Simplex 4007-9101 Installation Manual
Read Online
Read the Simplex 4007-9101 Installation Manual online using the built-in PDF viewer.
Text of the manual
Cautions, Warnings, and Regulatory Information.......................................................................................................3
2
Overview...........................................................................................................................................................................4
2.1
4007ES product list.............................................................................................................................................................................................. 4
2.2
Glossary.................................................................................................................................................................................................................5
3
Installation........................................................................................................................................................................6
3.1
Mounting the 4007ES panels..............................................................................................................................................................................6
3.2
Trim Kit.................................................................................................................................................................................................................. 7
3.2.1
Trim kit application................................................................................................................................................................................................................7
3.3
Wiring.....................................................................................................................................................................................................................8
3.3.1
Safety ground/ ferrite bead.................................................................................................................................................................................................9
3.3.2
AC supply wiring.....................................................................................................................................................................................................................9
3.3.3
Battery guidelines............................................................................................................................................................................................................... 10
3.4
Power...................................................................................................................................................................................................................10
4
NAC power supply.........................................................................................................................................................11
4.1
NAC power supply specifications.....................................................................................................................................................................12
4.2
NAC section overview........................................................................................................................................................................................12
4.3
Specifications......................................................................................................................................................................................................13
4.3.1
Wiring parameters.............................................................................................................................................................................................................. 13
4.3.2
Wiring distances.................................................................................................................................................................................................................. 14
4.3.3
Class A wiring....................................................................................................................................................................................................................... 14
4.3.4
Class B wiring....................................................................................................................................................................................................................... 15
4.4
Troubleshooting................................................................................................................................................................................................. 16
5
IDNAC power supply.....................................................................................................................................................17
5.1
Power supply specifications............................................................................................................................................................................. 18
5.2
IDNAC section overview.................................................................................................................................................................................... 18
5.3
Specifications......................................................................................................................................................................................................19
5.4
Wiring parameters.............................................................................................................................................................................................19
5.5
IDNAC Class B wiring tables............................................................................................................................................................................. 20
5.6
IDNAC Class B wiring......................................................................................................................................................................................... 21
5.7
Compatible devices and appliances................................................................................................................................................................ 22
5.8
Auxiliary relays section overview..................................................................................................................................................................... 25
5.9
Troubleshooting................................................................................................................................................................................................. 26
5.9.1
SLC channel trouble LED codes...................................................................................................................................................................................... 27
5.9.2
System trouble LED codes................................................................................................................................................................................................28
6
4007ES power supplies.................................................................................................................................................29
6.1
Power supplies specifications.......................................................................................................................................................................... 29
6.2
Wiring guidelines................................................................................................................................................................................................29
6.3
IDNet Section overview..................................................................................................................................................................................... 30
6.4
Device addressing, Class A and Class B.......................................................................................................................................................... 30
6.5
Wiring parameters.............................................................................................................................................................................................31
6.6
Class A Wiring.....................................................................................................................................................................................................32
6.7
Class B Wiring.....................................................................................................................................................................................................32
6.8
Auxiliary power selection..................................................................................................................................................................................33
6.9
RUI section..........................................................................................................................................................................................................34
6.10 Troubleshooting................................................................................................................................................................................................. 36
7
Optional modules and cards....................................................................................................................................... 37
7.1
Example of combinations................................................................................................................................................................................. 38
8
Appendix A ULC programming requirements........................................................................................................... 39
8.1
Common earth fault ground and common trouble indicator......................................................................................................................39
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Page 3
579-1102 Rev H
1 Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the
contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized
Simplex product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
EYE SAFETY HAZARD Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do
not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
SULFURIC ACID WARNING Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can destroy
fabric. Replace any leaking or damaged battery while wearing appropriate protective gear. If you come in contact with sulfuric acid,
immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
FCC RULES AND REGULATIONS – PART 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations,
or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper
system operation verified.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
2 Overview
The 4007ES fire alarm control panel provides audible and visible indication of alarms, troubles, and supervisory conditions. The 4007ES panels
supports addressable notification and initiating devices and the 4007ES Hybrid panels supports non-addressable notification devices and addressable
initiating devices*. The panel can be configured by using a panel programmer.
*From this point on, the 4007ES and the 4007ES hybrid is referred to as 4007ES, unless stated otherwise.
4007ES operator instructions are described in the 4007ES Operator’s Manual 579-1165.
4007ES programming instructions are described in the 4007ES Programmer’s manual 579-1167.
2.1 4007ES product list
Table 1: Product list
Part number
Base panels
4007-9101
4007ES Hybrid, red
4007-9201
4007ES, red
4007-9102
4007ES Hybrid, platinum
4007-9202
4007ES, platinum
Table 2: Product List and manual
Part number
Optional modules: field installed
Manual
4007-9801
Zone/Relay Module
579-1103
4007-9802
25V Regulator Module
579-812
4007-9803
IDNet+ Loop Expansion Module
579-1106
4007-9804
Dual Class A Module
579-1029
4007-9805
LED Module
579-1105
4007-9806
DACT Module
579-954
4007-9807
City Circuit with Disconnect Module
579-955
4007-9808
City Circuit without Disconnect Module
579-955
4007-9809
Relay Module
579-955
4007-9810
4120 NIC
579-956
4007-9812
Dual RS-232 Module
579-910
4007-9813
Wired Media Card
579-956
4007-9814
Fiber-Optic Media Card
579-956
4190-6106
TrueInsight Remote Service Gateway and Programming
579-953
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
2.2 Glossary
Table 3: Glossary
Term
Definition
Aux
Abbreviation for Auxiliary; typically used to describe Auxiliary Power.
EOL
End-of-Line, typically in reference to and end-of-line resistor or EOL
resistor.
FACP
Fire Alarm Control Panel.
Hybrid
In this document, “Hybrid” the 4007ES Hybrid models that provide both
addressable and conventional initiation with conventional non addressable Notification Appliance Circuits.
IDC
Initiating Device Circuit.
IDNet
Addressable SLC for up to 250 addressable devices.
IDNet+
IDNet which is electrically isolated from internal panel electronics.
IDNAC
Individual Device Notification Appliance Circuit (Addressable).
NAC
Notification Appliance Circuit, formerly called signal circuit.
NIC
Network Interface Card for the 4120 network.
Regulated 24 DC
Notification appliance operation that meets the minimum listing
requirements; inrush currents typically require power supply and NAC rating.
RS-232 module
The Dual RS-232 interface module provides a serial communication
interface to an AC or DC printer, a PC Annunciator, or a third party computer.
RUI
Remote Unit Interface; SLC for communications with remote
annunciators.
Simple NAC
A Reverse Polarity Supervised Notification Appliance Circuit that is
capable of on steady or coded operation. Sync or SmartSync operation is not supported.
SLC
Signaling Line Circuit
SmartSync
A reverse polarity monitored NAC capable of synchronizing and
controlling both horns and strobes on the same circuit using a proprietary signaling protocol. Used as the
protocol for TrueAlert Non-Addressable Devices.
User interface The user interface is a 4.3 in. (109mm) diagonal color LCD with a built-in resistive touch panel and 12 indicating LEDs. The color LCD
provides system status and access to perform system functions and to change the system configuration.
Figure 1: 4007ES panel inside view on page 5 shows an inside view of the 4007ES panel with the optional LED module (4007-9805) installed.
Fig 1: 4007ES panel inside view
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
3 Installation
Introduction
This chapter describes how to install the 4007ES panel. It can be semi-flush or surface mount.
3.1 Mounting the 4007ES panels
• Due to the danger of metal fragments falling into electronics when drilling the holes for the conduits, remove the electronics in the system:
- To remove the electronics, unscrew the ten screws. Remove the power supply and store it in a safe, clean, and dry location until the panel
installation is completed, see Figure 2: Screws location on page 6.
- If installing a 4007ES hybrid panel, also remove the Zone/Relay card (three screws).
• Use a suitable punch where a conduit entrance is required. The knockouts are not provided. Locate and create on-site as required during installation.
Fig 2: Screws location
• For surface or semi-flush mounting to a wooden wall structure, the panel must be attached with four 1 1/2 in. (38 mm) long lag bolts and four 1/2 in.
(13 mm) diameter washers, supplied by others.
• For surface mounting, secure the box to the wall using the tear-drop mounting holes on the back surface. For semi-flush mounting, secure the box
along the sides to the wall studs. Note that the front surface of the back box must protrude at least 1-1/2 in. (38mm) from the wall surface for semi-
flush installation. A trim kit is supplied for semi-flush mounting, see the Trim kit application on page 7 section for more information.
