If all the above-mentioned items are correct and this fault continues, please replace the PC
communication module on the LCD display.
The monitor disk might be incompatible with the antivirus software and thus cannot be
installed correctly. You are recommended to disable the antivirus software and then
install the monitor software.
11.1 Technical Data
11.1.1 Electrical Parameters
Input data (DC side)
Parameter
Specification
Max. DC Voltage
1000Vdc
Start-up voltage
500V
MPP Voltage Range
460V~850V
Min. DC Voltage
460V
Max. DC Power
560kW
Max. Input Current
1220A
Output data (AC side)
Parameter
Specification
Nominal Output Power
500kW
Max. Output Power
550kW
Max. AC Output Current
1008A
Nominal Grid Voltage
315Vac
Grid Voltage Range (3-phase)
252Vac~362Vac
Nominal Grid Frequency
50Hz/60Hz
Grid Frequency Range
47~52Hz/57~62Hz
Output Current THD
<3% at nominal power
DC current injection
<0.5% of nominal output current
Power factor
0.9(lagging) - 0.9(leading)
11.1.2 Mechanical Parameters
Parameter
Specification
Dimensions(W×H×D)
1205mmx1915mmx835mm
Weight
950kg
11.1.3 System Parameters
Parameter
Specification
Max. Efficiency
98.7%
European Efficiency
98.5%
Protection Degree
IP21
Power Consumption at Night
<20W
Operating Temperature
-30℃~+55℃ (without power derating at 55℃)
Cooling Method
Temperature-controlled forced air cooling
Relative humidity
0~95% (Non-condensing)
Max. Working Altitude
6000m (operation with derating above 3000m)
11.1.4 Display and Communication
Parameter
Specification
Display
LCD
Communication
RS485/Ethernet
11.2 Exclusion of Liability
The content of these documents is periodically checked and revised where necessary. Please call
us or check our website www.sungrowpower.com for the latest information. No guarantee is
made for the completeness of these documents. Please contact our company or distributors for
the latest version.
Guarantee or liability claims for damages of any kind are excluded if they are caused
Improper or inappropriate use or install of the product
Install or operate the product in unintended environment
Install or operate the product without observing relevant safety regulations in the
deployment location
Ignore the safety warnings or instructions contained in all documents relevant to the
product
Install or operate the product under incorrect safety or protection conditions
Alter the product or supplied software without authority
Product malfunctions due to operation attached or neighboring devices running out of the
allowed limit values
Unforeseen calamity or force majeure
The use of supplied software produced by Sungrow Power Supply Co., Ltd. is subject to the
following conditions:
Sungrow Power Supply Co., Ltd. assumes no liability for direct or indirect damages arising
from the use of SolarInfo software. This also applies to the provision or non-provision of
support activities.
SolarInfo software used for commercial purposes is prohibited.
Decompiling, decoding or destroying the original program, including SolarInfo software and
the embedded software, is prohibited.
11.3 About Us
Sungrow power supply is a Chinese leading manufacturer of various power electronics products
for renewable energy generation systems. Our products include converters, inverters, battery
chargers and other power supplies for distributable generation systems in both grid-connected
and stand-alone applications. The power rating of SUNGROW products covers a range from
several hundred watts to large mega-watt systems.
The pursuit of SUNGROW is to help our customers acquire stable and clean power with
minimum cost, maximum reliability and enhanced safety.
11.4 Contact Information
Should you have any questions or queries about this product, please contact us through the
following information. We will be more than happy to assist you!
Company:
Sungrow Power Supply Co., Ltd.
Website:
www.sungrowpower.com
Email:
[email protected]; [email protected].
Address:
No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, Hefei, P.
R. China.
Zip:
230088
Telephone:
+86 551 6532 7834, +86 551 6532 7845
Fax:
+86 551 6532 7856