Viessmann Vitodens 200-W System Technical Data Manual
Read Online
Read the Viessmann Vitodens 200-W System Technical Data Manual online using the built-in PDF viewer.
Text of the manual
Gas-fired wall-mounted condensing boiler
31 to 370 MBH / 9 to 105 kW
Multi-boiler installation 320 to 1480 MBH/
Vitodens 200-W
WB2B Series
Gas-Fired Wall-Mounted Condensing Boiler
with modulating MatriX cylinder burner
for room air independent operation
(using a direct vent system) or room air
dependent operation
For Natural Gas and Liquid Propane Gas
Heating input
31 to 370 MBH
for NG and LPG
9 to 105 kW
Technical Data Manual
Model Nos. and pricing: see Price List
This trademark is registered with the U.S. Patent and Trademark Office.
5369 295 v1.2
08/2010
Equipped with the industry’s first intelligent
combustion management system and
powerful control technology, the new
generation Vitodens 200-W gas-fired
wall-mount condensing boiler delivers
unparalleled performance, reliability and
comfort.
The benefits at a glance:
Best value in its class with new
industry-leading technology and the most
standard features.
Highest Efficiency up to 98% at full
modulation and up to 96.1% A.F.U.E.
CSA thermal efficiency rating to ANSI
Z.21.13/CSA 4.9 of 94.5% (for model
WB2B 105 only). Energy Star and the
CSA Energy Performance are not
applicable for model WB2B 105.
Lasting performance with industry-leading
Viessmann made SA240 316 Ti stainless
steel Inox-Radial heat exchanger
constructed to CSA B51 and ASME
Section IV.
Low Emission Combustion with Viessmann
made stainless steel MatriX cylinder
burner. Factory calibrated.
Fast Installation and Reduced Maintenance
with Lambda Pro, industry-first intelligent
combustion management system: Adjusts
automatically to gas type and quality. No
fuel conversion kit required.
Powerful and User-friendly
Viessmann Vitotronic on-board
multi-function outdoor reset boiler and
system control for multi-temperature
space and DHW heating.
Expanded Application Range with
increased capacity up to 370 MBH.
Multi-boiler installation up to 1480 MBH
with up to 4 boilers (models WB2B 45,
60, 80, 105).
Greater Venting Flexibility with increased
vent length (up to 180 ft. / 55 m) and
multiple venting options.
- Horizontal or vertical sealed combustion
coaxial venting (factory supplied).
- Horizontal, vertical or hybrid sealed
combustion double-pipe venting (field
supplied).
- Horizontal or vertical single-wall venting
(field supplied).
‘
Compact, Esthetic Product Design
and zero clearance to combustibles.
Extremely Quiet Operation; quieter than
most refrigerators.
True High-Altitude Operation up to
10,000 ft. / 3,000 m with simple
electronic adjustment.
5369 295 v1.2
Vitotronic 200, HO1
on-board outdoor
reset control
Boiler may not look exactly as illustrated.
Cross-Section
3
5369 295 v1.2
Model No. WB2B-
19
26
35
45
60
80
105*A
Natural gas / Liquid propane gas
CSA input
CSA output/DOE*1
heating capacity
MBH
kW
MBH
kW
31-67
9-20
28-61
8-18
31-93
9-27
28-85
8-25
31-125
9-37
28-114
8-33
60-160
17-47
55-146
16-43
60-212
17-62
55-194
16-57
104-285
30-83
95-260
28-76
104-370
30-108
98-350
29-103
Net I=B=R rating*2
MBH
53
74
99
127
169
226
304
Heat exchanger surface area
ft.2
m2
10.23
0.95
10.23
0.95
10.23
0.95
15.76
1.46
15.76
1.46
28.88
2.68
28.88
2.68
Min. gas supply pressure
Natural gas
Liquid propane gas
“w.c.
“w.c.
4
10
4
10
4
10
4
10
4
10
4
10
4
10
Max. gas supply pressure*3
Natural gas
Liquid propane gas
“w.c.
“w.c.
14
14
14
14
14
14
14
14
14
14
14
14
14
14
A.F.U.E.