• To install the panel, see Figure 3: Back Box Installation dimensions and Semi-Flush Mounting (Right) on page 7 for the dimensions and use the
holes in the back box to secure it to the wall.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 3: Back Box Installation dimensions and Semi-Flush
Mounting (Right)
3.2 Trim Kit
3.2.1
Trim kit application
Trim kits are used to cosmetically cover wall openings when boxes are mounted semi-flush into the wall. The kit includes:
• Two top trim bands (shorter).
• Two side trim bands (longer).
• Four corner pieces.
Fig 4: Semi-flush trim kit
After mounting the box semi-flush to the wall, attach the trim per the following procedure:
1.
The strips need to be cut before being attached. Carefully cut them to length using a hacksaw or sharp utility knife. Cut the strips approximately
1in. (25 mm) shorter than the box dimension. The box is 20-7/8 in. (530 mm) wide and 20-3/16 in. (512 mm) high.
2.
Attach the strips one at the time. Peel off the adhesive tape release and center the strip on the box placing the edge of the strip against the box
surface, then press solidly to assure adhesion.
3.
Each corner piece overlaps the trim strip slightly less than 3/4 in. (19 mm). Align the corner pieces tight to the box corner and attach with a drywall
or similar screw, suitable for the wall material. The screws are not supplied.
Fig 5: Applying the trim
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
3.3 Wiring
Wiring guidelines
Follow these guidelines when connecting power-limited (PL) systems. For more information about these guidelines, contact your authorized Simplex
product supplier.
• Non-power limited (NPL) field wiring (AC power, batteries, City connection, DACT) must be installed and routed in the shaded areas shown in Figure 6:
Field wiring guidelines (NAC power supply shown as reference) on page 8
• You must maintain a minimum of 0.25 in. (6.35 mm) space between NPL and PL field wiring.
• The AC harness is pre-wired and tied to back of the box.
Fig 6: Field wiring guidelines (NAC power supply shown as reference)
• The conductors must test free of all grounds.
• A system ground must be provided for earth detection and lightning protection devices. This connection must comply with approved earth detection
per NFPA780.
• Splicing is permitted. All spliced connections must either be soldered (resin-core solder), crimped in metal sleeves, or encapsulated with an epoxy
resin. When soldering or crimped metal sleeves are used, the junction must be insulated with a high-grade electrical tape that is as sound as the
original insulating jacket. Shield continuity must be maintained throughout.
• Excess slack should be kept to a minimum inside the back box enclosure. The wiring should be neatly dressed and bundled together using wire ties.
• All wiring must use copper conductors only, unless noted otherwise.
• For IDNet, shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each end in the panel to prevent it coming
into contact with other components. The metallic continuity of the shield must be maintained and insulated throughout the entire length of the
cable.
• If shielded wire is used, the metallic continuity of the shield must be maintained throughout the entire cable length, and the entire length of the cable
must have a resistance greater than 1 megohm to earth ground. Underground wiring must be free of all water.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 7: EOL relay diagram
• In areas of high lightning activity, or in areas that have large power surges, use the 2081- 9027 or the 2081-9044 Transient Suppressor on monitor
points.
• Wires must not be run through elevator shafts.
• Only system wiring can be run together in the same conduit. When powering remote units using relay contacts, power for these circuits must be
provided by a PL power supply listed for fire-protective signaling use. An end-of-line (EOL) relay must be used to supervise the auxiliary power circuit.
• Connect the output of the EOL relay to cause a trouble. Wire in series with the EOL resistor on an available initiating device circuit (IDC) or individual
addressable module (IAM).
3.3.1
Safety ground/ ferrite bead
Correct operation and protection against transient energy in accordance with UL 864 and ULC-S527 require the connection of safety ground wire to
cabinet chassis. Connect the safety ground before wiring any other circuits to the panel. Ferrite beads must be attached to the incoming AC power line
as shown in Figure 8: Safety ground and ferrite bead on page 9. Wrap the line leg twice through a ferrite bead, and the neutral leg of the power
line twice through the other ferrite bead.
Fig 8: Safety ground and
ferrite bead
NOTE: The ferrite bead should be installed as close as possible to where power enters the panel.
3.3.2 AC supply wiring
Adhere to the following guidelines when wiring AC Power. See Safety ground/ ferrite bead on page 9 for information about attaching the ferrite
bead to the AC power wires.
• The AC power must be wired from a dedicated circuit breaker or fuse, rated no more than 20 A, in accordance with NFPA-72, NEC, and local codes.
• Before handling the AC feed, verify that it is not live using a voltmeter. Make sure the circuit is de-energized and tagged to prevent injury.
• The AC supply wiring must be 14 AWG minimum to 12 AWG maximum.
• Connect a 12 AWG copper ground wire from safety ground in the electrical distribution panel to the panel safety ground stud.
• Input voltage:
- 120 VAC, 50/60 Hz.
- 240 VAC, 50/60 Hz.
No configuration settings required to select.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
3.3.3 Battery guidelines
A fused harness is required to connect the backup batteries. Use harness 734-304 for a NAC power supply, and harness 734-303 for an IDNAC power
supply. The harness is shipped with the panel. The mating spade lug on the battery should be 0.250 in. X 0.032 in. (6.35 mm X 0.81 mm). If another size
is needed, you need to replace the battery terminal connectors on the supplied battery harness.
• The 4007ES battery charger supports up to 33 Ah batteries (maximum) within UL864 and ULCS527 guidelines.
- 18 Ah batteries can fit inside the box.
- 25 Ah and 33 Ah batteries use 2081-9282(red 25 Ah or 33 Ah) or 4009-9801 (beige 25 Ah).
• To minimize the power losses due to wiring from the external battery box to the 4007ES, use at least a 12 AWG wire. Mount the battery box within 20
feet (609.6 cm) of the panel in accordance with the mounting instruction label in the box. All interconnecting wiring must be enclosed in conduit.
• Seismic battery brackets can be used internally in the 4007ES box (the 2081-9401: 12.7 Ah bracket, and the 2081-9402: 18 Ah bracket). For more
information on how to install the seismic brackets, see the Battery Bracket installation instructions (579-944).
3.4 Power
Final installation To finalize the installation:
1.
Reinstall the power supply and the electronics.
2.
To install the batteries:
a. Place the first battery on the left side of the panel to avoid interference with the DACT, if installed.
NOTE: The battery terminals should face the front of the box.
b. Insert the second battery and make sure it is snugly positioned beside the first battery.
c. Wire the batteries in series such that you have 24 V. Use the white wire provided to bridge the batteries together, see Figure 9: Power supply on
page 10.
IMPORTANT: Verify all field wiring before applying any power to the panel.
Power up the system:
1.
Connect the negative lead to the battery.
2.
Apply AC.
3.
Connect the positive to the battery.
Fig 9: Power supply
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4 NAC power supply
A conventional reverse polarity NAC power supply is used in a 4007ES hybrid panel. It provides 6A and can support the following:
• Non-addressable notification devices.
• Addressable initiating devices.
See Figure 10: NAC power supply on page 11 and Table on page 11 for the main components of the NAC power supply.
Fig 10: NAC power supply
Table 4: Main components information
P1
RUI Class A/B jumpers
P2
IDNet Class A/B jumper
TB4
Battery connection
TB2
NAC 1 and NAC 2
P10
AC Power Connection
TB3
NAC 3 and NAC 4
J5 and J15
Zone / Relay
J7
IDNet Loop B
J16
CPU Connection
J8
IDNet Loop C
J17
Option Connection
P4
NAC Power Supply Card On-line
P11
City/Relay Connection
P6
Battery Depleted Jumper
P8
1-2 (default) / IDNet card on line
TB1
IDNet Loop 1, Aux Power, RUI
Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/ relay card. No jumpers.
Using 4007-9802, 25V Regulator Module.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.1 NAC power supply specifications
The NAC power supply can supply 6 A of 24 V power in addition to the base draw of the CPU/ Power Supply cards. The current draw taken from
optional cards, IDNet Devices, Aux Power, and NACs must be subtracted from 6 A.
IMPORTANT: See the 4007-9801 8-Point Zone/Relay Card Installation Instructions 579-1103, to determine the draw of the pre-installed Zone/Relay
card.
Table 5: 4007ES hybrid system current draw
Maximum AC input
2 A at 120 VAC, 50/60Hz
1 A at 240 VAC, 50/60Hz
Standby conditions
Current
(battery standby 24 V)
No alarms (NACs normal). No IDNet devices connected.
