MG & SG SERIES BOILERS

S9361A CONTROL SUPPLEMENT MANUAL FOR MODELS MG-50-E TO MG-150-E AND SG-135-E TO SG-270-E This supplement manual must be used in conjunction with the Installation and Service Manual provided with your boiler. It provides important instructions relevant to controller programming, operation, troubleshooting, and wiring. NEW CONTROLLER Allied Engineering Company Division of E-Z-Rect Manufacturing Ltd. Manufacturers of Gas and Electric Boilers, Stainless Steel Tanks, Heat Exchangers and Electric Boosters. 94 Riverside Drive, North Vancouver, B.C. V7H 2M6 • Telephone (604) 929-1214 • www.alliedboilers.com Branches: Calgary • Edmonton • Toronto • Denver Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury, or loss of life. Please carefully read this manual along with the Installation and Service Manual. For assistance or additional information, consult a qualified installer, service agency or the gas supplier. WARNING

CONTROLLER PROGRAMMING AND SERVICE CODES

Section 1 1.1 CONTROLLER PROGRAMMING AND SERVICE CODES 2012 NRCan and DOE Compliance and Operation Operation of this control may delay the burner operation while the residual heat is circulated out of the boiler. Text Description The integrated boiler control module provides ignition sequence, flame monitoring and safety shutoff for intermittent pilot spark ignition. It also provides limit rated water temperature control for with two separate sensors in one casing (3-wire). The control is located on the front panel inside the boiler. The control display, along with Up ▲, Down ▼, and “I” keys may be used to view boiler operating status and program parameters (Figure 1). 1.1.1 RUN MODE Figure 1 Control Display In the RUN mode, status items and parameters are viewable. To read settings, press and release the “I” key to find the parameter of interest. Each setting will alternately flash between the relevant display code listed in the Table 1 and its corresponding value. For example, press and release “I” key until “HL_” setpoint is displayed, it will then flash a three-digit number, i.e., 220, followed by ˚F (or ˚C). This indicates that the boiler water temperature of 220 ˚F is set. Other operating parameters display the settings in a similar fashion. Display STA Status (see status numbers) StA BT Boiler temperature bt SP Operating setpoint SP HL High limit setpoint HL HDF Differential set-point HdF FLA Flame current FLA RUN Run time hours run CYC Boiler cycles CYC ERR Error (see error numbers) Err Table 1 Run Mode Parameters

1.1.2 INSTALLER MODE

To enter the adjustment mode: 1. Press with Up ▲, Down ▼, and “I” keys (see Figure 1) simultaneously for three seconds. 2. Press and release the “I” key until the parameter (listed in the Table 2) requiring adjustment is displayed. 3. Press with Up ▲ or Down ▼ key until the parameter has reached the desired value. 4. After 60 seconds without any key inputs, the control will automatically return to the RUN Mode. Table 2 Installer Mode Options 3-Digit 7-Segment Display 1st Screen 2nd Screen (setting value) 3rd Screen Default Range Description HL_ ˚F or ˚C 180 ˚F 130 to 220 ˚F Adjust high limit setting HdF ˚F or ˚C 15 ˚F 10 to 30 ˚F Adjust high limit differential Or_ Sec 60 sec 0 to 120 seconds Pump post-purge time otH ˚F or ˚C 55 ˚F 40 to 70 ˚F Maximal outdoor temperature otL ˚F or ˚C 0 ˚F -40 to 40 ˚F Minimal outdoor temperature btL ˚F or ˚C 140 ˚F 130 to 150 ˚F Minimal boiler temperature tPL ˚F or ˚C 140 ˚F OFF, 120 to 160 ˚F Thermal purging minimal temperature (parameter is available only if outdoor temperature is invalid) tPt Min 2 1 to 10 minutes Maximal thermal purge time (parameter is available only if outdoor temperature is invalid) rSt On or OFF N/A N/A Reset lockout F-C ˚F or ˚C ˚F ˚F or ˚C Select degrees ˚F or ˚C mode

1.1.3 OPERATING CHECKOUT

After adjusting parameters, put the boiler into operation and observe operation through at least one complete cycle to make sure that the controller operates properly. See controller troubleshooting section to assist in determining boiler operation. The sensor should fit snugly and should touch the bottom of the well for best temperature response. The sensor is held inside the well using the well clip. 1.1.4 THERMAL PURGE The intent of thermal purge is to ensure usable residual heat in the boiler is circulated until it is sufficiently depleted from the system before the burner is allowed to fire. To that end, on a call for heat, the burner remains off while the circulator runs until the boiler temperature drops to the thermal purge temperature limit or the time delay is exceeded. Both of these parameters are adjustable. When the boiler temperature falls below the thermal purge temperature limit or the time delay expires, the burner is allowed to fire. In addition to the thermal purge temperature and thermal purge time delay parameters, two other conditions release the integrated boiler controller from thermal purge and allow the burner to run in order to maintain comfort in the space: • The boiler temperature has dropped 10 °F from the boiler water temperature measured at the beginning of the call for heat. • Boiler temperature is cooling at a rate greater than 5 °F/minute while the circulator is running. 1.1.5 OPERATING STATE CODES AND TROUBLESHOOTING When there is a problem during a call for heat or boiler operation, the controller provides specific information to help resolve the issue quickly. If the controller is displaying “StA” by a number, use the state code definitions in Table 3 to determine the problem and possible causes. 1.1.6 CONTROLLER MOUNTING The controller has four tabs which align with four slots in the control panel. To remove the controller, press and hold in the bottom two tabs while simultaneously rotating the controller about 45 degrees to unhook the top two tabs. Rotate 45° PRESS and HOLD both tabs while rotating controller Figure 2 Controller Replacement

