Trox VSD15 Installation Manual
| Brand: | Trox |
| Category: | Fan |
| Model: | VSD15 (Installation Manual) |
| File Type: | |
| File Size: | — |
| Pages: | 12 |
Text of Trox VSD15 Installation Manual
Trox VSD15 Fig. 1: Schematic illustration of VSD35-1-AK-M-L/000
①
Diffuser face
②
Adjustable air control element
③
Neck
④
Plenum box
⑤
Suspension lug
⑥
Spigot
⑦
Lip seal
⑧
Damper blade for volume flow rate balancing
⑨
Clamp fixing
⑦ – ⑨: Optional equipment
This manual describes the following product types: - VSD15, VSD35, VSD50, VSD35-Varyset,
VSD50-1-LT, VSD35-3-AZ
Installation manual
GB/en
Air terminal devices
Slot diffusers
Trox VSD15 Information on the installation manual
This manual enables operating or service personnel
to correctly install the product described below and
to use it safely and efficiently.
It is essential that these individuals read and fully
understand this manual before starting any work.
The basic prerequisite for safe working is to comply
with the safety notes and all instructions in this
manual.
The local regulations for health and safety at work
The installation of air terminal devices in humid
rooms, areas with potentially explosive atmos-
pheres or rooms with dust-laden or aggressive air
has to be assessed for each individual case.
Transport and storage
Delivery check
Upon delivery, carefully remove the packaging and
check the unit for transport damage and complete-
ness. In case of any damage or an incomplete ship-
ment, contact the shipping company and your sup-
plier immediately. Put the prod
Trox VSD15 Industrial safety helmet
Protective gloves
Safety shoes
Installation notes:
Fix the device only to load-bearing structural
elements.
Load suspension systems only with the weight
of the device. Adjacent components and con-
necting ducts must be supported separately.
Use only approved and adequately sized fixing
material (fixing material is not
Trox VSD15 If possible, install the unit before fixing the ceiling
tiles; if this is not possible, remove the adjacent
ceiling tiles.
Use only approved and adequately sized suspen-
sion systems (fixing material is not included in the
supply package). Dimensions and weights are
given in the technical leaflets.
Only work in pairs; preferably use a lift.
Fig. 2: Plenum box
1.
Fix the suspension parts such as ropes,
cables or metal hangers (Fig. 2/1)
Installation in panelled ceilings
Fig. 5: Slot diffuser without extended border
End seal (for VSD15 only)
Fig. 6: Fitting an end seal
①
Intermediate seal
②
End seal (tubular)
Continuous linear runs require an end seal on
each end to ensure that no air leaks
End seals can be either factory fitted or fitted
by others
Single diffusers require end seals on both ends
End seals are suitable only for slot diffusers
without extended border
Inst
Slot diffusers with concealed screw fixing
The face of slot diffusers with concealed screw fixing (variant AS or DS) can be fixed to the plenum box
after the false ceiling has been completed.
Fig. 7: Diffuser face with concealed screw fixing
Installation
Air terminal devices Slot diffusers, Type VSD...
7
Trox VSD15 Installation into a wall opening
VSD50-1-LT
Installation in lightweight partition walls with
metal support structure
Preferably for rooms with a clear height up to
4.0 m
Wall installation below the ceiling
Horizontal duct connection
Installation together with drywalling
Fig. 8: Installation example
①
Ceiling
②
Suspended ceiling
③
VSD50-1-LT
④
Duct
Installation opening
Nominal
length
l [mm]
h [mm]
550
560
58
1175
1185
VSD35-3-AZ
The diffuser has a spigot to connect it to the
ducting. Variants with a double lip seal allow for a
sufficiently tight connection; additional sealing is not
required.
Commissioning, maintenance and cleaning
Initial commissioning
Before you start commissioning:
Check that the air terminal devices are cor-
rectly seated.
Remove protective films, if any.
Ensure that all air terminal devices are clean
and free from residues and forei
Setting the air discharge direction
These are only schematic diagrams to illustrate the setting of the air control elements.
Slot diffusers for ceiling installation
Airflow direction
Setting of the air control elements
Alternating horizontal
air discharge
Alternating air control elements (every second
element different)
One-way horizontal
air discharge to the
left
One-way horizontal
air discharge to the
right
Alternating angled air
discharge
Alternating ai
Slot diffusers for wall installation
Airflow direction
Setting of the air control elements
VSD50-1-LT
Angled one-way air discharge
VSD35-3-AZ
Angled one-way air discharge
and extract air
Maintenance and cleaning
Please note:
The cleaning intervals given in the VDI 6022
standard apply.
Clean surfaces with a damp cloth.
Use only common household cleaners, do not
use any aggressive cleaning agents.
Cleaning agents that contain chlorine must no
Trox Fan Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated |
|---|---|---|---|---|---|---|
TJN |
PDF Guide (@H313D8), Trox TJN Fan (05-10-2026) |
16 | 616 | 118 | 05-10-2026 | |
DRH Series |
PDF User Manual (@QB221I), Trox DRH Series Fan (28-04-2026) |
64 | 561 | 141 | 28-04-2026 | |
VFL |
#Z9AEIK: VFL Fan Manual |
12 | 1266 | 292 | 23-08-2026 | |
VSD15 |
VSD15 (Fan ePDF User Manual, #N5R2GW) |
12 | 573 | 144 | 22-06-2026 |