145 mA
Add to above for each additional IDNet device in standby.
0.8 mA
Total current for fully loaded IDNet channel in standby.
345 mA
Alarm conditions
Current
(battery alarm 24 V)
4 NACs ON: TBL Relay Activated: IDNet LED On. No IDNet devices connected.
190 mA
Add to above for each IDNet device in alarm.
1 mA
Add to above for each IDNet LED On (20 maximum IDNet devices LEDs On).
2 mA
Total current for fully loaded IDNet channel in alarm.
480 mA
4.2 NAC section overview
The NAC power supply allows connection to up to four Class A NAC circuits. Notification appliances within the 4007ES system are synchronized
including any attached 4009 series NAC extenders. Do not mix Wheelock and Simplex branded devices in the same system, they will not be
synchronized. The following TrueAlert non-addressable appliances are Special Application compatible with the NAC power supply:
• 4098-9772 Sensor Base with 520 Hz Sounder
• 4098-9773 CO Sensor Base with 520 Hz Sounder
• 4901-series Horn
• 4903-series A/V
• 4903-series S/V
• 4904-series VO
• 4906-Multicandela series
• 49CMT series Horn
• 49CMTV series A/V
• Wheelock Series: AS, HS, NS, ZNS, RSS, RSSP, STR, ZRS, MT, AMT, MTWP, ET, CH, E50, E60, E70, E80, E90, S8, SA
Fig 11: NAC terminal on NAC power supply
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.3 Specifications
Table 6: Specifications
Maximum appliances
70 per circuit.*
* Each 49CMT series appliance counts as 5 regular appliances for the maximum 70 appliances that can be supported per NAC. As the earth fault
sensitivity with thirteen MT appliances drops from 10 K to 9.6K ohms, no more than thirteen 49CMT series appliances may be placed on one circuit.
Electrical specifications:
Voltage
24 VDC nominal.
Alarm current
The maximum alarm current is 3 A per circuit.
Supervisory current
Refer to Table on page 13.
Special application appliances (TrueAlert Non-
Addressable)
6 A total.
NOTE:
When NACs are used for Regulated 24DC appliances, maximum current per NAC is reduced to 2 A and total power supply notification current rating
is reduced to 3 A. Current used by modules powered from the 4007ES power supply must be deducted from the total current.
4.3.1
Wiring parameters
The NAC power supply is supervised and power-limited. See Table on page 13 for the NACs’ supported EOL resistors and the related supervisory
current, and see Table on page 13 for the wiring parameters.
NOTE: If a shielded wire is used, cut it and tape it at both ends.
Table 7: Wiring parameters
Maximum wiring distance
Maximum cable load
10,000 ft (3,048 m) per channel
Maximum wire length from panel to any device
4,000 ft (762 m)
Maintain the correct polarity on terminal connections. Do not loop wires under terminals.
Table 8: Supported EOLR and supervisory current
EOLR
Current
3.9 k
5.7 mA
4.7 k
4.8 mA
5.1 k
4.4 mA
5.6 k
4.0 mA
10 k
2.2 mA
15 k
1.4 mA
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.3.2 Wiring distances
Table on page 14 lists the maximum distances from the NAC terminal block to the last appliance in a Class A configuration, depending on wire
gauge and current. Use Table on page 14 to calculate the wire distances for your application if you are using Class A wiring. Table on page 14
gives the values for a Class B configuration.
Table 9: Class A wiring distances
Alarm current
Max distance w/ 18
AWG(0.8231 mm2)
Max distance w/ 16
AWG(1.309 mm2)
Max distance w/ 14
AWG(2.081 mm2 )
Max distance w/ 12
AWG(3.309 mm2)
DC resistance
0.25 A
420 ft (128 m)
667 ft (203 m)
1,063 ft (324 m)
1,691 ft (515 m)
6 Ohms
0.50 A
210 ft (64 m)
334 ft (102 m)
532 ft (162 m)
845 ft (258 m)
3 Ohms
0.75 A
140 ft (43 m)
222 ft (68 m)
354 ft (108 m)
564 ft (172 m)
2 Ohms
1.00 A
105 ft (32m)
167 ft (51 m)
266 ft (81 m)
423 ft (129 m)
1.5 Ohms
1.25 A
84 ft (26 m)
133 ft (41 m)
213 ft (65 m)
338 ft (103 m)
1.2 Ohms
1.50 A
70 ft (21 m)
111 ft (34 m)
177 ft (54 m)
282 ft (86 m)
1 Ohm
1.75 A
60 ft (18 m)
95 ft (29 m)
152 ft (46 m)
242 ft (74 m)
0.86 Ohm
2.00 A
53 ft (16 m)
83 ft (25 m)
133 ft (41 m)
211 ft (64 m)
0.75 Ohm
2.25 A
47 ft (14 m)
74 ft (23 m)
118 ft (36 m)
188 ft (57 m)
0.67 Ohm
2.50 A
42 ft (13 m)
67 ft (20 m)
106 ft (32 m)
169 ft (51 m)
0.60 Ohm
2.75 A
38 ft (12 m)
61 ft (19 m)
97 ft (30 m)
154 ft (47 m)
0.55 Ohm
3.00 A
35 ft (11 m)
56 ft (17 m)
89 ft (27 m)
141 ft (43 m)
0.50 Ohm
Table 10: Class B wiring distances
Alarm current
Max distance w/ 18
AWG(0.8231 mm2)
Max distance w/ 16
AWG(1.309 mm2)
Max distance w/ 14
AWG(2.081 mm2)
Max distance w/ 12
AWG(3.309 mm2)
DC resistance
0.25 A
840 ft (256 m)
1,335 ft (407 m)
2,126 ft (648 m)
3,382 ft (1,031 m)
12 Ohms
0.50 A
420 ft (128 m)
667 ft (203 m)
1,063 ft (324 m)
1,691 ft (515 m)
6 Ohms
0.75 A
280 ft (85 m)
445 ft (136 m)
709 ft (216 m)
1,127 ft (344 m)
4 Ohms
1.00 A
210 ft (64 m)
334 ft (102 m)
532 ft (162 m)
845 ft (258 m)
3 Ohms
1.25 A
168 ft (51 m)
267 ft (81 m)
425 ft (130 m)
676 ft (206 m)
2.4 Ohms
1.50 A
140 ft (43 m)
222 ft (68 m)
354 ft (108 m)
564 ft (172 m)
2 Ohms
1.75 A
120 ft (37 m)
191 ft (58 m)
304 ft (93 m)
483 ft (147 m)
1.71 Ohms
2.00 A
105 ft (32 m)
167 ft (51 m)
266 ft (81 m)
423 ft (129 m)
1.5 Ohms
2.25 A
93 ft (28 m)
148 ft (45 m)
236 ft (72 m)
376 ft (115 m)
1.33 Ohms
2.50 A
84 ft (26 m)
133 ft (41 m)
213 ft (65 m)
338 ft (103 m)
1.2 Ohms
2.75 A
76 ft (23 m)
121 ft (37 m)
193 ft (59 m)
307 ft (94 m)
1.09 Ohms
3.00 A
70 ft (21 m)
111 ft (34 m)
177 ft (54 m)
282 ft (86 m)
1 Ohm
NOTE:
• Max distance = distance from the power supply to last appliance.
• This table is calculated at 49°C (120°F). If you are installing in locations that could be exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
• If circuit integrity wire is used instead of housing cable in a fire rated enclosure, reduce the wiring distances by 38 ft (12 m) for every 10 ft (3 m) of
potential exposure.
4.3.3 Class A wiring
NOTE: The Class A wiring style is set up in the ES Panel Programmer. See the 4007ES Programmer’s Manual (579-1167), for more information.
To connect the power supply to reverse-polarity, non-addressable notification appliances using Class A wiring, complete the following steps:
1.
Route wire from the B+ and B- outputs of the power supply to the appropriate inputs on a peripheral notification appliance. Use NAC1, NAC2,
NAC3, or Figure 12: Class A NAC wiring on page 15.
2.
Route the wire from the first appliance to the next. Repeat this for each appliance.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 12: Class A NAC wiring
3.
Route the wire from the last appliance to the A+ and A- inputs on the same NAC circuit of the power supply.
4.
Repeat steps 1 through 3 for each NAC output you want to use.
5.
Leave the 10 KOhms, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. No external end-of-line resistor is needed for circuits in
use.
4.3.4 Class B wiring
NOTE: The Class B wiring style is set up in the ES Panel Programmer. See the 4007ES Programmer’s Manual (579-1167), for more information.