%
96.1
96.1
96.1
96.1
96.1
96.1
CSA thermal efficiency
ANSI Z21.13/CSA 4.9
%
94.5
Weight
lbs
kg
102
46
102
46
102
46
155
70
155
70
225
102
225
102
Boiler water content
USG
L
0.87
3.3
0.87
3.30
0.87
3.3
1.9
7.2
1.9
7.2
3.4
12.8
3.4
12.8
Boiler max. flow rate*4
GPM
L/h
6.2
1400
6.2
1400
6.2
1400
15.4
3500
15.4
3500
35.2
8000
35.2
8000
Max. operating pressure
at 210ºF / 99ºC
psig
bar
45
3
45
3
45
3
60
4
60
4
60
4
60
4
Boiler water temperature
– Adjustable high limit (AHL)
range
space heating
(steady state)
DHW production
– Fixed high limit (FHL)
ºF/
ºC
ºF/
ºC
ºF/ºC
68 to 165 /
20 to 74
165 /
74
210/99
68 to 176 /
20 to 80
176 /
80
210/99
Boiler connections
Boiler heating supply and return NPTM “
Pressure relief valve
NPTF “
Drain valve
(male
thread)
Boiler supply/return for
indirect-fired DHW storage tank NPT”
(field supplied)
Gas valve connection
NPTF
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
1¼
¾
¾
1¼
1
1¼
¾
¾
1¼
1
1¼
¾
¾
1¼
1
1¼
¾
¾
1¼
1
*A For high altitude installations (5,000 - 10,000 ft.), the input for model WB2B 105 will have an altitude de-ration of 14% for 5,000 ft.
and 28% for 10,000 ft. (average of 2.8% / 1,000 ft.).
*1 Output based on 140ºF / 60ºC, 120ºF / 49ºC system supply/return temperature.
*2 Net I=B=R rating based on piping and pick-up allowance of 1.15.
*3 If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed upstream of the
heating system.
*4 See “Typical System Flow Rates” on page 11 in this manual.
5369 295 v1.2
Table 1 (continued)
Boiler Model
Model No. WB2B-
19
26
35
45
60
80
105*A
Dimensions
Overall depth
Overall width
Overall height
Height with flue gas elbow
(accessory)
inches
mm
inches
mm
inches
mm
inches
mm
14
360
17¾
450
33½
850
44
1116
14
360
17¾
450
33½
850
44
1116
14
360
17¾
450
33½
850
44
1116
15
380
19
480
33½
850
47¼
1200
15
380
19
480
33½
850
47¼
1200
21
530
19
480
33½
850
47¼*9
1200
21
530
19
480
33½
850
47¼*9
1200
Flue gas*5
Temperature (at boiler return
temperature of 86ºF / 30ºC)
– at rated full load
– at rated partial load
Temperature (at boiler return
temperature of 140ºF / 60ºC)
ºF/ºC
ºF/ºC
ºF/ºC
113/45
95/35
154/68
113/45
95/35
158/70
113/45
95/35
158/70
95/35
91/33
149/65
104/40
95/35
158/70
95/35
91/33
149/65
104/40
95/35
158/70
Average condensate
flow rate*6
with natural gas and
TS/TR =104/86ºF / 40/30ºC
USG/day
L/day
2.6-3.4
10-12
2.9-3.4
11-13
4-4.5
15-17
3.7-5
14-19
6-7.4
23-28
6.6-7.9
25-30
9.5-10.5
35-40
Condensate connection*7
hose
nozzle
∅in
1
1
1
1
1
1
1
Boiler flue gas connection*8
∅
in/mm
23/8 /60
23/8 /60
23/8 /60
3¼/80
3¼/80
43/8 /110
43/8 /110
Combustion air supply
connection (coaxial)*8
outer
∅in/mm
4/100
4/100
4/100
5/125
5/125
6/150
6/150
*A For high altitude installations (5,000 - 10,000 ft.), the input for model WB2B 105 will have an altitude de-ration of 14% for 5,000 ft.
and 28% for 10,000 ft. (average of 2.8% / 1,000 ft.).
*5 Measured flue gas temperature with a combustion air temperature of 68°F / 20°C.
*6 Based on typical boiler cycles, including partial load conditions.
*7 Requires 1” / 25 mm tubing. See the Installation Instructions of the Vitodens 200-W, WB2B for details.
*8 For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, WB2B Venting System.
A maximum of 5 elbows may be installed in the vent system.
Do not attempt to common-vent Vitodens 200-W with any other appliance.
Venting material to be supplied by Viessmann only; side wall vent installation must include Viessmann protective screen!
For details refer to the Installation Instructions for the Vitodens 200-W, WB2B Venting System.
*9 Add 2½” / 65 mm for coaxial vent pipe transition adaptor.
For information regarding other Viessmann System Technology componentry, please reference documentation of respective product.
