AC mains supply
Refer to the quick guide for safety
and proper installation instructions
The intended use of X Series amplifiers is in a rack only. The AC mains
wirings of the units must be connected to a terminal box provided with a
properly breaker. The proper device to use depends on mains configuration;
for X8 Powersoft suggests:
single-phase AC (P+N+E): 32 A rating, C or D curve, 10 kA;
three-phase AC (3P+N+E): 4 x 16 A rating, C or D curve, 10 kA.
Fo
Keep this guide for future reference
| ©2015 Powersoft
|
Three-phase electric power
f
f Five conductors: 3P+N+E
f
f Wye and Delta connections supported.
f
f Each single conductor must be secured to the PC 5/5-
STF1-7,62 flying plug as shown in the figure below.
DO000181.01 Rev. 5
This device must be powered exclusively by earth
connected mains sockets in electrical networks
compliant to the IEC 364 or similar rules.
Bi-phase electric power
f
f Three cond