To connect the power supply to appliances using Class B wiring, complete the following steps:
1.
Route the wire from the B+, B- outputs on TB2 and TB3 of the power supply to the appropriate inputs on a peripheral notification appliance. Use
NAC1, NAC2, NAC3, or NAC4.
Fig 13: Class B NAC wiring
2.
Route the wire from the first appliance to the next. T-tapping is not permitted. Repeat this for each appliance.
3.
Route the wire from the last appliance to the EOLR harness (10KOhms, 1/2 W: P/N 733- 894).
4.
Repeat steps 1 through 3 for each NAC output you want to use.
5.
Leave the factory installed EOL resistor (10 KOhms*, 1/2 W; brown/black/orange) on each unused circuit. The circuit must connect B+ to B-
terminals.
6.
Document the EOL value in the panel for each circuit.
*If using a 4007ES hybrid panel, keep the original value and set the ES Panel Programmer accordingly.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.4 Troubleshooting
Figure 14: LEDs on the 4007ES hybrid power supply on page 16 and Table on page 16 show the LED definition for the NAC power.
Fig 14: LEDs on the 4007ES hybrid power supply
Table 11: LEDs on the 4007ES hybrid power supply
LED10
AC
Green. Off on AC failure.
LED2
RUI Trouble
Yellow. On for Class A RUI trouble.
LED6
RUI OC
Yellow. Indicates a short (overcurrent).
LED3
Comm
Yellow. Indicates that the communication between the NAC power supply and the CPU is lost.
LED 4
Gen Power
Steady On, yellow. Indicates AC power loss, earth fault, overcurrent and battery trouble.
LED5, 7, 8,
and 9
NAC 1, 2, 3,
4
Steady On, yellow. Used to signal overcurrent, short, and open circuit.
LED1
Aux/SNAC
Steady On, yellow. Use to signal overcurrent, short, and open circuit.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5 IDNAC power supply
An IDNAC power supply is used in the 4007ES panel, the non-hybrid panel. It provides 4 A and can support the following:
• Addressable notification devices.
• Addressable initiating devices.
See Figure 15: IDNAC power supply on page 17 and Table on page 17 for the main components of the IDNAC power supply.
Fig 15: IDNAC power supply
Table 12: Main components information
P1
RUI Class A/B jumpers
P2
IDNet Class A/B jumper
TB4
Battery connection
TB2
IDNAC
P10
AC Power Connection
TB3
Aux Relay 1 and 2
J15
DCAI
Zone/Relay Connection
J10
IDNet Loop 2
J7
Zone/Relay
J11
IDNet Loop 3
J16
CPU Connection
P5
Battery Depleted Jumper
J17
Option Connection
P8
1-2 (default) / IDNet card on line
P11
City Circuit Connection
TB1
IDNet Loop 1, Aux Power, RUI Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/relay card. No jumpers.
Using 4007-9802, 25V Regulator Module
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.1 Power supply specifications
The IDNAC Power Supply can supply 4A of 24V power in addition to the base draw of the CPU/power supply cards. The current draw taken from
optional cards, IDNet Devices, Aux Power, and NACs must be subtracted from 4A.
Table 13: 4007ES system current draw
Maximum AC input
2 A at 120 VAC, 50/60 Hz
1 A at 240 VAC, 50/60 Hz
Standby conditions (see Note 1)
Current (see Note 1) (Battery Standby 24 V)
No alarms (NACs normal). No IDNet devices connected
180 mA
Add to above for each additional IDNet or IDNAC device in standby
0.8 mA
Total current for fully loaded IDNet or IDNAC channel in standby
431 mA
Alarm conditions (see Note 1)
Current (see Note 1) (Battery Alarm 24 V)
IDNAC ON: No IDNet LED On. No IDNet devices connected
185 mA
Add to above for each IDNet device in alarm (see note 2)
1 mA
Add to above for each IDNet LED On (20 maximum IDNet devices LEDs On)
2 mA
Total current for fully loaded IDNet channel in alarm (20 LEDs On) (see note 2)
475 mA
NOTE:
1.
Add an additional 9 mA per active auxiliary relay (Alarm or Standby).
2.
The IDNAC Alarm current depends on the IDNAC device used. See the relevant device manual for more information on currents.
5.2 IDNAC section overview
The IDNAC power supply has a single SLC for connecting addressable IDNAC devices. The power supply is compatible with TrueAlertES and TrueAlert
Addressable product lines, both multi and fixed candela. The IDNAC output is Class B only. Class A operation requires use of the optional module
4007-9804, IDNAC dual Class A isolator.
The output is duplicated on the terminal block to facilitate T-tapping on the circuit at the panel. EOL resistors are not required.
All wiring is supervised and power-limited.
+ -
IDNAC
+ -
Fig 16: IDNAC terminal
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.3 Specifications
Table 14: IDNAC specifications
Supports
• Up to 12 4905-9929 remote TrueAlert Addressable Isolators per IDNAC Circuit.
• Up to 30 devices connected directly to any isolator terminal pair*.
• Up to six isolators between any appliance and the IDNAC SLC terminals. All wiring is 20 AWG to 12 AWG. *For
more information on the isolator, refer to the 4905 Isolator+ Installation Instructions, 574-769.
Electrical specifications:
Channel voltage
29.5 VDC nominal.
Circuit requirements
The maximum alarm current is 3 A per circuits.
Isolator
Isolator (DCAI)
To wire an IDNAC as a Class A circuit, the DCAI modules (4007-9804) is required (2 Class A circuits with fault
isolation). For more information about Dual Class A isolators and on how to calculate Class B wiring with
isolation, see the DCAI Installation Instructions (579-1029).
5.4 Wiring parameters
Table on page 19 identifies the wiring parameters for the IDNAC.
Table 15: IDNAC Wiring parameters
IDNAC wiring limits
Channel loading
127 devices (IDNAC devices or other compatible devices). See
Compatible devices and appliances on page 22 for more information.
Max. wiring distance
Max. cable load
10,000 ft (3,048m) per channel.
Max. wire length from panel to any
device
4,000ft (762m).
NOTE: If a shielded wire is used, cut it and tape it. The required wiring is unshielded twisted pair (UTP). This wiring must have a capacitive
rating of less than 60pF/ft and a minimum of 3 twists (turns) per foot.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.5 IDNAC Class B wiring tables
Use the following tables to calculate the wiring distance to farthest appliance. The maximum wiring distance is the shorter of the distance limits as
calculated by alarm current voltage drop or by reaching the communications distance limit.