Table 3 State Code Definitions

Display Code State Specific Description Operation Sequence Idle/Standby The boiler is in standby - no call for heat StA ↔1 Run circulator Heat request present but boiler water temperature sufficiently high to run circulator pump only (no ignition sequence) Thermostat Calls For Heat Self Test Hardware self check, check of connected periphery, it is performed at start up, in the beginning of the heat cycle and in the “Wait For recovery” state StA ↔17 Wait for recovery There is an external error and the control is waiting to recover, no lockout Circulator output energizes StA ↔ 2 Wait for end switch to open The control is waiting for the end switch of the vent damper to open at the beginning of a heat cycle. If the end switch doesn’t open in 60 seconds, the control goes to error code Err 2 StA ↔ 3 Wait for end switch to close The control is waiting for the end switch of venting damper to close at the beginning of a cycle. If the end switch doesn’t close within 60 seconds, the control goes to error code Err 29 StA ↔ 4 Pump pre-purge/ thermal purge System is purging before ignition trial-safety relay diagnostics followed safety relay switch-on during last 2 seconds this sate StA ↔ 6 Spark, ignition activation System is sparking permanently 13 seconds whilst pilot gas valve relay is turned on StA ↔ 7 Prove flame System is proving flame signal, typically 2 seconds StA ↔ 8 Running System is in running mode, flame signal must be present Call For Heat Ends StA ↔ 9 Pump post-purge System is purging at the end of a call for heat Troubleshooting/Diagnostics StA ↔10 Inter-purge (retry/recycle delay) If the control loses flame signal during state code 7 or 8, or flame is not detected during stat code 6 to 8, it will recycle through the 30 seconds purge time and last 2 seconds part of pre-purge time Err ↔ 2 Wait for end switch to open – failed closed The end switch of venting damper has not opened at the beginning of the heat cycle. The control is not in lockout Err ↔ 29 Wait for end switch to close – failed open Waiting time for pressure switch to close expired. The control is not in lockout Err ↔ 62 Soft lockout System is shutdown and will re-start following an enforced delay StA ↔15 Wait for limit to close There may be a call for heat from the thermostat, but the limit switch is open Flame out of sequence – before trial Flame signal sensed before trial for ignition. Flame out of sequence – after trial Flame out of sequence during post-purge. StA ↔16 Wait for flame loss Flame signal still present when not expected.

If the controller is displaying “Err” followed by a number, use the error code definitions in the Table 4 to

determine the problem and possible causes. Table 4 Error Codes Display State Solution Err ↔ 2 End switch of venting damper failed to open The end switch contacts stuck closed. Check the venting damper and replace it if necessary. Err ↔ 4 Low flame current Check pilot assembly and replace it if necessary. Err ↔ 6 Flame sensed out of normal sequence Flame sensed out of normal sequence (before opening gas valve or after closing gas valve). Err ↔18 Gas valve relays welded 5 consecutive soft lockouts A manual reset is required. Err ↔ 23 Flame sensed during pre-purge Flame sensed during pre-purge (before gas valve signaled opened) Err ↔ 24 Flame sensed during post-purge Flame sensed during post-purge (before gas valve signaled closed) Err ↔ 29 End switch of venting damper failed to close The end switch contacts stuck open. Check the venting damper and replace it if necessary. Err ↔ 32 Sensor error Temperature sensor or interface failure (open or short connection, increased connection resistance, dual sensor mismatch) or failure of A/D conversion (invalid offset or gain, too many failures during A/D conversion). Err ↔ 57 Flame rod shorted to burner ground Check and adjust or replace if necessary. Err ↔ 58 AC line frequency error AC signal is too noisy or frequency is incorrect. Err ↔ 59 Line voltage error AC voltage out of specification high or low. Err ↔ 60 Thermostat input higher than threshold Check thermostat wiring and replace it if necessary. Err ↔ 61 Line voltage unstable Possibly too many heavy loads switching on and off cause erratic supply voltage. Err ↔ 62 Soft lockout Maximum number of retries exceeded. Err ↔ 63 Soft lockout Maximum number of recycles exceeded. Err ↔ 64 Soft lockout Internal failure (Electronics failure). Caused by general electronics failure such as relay open or shorted contacts, flame sensing circuit error, or A to D error. Err ↔ 65 Over temperature error Sensor measured temperature in excess of ECO limit.