Wiring Limit Based on Alarm Current
Alarm
Current
Line
Distance to the Last Appliance
(Ohms)
Devices
Impedance
20
AWG
18
Distance to the Last Appliance
AWG
16
AWG
14
AWG
12
AWG
20
AWG
18
16
AWG
AWG
14
AWG
12
AWG
0.050
4000 ft
4000 ft
4000 ft
4000 ft
4000 ft
14.54
1
1252 ft
2038 ft
3241 ft
4000 ft
4000 ft
0.100
2644 ft
4000 ft
4000 ft
4000 ft
4000 ft
12.96
5
1142 ft
1815 ft
2887 ft
4000 ft
4000 ft
0.150
1763 ft
2802 ft
4000 ft
4000 ft
4000 ft
11.38
10
1003 ft
1595 ft
2536 ft
4000 ft
4000 ft
0.200
1322 ft
2102 ft
3342
4000 ft
4000 ft
10.14
15
893 ft
1420 ft
2258 ft
3590 ft
4000 ft
0.250
1058 ft
1681 ft
2674 ft
4000 ft
4000 ft
9.12
20
804 ft
1278 ft
2033 ft
3231ft
4000 ft
0.300
881 ft
2228 ft
1401 ft
3542 ft
4000 ft
8.28
25
730 ft
1160 ft
1845 ft
2934 ft
4000 ft
0.350
755 ft
1201 ft
1910 ft
3036 ft
4000 ft
7.58
30
668 ft
1061 ft
1688 ft
2683 ft
4000 ft
0.400
661 ft
1051 ft
1671 ft
2657 ft
6.97
4000 ft
35
614 ft
977 ft
1553 ft
2469 ft
3928 ft
0.450
588 ft
934 ft
1485 ft
2362 ft
3756
6.45
40
568 ft
904 ft
1437 ft
2285 ft
3634 ft
0.500
529 ft
1337 ft
841 ft
2125 ft
3380
6.00
45
528 ft
840 ft
1336 ft
3378 ft
2124 ft
0.750
353 ft
891 ft
560 ft
1417 ft
5.60
50
2254 ft
493 ft
784 ft
1247 ft
1982 ft
3152 ft
1.000
264 ft
420 ft
668 ft
1063 ft
5.24
55
1690 ft
462 ft
734 ft
1168 ft
1856 ft
2952 ft
1.250
212 ft
336 ft
535 ft
850 ft
4.92
60
1352 ft
434 ft
690 ft
1097 ft
1744 ft
2774 ft
1.500
176 ft
446 ft
280 ft
708 ft
4.75
63
1127 ft
419 ft
665 ft
1058 ft
1682 ft
2675 ft
1.750
151 ft
382 ft
240 ft
607 ft
4.64
65
966 ft
409 ft
650 ft
1034 ft
1643 ft
2613 ft
2.000
132 ft
334 ft
210 ft
531 ft
845 ft
4.38
70
386 ft
614 ft
976 ft
1552 ft
2468 ft
2.250
118 ft
187 ft
297 ft
472 ft
4.15
75
751 ft
366 ft
581 ft
924 ft
1469 ft
2337 ft
2.500
106 ft
168 ft
267 ft
425 ft
3.94
80
676 ft
347 ft
551 ft
877 ft
1394 ft
2217 ft
2.750
96 ft
153 ft
243 ft
386 ft
3.74
85
615 ft
330 ft
524 ft
833 ft
1325 ft
2107 ft
3.000
88 ft
140 ft
223 ft
354 ft
3.56
90
563 ft
314 ft
499 ft
794 ft
1262 ft
2006 ft
3.40
95
Wiring distance must not exceed 4000 ft
299 ft
476 ft
757 ft
1203 ft
1913 ft
3.24
100
286 ft
454 ft
723 ft
1149 ft
1827 ft
3.10
105
273 ft
435 ft
691 ft
Ohms per 1000
ft
1099 ft
Gage
1748 ft
2.97
Ohms/1000 ft
110
262 ft
416 ft
662 ft
1052 ft
1673 ft
2.85
20 AWG
11.347
115
251 ft
399 ft
634 ft
1009 ft
1604 ft
7.137
18 AWG
2.73
120
241 ft
383 ft
609 ft
968 ft
1539 ft
16 AWG
4.488
2.58
127
228 ft
362 ft
576 ft
915 ft
1456 ft
14 AWG
2.8230
Wiring distance must not exceed 4000 ft
12 AWG
1.7750
Wiring Limit Based on Communication
Fig 17: Class B wiring tables
NOTE: Although the required wiring for IDNAC circuits is twisted pair (controlled impedance) wiring, some applications will wish to take
advantage of existing wiring that is not twisted pair. This is only allowed if both conductors of the IDNAC circuit reside in the same metal conduit,
and only under certain conditions. Check with your local sales office before using wiring that is not twisted pair.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.6 IDNAC Class B wiring
To connect the power supply to appliances using Class B wiring:
1.
Route the wire from the + and the - outputs on the IDNAC terminal block (TB2) to the appropriate inputs on a peripheral notification appliance.
2.
Route the wire from the first appliance to the next. T- tapping is permitted. Repeat this for each appliance.
3.
Repeat steps 1 and 2 for each IDNAC output you want to use.
Fig 18: Class B wiring
NOTE:
1.
Notification appliances are rated using an individual nameplate label. Maintain the correct polarity on terminal connections.
2.
Each IDNAC + and - terminal is rated for 2 identical wires. This allows up to 4 Class B T-TAP circuits directly from each IDNAC terminal block, see
IDNAC Class B wiring on page 21.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.7 Compatible devices and appliances
The devices and appliances listed in Table on page 22 are compatible with the IDNAC power supply. Notification devices are synchronized within the
4007ES system, including any attached 4009 series NAC extenders.
Table 16: Compatible devices and appliances
Addressable device description
Model numbers
4009 IDNAC Repeater
4009-9601 (platinum)
4009-9602 (red)
Dual Class A Isolator (DCAI)
4007-9804
TrueAlert Addressable Isolator+ module
4905-9929
Table 17: Compatible devices and appliances
Addressable device appliance
description
TrueAlert ES appliance model numbers
TrueAlert appliance model
numbers
Audible only (AO) horn notification
appliances
49AO-WRF
49AO-WRF-BA
49AO-WRS-BA
49AO-WRS
49AO-WRQ
49AO-WWF
49AO-WWF-BA
49AO-WWS-BA
49AO-APPLC
49AO-APPLC-BA
49AO-APPLW
49AO-APPLW-BA
49MT-WRF1
49MT-WRF-BA1
49MT-WRS-BA1
49MT-WWS-BA1
49MT-WWF-BA1
49MT-APPLW1
49MT-APPLW-BA1
4901-9850
4901-9853
Audible/visible (A/V) notification
appliances
49AV-WRF
49AV-WWF
49AV-WRF-BA
49AV-WRQ-BA
49AV-WRS-BA
49AV-APPLC
49AV-APPLC-BA
49AVH-APPLC
49AVH-APPLC-BA
49AVH-APPLCA
49AVH-APPLCA-BA
49AVH-APPLCB
49AVH-APPLCB-BA
49AV-WWF-BA
49AV-WWS-BA
49AV-WRS
49AV-APPLW-BA
49AV-APPLW
49AV-WRQ
49MTV-WWS-BA2
49MTV-WRF2
49MTV-WRF-BA2
49MTV-WRS-BA2
49MTV-WWF2
49MTV-WWF-BA2
49MTV-APPLW2
49MTV-APPLW-BA2
4906-9227
4906-9229
4906-9228
4906-9230
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Table 17: Compatible devices and appliances
Addressable device appliance
description
TrueAlert ES appliance model numbers
TrueAlert appliance model
numbers
Visible only (VO) notification
appliances
49VO-WRF
49VO-WWF
49VO-WRA-A
49VO-WRA-A-BA
49VO-WWA-A
49VO-WRA-BA
49VO-WRF-BA
49VO-WRQ-BA
49VO-APPLC
49VO-APPLC-BA
49VOH-APPLC
49VOH-APPLC-BA
49VOH-APPLCA
49VOH-APPLCA-BA
49VOH-APPLCB
49VOH-APPLCB-BA
49VO-WRS-BA
49VO-WWS-BA
49VO-WWF-BA
49VO-WWA-BA
49VO-WWA-A-BA
49VO-WWS-A-BA
49VO-WRS
49VO-WWS
49VO-WWA
49VO-WWQ
49VO-WRA
49VO-WRQ
49VO-APPLW
49VO-APPLW-BA
49VO-APPLWE
49VO-APPLWE-BA
4906-9201
4906-9203
4906-9202
4906-9204
Speaker/visible (S/V) notification
appliances (visible/strobe)
4906-9251
4906-9253
4906-9254
Audible/visible (A/V) weatherproof
notification appliances
49AV-WRFO
49AV-WRFO-BA
49AV-WWFO-BA
49AV-APPLW-CO
49AV-WRQO-C
49AV-WRFO-C
49AV-APPLW-O
49AV-APPLW-O-BA
N/A
Visible only (VO) weatherproof
notification appliances
49VO-WRFO
49VO-WRFO-BA
49VO-WRSO-BA
49VO-WWFO-BA
49VO-APPLW-CO
49VO-WRFO-C
49VO-WRQO-C
49VO-WRSO
49VO-APPLW-O
49VO-APPLW-O-BA
N/A
TrueAlert adapter
N/A
4905-9816
LED visible only (VO) wall mount
59VO-WRF
59VO-WRF-BA
59VO-WWF
59VO-WWF-BA
59VO-WRFAB
59VO-WRFAB-BA
59VO-WWFAB
59VO-WWFAB-BA
59VO-APPLWR
59VO-APPLWW
LED visible only (VO) high candela
wall mount
59VO-WRFH-BA
59VO-WWFH-BA
59VO-WRFABH-BA
59VO-WWFABH-BA
59VO-APPLWRH
59VO-APPLWWH
LED visible only (VO) wall mount
weatherproof
59VO-WRFO
59VO-WRFO-BA
59VO-WWFO-BA
59VO-WRFABO
59VO-WRFABO-BA
59VO-WWWFABO-BA
59VO-APPLWR-O
59VO-APPLWW-O
LED visible only (VO) high candela
wall mount weatherproof
59VO-APPLWRH-O
59VO-APPLWWH-O
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Table 17: Compatible devices and appliances
Addressable device appliance
description
TrueAlert ES appliance model numbers
TrueAlert appliance model
numbers
LED audible/visible (A/V) wall mount
59AV-WRF
59AV-WRF-BA
59AV-WWF
59AV-WWF-BA
59AV-WRFAB
59AV-WRFAB-BA
59AV-WWFAB
59AV-WWFAB-BA
59AV-APPLWR
59AV-APPLWW
LED audible/visible (A/V) wall mount
high candela
59AV-WRFH
59AV-WRFH-BA
59AV-WWFH-BA
59AV-WRFABH
59AV-WRFABH-BA
59AV-WWFABH-BA
59AV-APPLWRH
59AV-APPLWWH
LED audible/visible (A/V) wall mount
weatherproof
59AV-WRFO
59AV-WRFO-BA
59AV-WWFO-BA
59AV-WRFABO
59AV-WRFABO-BA
59AV-WWFABO-BA
59AV-APPLWR-O
59AV-APPLWW-O
59AV-APPLWR-O
59AV-APPLWW-O
59AV-APPLWRH-O
59AV-APPLWWH-O
Audible only (AO) wall mount
59AO-WRS
59AO-WRS-BA
59AO-WWS
59AO-WWS-BA
59AO-APPLWR
59AO-APPLWW
Audible only (AO) wall mount
weatherproof
59AO-WRSO
59AO-WRSO-BA
59AO-WWSO-BA
59AO-APPLWR-O
59AO-APPLWW-O
Plate
59AP-EUROBB
Notes:
1. Maximum thirty-two (32) 49MT appliances per circuit.
2. Maximum twenty-one (21) 49MTV appliances per circuit.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.8 Auxiliary relays section overview
Table 18: Electrical specifications for Auxiliary relays
Electrical specifications:
Relay circuit rated to switch:
2 A at 30 VAC or 30 VDC, resistive load.
Contacts:
Relay contacts are Form C dry contacts. Transorbs provide suppression to earth. Do not switch voltages
greater than rating, or damage may result.
Table 19: Power specifications for auxiliary relays
Power
When power through auxiliary contacts is provided by the power supply, the wiring is power-limited.
When power through auxiliary contacts is not provided by the power supply, use in-line fuse holder 208-165 with 208-183, 1A fuse with attached cap
(supplied separately). If the power source is not power-limited to the requirements of UL864, wiring is to be segregated to the non-power-limited
spaces of the cabinet.
Note:
The Aux relay terminals on the IDNAC power supply are controlled by two on-board
programmable relays. The relay circuits are not supervised.
Fig 19: Aux relay terminals
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.9 Troubleshooting
The code produced by the illuminated yellow indicator LEDs corresponds to a trouble that is either occurring on the system, or on the SLC channels.
See Table on page 26 for the 4007ES LED definitions, and see Figure 21: SLC channel trouble LED codes on page 27 for the 4007ES LEDs and
their codes.
IDNAC channel troubles are indicated by yellow LEDs labeled IDNAC TBL and letters A to D. When the IDNAC TBL LED illuminates, the IDNAC channel
is experiencing a trouble. Refer to Figure 22: System trouble LED codes on page 28 or the trouble codes for LEDs A to D. The LED SCROLL
pushbutton can be used to scroll through multiple trouble indicators.
Table 20: 4007ES indicator LEDs
LED: A, B, C, D
Signal various trouble conditions on the 4007ES and its SLC. Refer to Figure 21: SLC channel
trouble LED codes on page 27 and
Figure 22: System trouble LED codes on page 28 for troubles details.
IDNAC TBL
When On steady, refer to Figure 21: SLC channel trouble LED codes on page 27 for
detailed troubles indicated by LEDs A-D.
LED COMM Loss
Indicates that the communication between the IDNAC power supply and the CPU is lost.
Scroll Push Button (SW1)
Used to scroll through multiple troubles, since only one trouble can be displayed at a time.
Fig 20: LEDs on the 4007ES power supply
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.9.1 SLC channel trouble LED codes
SLC channel troubles are indicated by LEDs A to D, as well as IDNAC. See Figure 21: SLC channel trouble LED codes on page 27 for the description
of the LEDs.
Fig 21: SLC channel trouble LED codes
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.9.2 System trouble LED codes
System troubles are indicated by LEDs A to D.
Fig 22: System trouble LED codes
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6 4007ES power supplies
This chapter describes the common sections of both the 4007ES Hybrid NAC power supply and the 4007ES IDNAC power supply.
6.1 Power supplies specifications
Table 21: Operating conditions
Operating conditions:
Operating temperature range
32 °F - 120 °F (0 °C - 49 °C).
Operating humidity range
Up to 93% relative humidity at 90 °F (32 °C), non-condensing.
6.2 Wiring guidelines
Class A: Using Class A wiring allows devices to communicate with the FACP even in the event of a single open circuit somewhere on the loop. Class A
wiring requires that two wires are routed from the power supply to each device, and then back to the power supply.
Class B: T-tapping is permitted on Class B wiring. Class B wiring therefore requires less cable distance per installation than Class A.
Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to connect a circuit
using PL wiring, the devices being powered must all be addressable, or a UL Listed EOL relay must be used to supervise the circuit.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.3 IDNet Section overview
The power supply provides an isolated IDNet channel. This section is compatible with IDNet communicating initiating devices and enables the system
CPU to communicate with up to 250 peripheral devices, such as smoke detectors and pull stations.
Fig 23: IDNET on the power
supply
Specifications
Table 22: IDNet specifications
Supports:
Up to 250 addressable IDNet devices and up to 43 coded piezo sounders may be coded by the IDNet
channel. Base panel supports 100 points, with 75 additional points per additional IDNet+ Loop Expansion
Module (refer to manual 579-1106).
Electrical specifications:
Channel voltage
to remote devices
30 VDC (normal); 35 VDC Alarm.
Data rate is 3333 bps.
Output circuits are supervised and power-limited.
Earth detection threshold:
10k ohms minimum from either positive or negative terminals.
Circuit requirements:
Refer to Table on page 12 for the IDNet current on a NAC power supply. Refer to Table on page 18
for the IDNet current on a IDNAC power supply.
LEDS:
For detailed information on LEDs troubleshooting, refer to Figure 21: SLC channel trouble LED codes on page 27Figure 22: System trouble LED
codes on page 28 in the Troubleshooting section.
6.4 Device addressing, Class A and Class B
The IDNet section can be wired as a Class A circuit or a Class B circuit.
Class A wiring: Class A wiring provides an alternate communication path that maintains communication to all devices when a single open circuit fault
occurs. Class A wiring requires two wires to be routed from the IDNet Primary Terminals (B+, B-) to each device, and then back to the IDNet Secondary
Terminals (A+, A-). Wiring is in/out, and T-tapping is not permitted.
Class B wiring: T-tapping is permitted on Class B wiring. IDNet wiring is inherently supervised due to individual device level communications. EOL
resistors are not required.
• If there are no remote isolators or isolator bases on the loops, device addressing can be assigned without concern for sequence.
• If there are remote isolators or isolator bases on the loops, the required addressing approach is to start from the B side and assign each
successive isolator a higher address than the isolator it precedes.
• For Class B wiring only, the A output and B output on a loop are connected in parallel using a jumper.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.5 Wiring parameters
Table on page 31 identifies the IDNet wiring parameters that you must consider when installing this card. For additional wiring information, see
Simplex Addressable Fire Alarm Panels Field Wiring Specifications (900-408).
Table 23: IDNet wiring parameters
IDNet wiring capacitance parameters
Parameter
Value
Maximum supported channel capacitance
The sum of line-to-line capacitance, plus the capacitance of either line-to-
shield (if shield is present) = 0.6 µF
IDNet wiring Class A and Class B limits
Channel loading
Up to 125 devices
126 to 250 devices
Max. resistance to compatible devices. (Include the
2081-9044 Overvoltage Protector resistance when
applicable)
50 ohms maximum
35 ohms maximum
Maximum wiring distance*:
(18 AWG, 16 AWG, 14 AWG, 12 AWG)
4000 ft (1219 m)
2500 ft (762 m)
NOTE:
• The maximum wiring distance is the maximum distance from both the IDNet control terminals (primary and return) to the farthest device on the
circuit. See Figure 24: Maximum wiring distance on page 31.
• The maximum wiring distance is determined by either reaching the maximum resistance, the maximum capacitance, or the stated maximum
distance, whichever occurs first.
• The total circuit cable load (amount of cable used) must not exceed 12,500ft (3,8km).
• Twisted wiring is recommended for improved noise immunity.
Fig 24: Maximum wiring distance
Table 24: IDNet wiring considerations
External wiring must be shielded (for lightning suppression) and 2081-9044 Overvoltage Protectors must be
installed at building exit and entrance locations.
For more information, refer to the Model 2081-9044 Overvoltage Protector Installation Instructions
(S4906-0016).
Capacitance; each protector adds 0.006 µF across the connected line.
Resistance; each protector adds 3 ohms per line of series resistance; both IDNet wires are protected; 6 ohms
per protector will be added to the total loop resistance.
The maximum distance of a single protected wiring run is 3270 ft (1 km).
IDNet wiring considerations using
2081-9044 Overvoltage Protectors
(2081-9044 is UL listed to Standard
1459, Standard for Telephone
Equipment)
See the 2081-9044 Overvoltage Protector Installation Instructions (574-832), for additional information.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.6 Class A Wiring
To wire an IDNet section as a Class A circuit:
1.
Make sure the jumpers on P2 are set to positions 3-5 and 4-6.
2.
Route the wiring from the IDNet circuit primary terminals (B+, B-) on TB1 of the IDNet to the corresponding inputs on the first device.
3.
Route the wiring from the first device to the next as in/out. See Figure 25: IDNet Class A wiring on page 32. Repeat this for each device.
4.
Route the wiring from the last device to the terminals A+, A- to the panel, maintaining polarity.
5.
Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each end in the panel to prevent it from coming into
contact with other components. The metallic continuity of the shield must be maintained and insulated throughout the entire length of the cable.
Fig 25: IDNet Class A wiring
6.7 Class B Wiring
When wiring the circuit as Class B, both the B+, B- and A+, A- terminals are available for parallel connections. Within the IDNet circuitry, A+ is connected
to B+, and A- is connected to B- so circuits can stem from either one. Additionally, two wires can be connected to each screw terminal.
To wire an IDNet as a Class B circuit, complete the following steps:
1.
Set the jumpers on P2 to positions 1-3 and 2-4.
2.
Route the wiring from the IDNet circuit primary terminals (B+, B-) to the corresponding inputs on the first device. It is possible to add up to 4
circuits on the terminal block when using Class B wiring. See Figure 26: IDNet Class B wiring on page 32 for the diagram.
3.
Route the wiring from the first device to the next as in/out, see Figure 26: IDNet Class B wiring on page 32. Repeat this for each device.
4.
Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each end (in the panel and at the last device in each
run) in the panel to prevent it coming into contact with other components. The metallic continuity of the shield must be maintained and insulated
throughout the entire length of the cable.
Fig 26: IDNet Class B wiring
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.8 Auxiliary power selection
AUX PWR/SNAC overview
The AUX PWR/SNAC terminal block is located on the top left corner of the power supply. Using the ES Panel Programmer, this point can be configured
as either a 24V Auxiliary (AUX) power or as a simple reverse polarity Notification Appliance Circuit (NAC). This circuit does not support TrueAlert
addressable devices nor non-addressable SmartSync appliances.
The AUX PWR/SNAC is rated 2 A maximum. The current used is deducted from the total available power supply current.
Fig 27: AUX/SNAC
terminal
Output rating:
29.5 V maximum
Current Rating:
2 A, maximum.
Earth Detection
Threshold
10K ohms minimum from either positive
or negative terminals.
Wiring Gauge:
18 AWG (min.)
to 12 AWG (max.).
Wiring Notes:
1.
All wiring from the AUX/SNAC is power limited.
2.
The conductors must test free of all grounds and stray voltages before connection to appliances and panel.
3.
Terminate Class B NACs, as shown, using a 733- 894 EOL. For Canadian applications, mount end-of-line resistor to a Simplex-US Model 431537
EOL plate in accordance with ULC-S527.
4.
If the wiring is routed outside the building, use of a listed secondary protector is required. Use Simplex2081-9028 (rated 5 A) or 2081-9044 (rated
0.2 A). A protector must be installed at each building exit or entrance. Each 2081-9028 adds 0.2 ohms wiring resistance. 2081-9044 adds 6 ohms
wiring resistance, and greatly reduces the wiring distance.
Fig 28: Simple NAC wiring
Table 25: Simple NAC wiring limits
Alarm current
20 AWG
18 AWG
16AWG
14 AWG
12 AWG
Line resistance (Ohms)
0.25
617 ft
981 ft
1560 ft
2480 ft
3944 ft
14.00
0.50
308 ft
490 ft
780 ft
1240 ft
1972 ft
7.00
0.75
206 ft
327 ft
520 ft
827 ft
1315 ft
4.67
1.00
154 ft
245 ft
390 ft
620 ft
986 ft
3.50
1.25
123 ft
196 ft
312 ft
496 ft
789 ft
2.80
1.50
103 ft
163 ft
260 ft
413 ft
657 ft
2.33
1.75
88 ft
140 ft
223 ft
354 ft
563 ft
2.00
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Table 25: Simple NAC wiring limits
Alarm current
20 AWG
18 AWG
16AWG
14 AWG
12 AWG
Line resistance (Ohms)
2.00
77 ft
123 ft
195 ft
310 ft
493 ft
1.75
Note: This chart indicates the maximum distance for 1/4 -2A loads. The wiring distance is from the panel terminals to the last appliance. Use of a
2081-9044 protector reduces wiring distance.
Output of AUX or NAC is 24 V nominal. The minimum voltage is 19.5 at minimum battery; the maximum is 29.5 V. Aux Loads include the compatible
4007ES annunciators series, 4090 series of IDNet ZAMs and IAMs, and any listed device operating within the output limits of the AUX. Calculate the
wiring loss for the actual devices used. Compatible appliances include 4904 series of free-run strobes, 4901 series non-SmartSync horns, 4098 series
TrueAlarm Sounder Base and 4009 NAC extenders, used in reverse-polarity activation mode.
Table 26: Compatible devices with 24V Aux.power
2088-series relays
2098-series four-wire smoke detectors
4098-series four-wire smoke detectors
4190-9050/9051 4-20mA ZAMs
4090-series IDNet ZAMs
4602-6001, 4602-7001, 4602-7101, and
4602-9150 RCU/SCU Modules
4100-7401, -7402 Graphic Annunciator Modules
6.9 RUI section
RUI overview
The 4007ES RUI channel supports the following devices:
• 4100-7401, 7402 Graphic Modules.
• 4602-6001, 7001, 7101, 9150 RCU/SCU Modules.
Wire from the power supply's RUI channel on terminal block TB1 to each RUI device. The wiring can be Class A or Class B.
Fig 29: Location of the RUI terminal
block
Table 27: RUI specifications
Supports:
Up to 10 RUI devices.
Electrical specifications:
Channel voltage
29.5 V nominal.
Earth detection threshold
10K ohms minimum from either positive or negative terminals.
Capacitance
The maximum allowed line-to-line capacitance (“+” to “-” terminals) is 0.58uF. For
applications with shielded wire, be sure that the total capacitance from line-to-
line plus the shield to either line is not more than 0.58uF.
Wiring
Maximum wiring distance:
(18 AWG, 16 AWG, 14 AWG, 12 AWG)
2,500 feet (762 m) to device from PSU card.
Maximum T- tapping length
10,000 feet (3,048 m).
Notes:
Maintain the correct polarity on terminal connections. Do not loop wires under terminals. If Class A is not used, configure jumpers P1 accordingly.
Shielded wire is not required. Twisted wire is recommended for improved noise immunity.
Figure 30: RUI wiring to the host panel on page 35 depicts Class A and Class B wiring.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 30: RUI wiring to the host panel
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.10Troubleshooting
The code produced by the illuminated indicator LEDs corresponds to a trouble occurring on the system. See Table on page 36 for the IDNet LED
definitions, and see Table on page 36 for the 4007ES trouble messages.
Table 28: LEDs on the 4007ES power supplies
Comm trouble
Normally off. Turns on steady if the IDNet is
not communicating with the FACP CPU.
IDNet trouble
Normally off. Illuminates to indicate a problem
with the IDNet channel:
• Channel failure.
• Line short.
• Class A failure or an open line.
Earth fault+
Illuminates to indicate a positive earth fault.
Earth fault -
Illuminates to indicate a negative earth fault.
IDNet LEDs: A, B, and C
Steady ON: Indicates an open or short
condition on indicated loop.
Fig 31: LEDs on the 4007ES power supplies
Table 29: 4007ES system trouble messages
Message
Definition
AC Fail
AC power is not present or is too low for proper system operation.
Low Battery
The battery voltage is below the 22.8 V nominal level by 10% or more.
Depleted/Missing Battery
The battery is either below 19.4 V or completely undetected.
Card Overcurrent
The module is drawing more current than it should. Check for faults on the circuit.
Charger trouble
The battery charger is either defective or being heavily loaded by batteries. Read charger current at front panel,
if charger current is approximately 1.4 A, batteries are likely loading the charger. Remove battery connection and
measure the output. If the output is 27.6 (or close, temperature dependent), there is a possibility of depleted
batteries or a bad set of batteries. Allow batteries to charge or replace them if they do not take a charge.
If the current is ~1.4 A with batteries and charger voltage below 20 V, remove the batteries and recheck the charger
voltage. If the voltage is around ~27.3 V, then the batteries are heavily depleted.
Extra Device
Appears if one or more extra devices (i.e., devices that have not been configured for the IDNAC or IDNet channel) are
on the system. Only one message appears, regardless of the number of extra devices found.
Earth Fault Search
Comes up during the Earth Fault Search diagnostic function. Once the search is initiated, the front panel display
indicates how far along the search process has progressed (10%, 25%…75%), and then shows the results of the
search. The result either identifies the offending circuit or indicates that the earth fault could not be found. During
the search of circuits (IDNet, NAC, IDNAC, and aux power), system alarm and trouble processing is suspended.
Positive Earth
Appears when a positive earth fault is detected.
Negative Earth
Appears when a negative earth fault is detected.
Short Circuit
Appears when a short is detected on the IDNAC/NAC channel. This status clears automatically when the short circuit
is removed.
Channel Fail
Appears when each device on the IDNet channel has been configured, and when none of the devices are
communicating on the channel. This message does not appear if there are no configured devices on the IDNAC
channel.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
7 Optional modules and cards
The 4007ES can be ordered with a variety of optional cards and modules, depending on the system requirements.
8 Point Zone/ Relay Card
The 8-point Zone/relay Card (4007-9801) mounts in the 4007ES panel. Up to four cards can be added. Each card monitors up to eight Class B or four
Class A zones, or eight relay contacts. For more information about the 8-point zone/relay card, see the 4007-9801 8-Point Zone/Relay Card installation
instructions (579-1103).
25V Regulator Module
The 25V Regulator Module (4007-9802) regulates the panel power supply output received from the NAC power supply (4007ES) or the IDNAC power
supply (4007ES hybrid) to a 25VDC level. The 25VDC regulated output is isolated from the panel and complies with power-limited requirements. For
more information about the 25V regulator module, see the 25 V Regulator Module installation instructions (579-812).
IDNet+ Loop Expansion Card
The IDNet+ loop expansion card (4007-9803) mounts directly on the IDNAC/NAC power supply. Up to two cards can be added. Each card adds a single
Class A/Class B IDNet+ loop and increases the device capacity by 75 points. For more information about the IDNet+ loop expansion card, see the
4007-9803 IDNet+ Loop Expansion Card installation instructions (579-1106).
LED module
The operator uses the LED module (4007-9805) to view the simultaneous signaling of alarm and trouble conditions on up to 24 zones. All the LEDs
have configurable colors, red or yellow, except the LEDs in the last column, which are configurable as red or green.
For more information about the LED module, see the 4007-9805 LED Module installation instructions (579-1105).
The SDACT card
The SDACT card (4007-9806) can be mounted in the 4007ES panel. It is used to notify a central station when an event occurs, to report changes to a
specific point, and to connect a transmitter to a central station. For more information, see the 4010 ES and 4007ES Serial Digital Alarm Communications
Transmitters installation instructions (579-954).
City Circuit
The city circuit card with disconnect switches (4007-8907), and without disconnect switches (4007-9808), are used to annunciate alarms and other
urgent indications to remote facilities. Each city circuit module has two configurable circuits (alarm, trouble, or supervisory reporting) and supports
Reverse Polarity and Local Energy Master Box Applications. Only one city card can be installed on a system. It is not available when an alarm relay is
used.
For more information about city circuits cards, see the City and Relay Cards installation instructions (579-955).
Alarm Relay Card
The Alarm relay card (4007-9809) is used to provide common unsupervised control functions or indications for devices. Each relay module has three
circuits (alarm, trouble, and supervisory signals). It is not available when a city circuit card is used. For more information about alarm relay card, see the
City and Relay Cards installation instructions (579-955).
TrueInsight Service Gateway
The remote service gateway (4190-6104) sends data to a remote service monitoring facility to detail troubles in the panel. When the data reaches the
monitoring facility, a qualified technician is notified by e-mail, and can then begin the diagnostic process remotely. For more information about the
remote service gateway, see the TrueInsight Remote Service gateway installation instructions (579-953).
Dual Class A Isolator
The Dual Class A Isolator (DCAI) (4007-9804) card converts the Class B output of the IDNAC SLC into two isolated Class A outputs. For more
information about the DCAI, see the 4100- 6103, 4007-9804 DCAI Cards installation instructions (579-1029).
NIC
The panel connects to a 4120 network using a NIC slave card. This enables communication between each panel by fiber, modem, or twisted shielded
pair wire in a Style 4 or Style 7 wiring configuration.
Two types of cards can be used with the NIC:
• The Fiber-Optic Media card can be used for noisy electrical environments, or for connecting externally to other buildings.
• The Wired Media Card is used for all other applications.
The 4007ES NIC is part of the 4007-9810 kit which also includes the mounting bracket used to mount the card inside the 4007ES panel. See the
4010ES and 4007ES Network Interface and Media Cards Installation Instructions (579-956) for more information about installing the NIC.
Dual RS-232 Module
The Dual RS-232 interface module provides a serial communication interface to an AC or DC printer, a PC Annunciator, or a third party computer.
Power to both ports can be either isolated or non-isolated. The isolated power is intended for AC printers or PC Annunciators. Ground faults can result
if isolated power is not used for AC devices and third party computers. DC printers use the non-isolated power.
The 4007-9812 Dual RS-232 Interface Module is pre-installed on a bracket and it must be mounted in the top left corner (Block E) of the 4007ES box.
To complete the module installation, complete the following steps:
NOTE: The Dual RS-232 Interface Module cannot be installed if a module such as a 25 V Regulator, DCAI or a Zone Relay Card is already
mounted in Block E inside the panel.
1.
Connect one end of the provided harness (734-308) to connector P7 on the back of the RS-232 card.
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
2.
Use the provided hardware to secure the RS-232 bracket to the 4007ES box.
3.
Connect the free end of harness 734-308 to connector J17 (Zone/Relay) on the IDNAC PSU.
See the Dual RS-232 Interface Module installation instructions (579-910) for more information about installing the module.
7.1 Example of combinations
Figure 32: Example 1 on page 38 , Figure 33: Example 2 on page 38, and Figure 34: Example 3 on page 38 are examples of some of the
combinations that can be made in a 4007ES using the available optional cards and modules.
Fig 32: Example 1
Fig 33: Example 2
Fig 34: Example 3
579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
8 Appendix A ULC programming requirements
8.1 Common earth fault ground and common trouble indicator
This application monitors a system pseudo that counts the number of ground faults or troubles that occur on the system. Each time this counter
increments, such as when a ground fault or trouble occurs, a yellow LED on the operator interface panel illuminates.
Step 1. Add a Custom Control equation to monitor all ground faults:
1.
Click the Custom Control tab.
2.
Add a new equation.
3.
Paste the following equation:
[INPUTS]
STATUS ON
A112 | ANALOG | COUNTER | GROUND TROUBLE COUNTER
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY |
[END OUTPUTS]
NOTE: P535 is shown as an example; use any digital point.
Step 2. Open Color User Interface Card Properties Dialog
1.
Click the Hardware tab and expand the Unit 0, Box 1, Bay 1 icons to display the Color User Interface Card. Click the + signs to the left of the
Unit 0, Box 1, and Bay 1 icons to expand them.
Fig 35: Selecting the Color User Interface
Card
2.
Right-click the Color User Interface card icon and select Properties.
3.
Click the Point Editing tab, see Figure 36: The Display tab:Display Checkboxes on page 39.
Fig 36: The Display tab:Display Checkboxes
Step 3. Program the LED
1.
Select one of the multicolor LEDs (3-2-1, 3-2-2, or 3-2-3) to program.
2.
Click the Point Type drop down list and select LEDYELLOW.
3.
Click the Mode drop down list and select ON.
4.
Enter P535, or your chosen digital point number from the equation, in the Reference Address field to program the LED for ground faults.
OR
5.
Enter A2 (no spaces) in the Reference Address field to program the LED to illuminate whenever a general system trouble is present.
579-1102 Rev H
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to
change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals
under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is
strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).