5369 295 v1.2
6¼” / 158 mm
55/8” /
143 mm
1¾” /
44 mm
141/8” /
360 mm
2¾” /
70 mm
2½” /
65 mm
7” / 177 mm
13¾” /
348 mm
87/8” / 225 mm
4” / 102 mm
4” / 102 mm
33½” /
850 mm
12” /
300 mm
2¾” /
70 mm
17¾” /
450 mm
BS
BR
PRV
BD
DS
GC
DR
BF
*1 DHW Connections
(Field Supplied)
EXT
EXT
Floor line
78” / 1975 mm
for single boiler
installation
Fig. 1
Fig. 2
Fig. 3
6
*1
Models WB2B 19, 26, 35
Legend
BD
Boiler Drain
BR
Boiler Return
BS
Boiler Supply
AV
Air Vent (not shown)
GC
Gas Connection, ¾” NPT
PRV
Pressure Relief Valve
BF
Boiler Fill
PG
Pressure Gage
EXT
Extension Adaptors, ¾” NPT
DR
Boiler heating return for domestic hot
water production ¾” (field supplied)
DS
Boiler heating supply for domestic
hot water production ¾” (field
supplied)
*1
See page 38 for alternate DHW
connection.
5369 295 v1.2
19” / 480 mm
9½” / 240 mm
35½” /
902 mm
39” /
996 mm
41¾” /
1061 mm
51” /
1301 mm
78” / 1975 mm
for single boiler
installation
9½” /
240 mm
6½” /
165 mm
9½” / 240 mm
3” / 80 mm
15¾” /
400 mm
6½” /165 mm
5½” / 146 mm
4” / 100 mm
15” /
380 mm
Ø 5” /
125 mm
33½ “/
850 mm
12” /
305 mm
PRV
BD
GC
BF
PG
Floor line
BS
BR
DS
DR
*1 DHW Connections
(Field Supplied)
Fig. 4
Fig. 5
Fig. 6
7
Models WB2B 45, 60
Legend
BD
Boiler Drain
BR
Boiler Return
BS
Boiler Supply
AV
Air Vent (not shown)
GC
Gas Connection, 1” NPT
PRV Pressure Relief Valve
BF
Boiler Fill
PG
Pressure Gage
DR
Boiler heating return for domestic hot
water production 1¼” (field supplied)
DS
Boiler heating supply for domestic hot
water production 1¼” (field supplied)
*1
See page 38 for alternate DHW
connection.
5369 295 v1.2
3” / 80mm
9½” / 240mm
15¾” /
400mm
6½” /
165mm
9½” /
240mm
9½” /
236mm
4” / 102mm
21” /
530mm
15¾” /
400mm
Floor line
PRV
BD
GC
BF
PG
78” / 1975 mm
for single boiler
installation
BS
BR
DS
*1 DHW Connections
(Field Supplied)
DR
Fig. 7
Fig. 8
11 5/8“ / 295mm
for WB2B 80-105
using the coaxial
vent system
Fig. 9
8
Models WB2B 80, 105
Legend
BD
Boiler Drain
BR
Boiler Return
BS
Boiler Supply
GC
Gas Connection, 1” NPT
PRV Pressure Relief Valve
BF
Boiler Fill
PG
Pressure Gage
DR
Boiler heating return for domestic hot water production 1¼”
DS
Boiler heating supply for domestic hot water production 1¼”
*1
See page 38 for alternate DHW connection.
5369 295 v1.2
Recommended Minimum Service Clearances
Minimum Clearances to Combustibles
Top
Front
Rear
Left
Right
Vent pipe*1
0
0 AL, CL
0
0
0
0
AL= Alcove
CL= Closet
*1Refer to the Installation Instructions of the Vitodens 200-W, WB2B Venting System for details.
Please note:
The Vitodens boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the Harmonized Standard
ANSI Z21.13. CSA 4.9.2000 and therefore is listed for zero clearance to combustibles when vented with a single wall special venting
system (AL-29-4C material). The zero inches vent clearance to combustibles for the Vitodens boiler supercedes the clearance to
combustibles listing that appears on the special venting system label.
5369 295 v1.2
Front
12” / 305 mm
Top
12”/305 mm
0”/mm
Side
0”/mm
Back
Side
28” / 700 mm
Fig. 10
Waterside Flow (primary circuit)
The Vitodens 200-W, WB2B is designed for closed loop, forced circulation hot water heating systems only.
Pressure drop (primary circuit) for Vitodens
200-W, WB2B 19, 26, 35
For sizing an on-site circulation system.
Max. flow rate: 1400 L/h / 6.2 GPM
Pressure drop (primary circuit) for Vitodens
200-W, WB2B 45, 60
For sizing an on-site circulation system.
Max. flow rate 3500 L/h / 15.4 USGPM
Pressure drop (primary circuit) for Vitodens
200-W, WB2B 80, 105
For sizing an on-site circulation system.
Max. flow rate 8000 L/h / 35.2 USGPM
Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds
boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly
recommends the installation of a low-loss header. An alternative method may be used, such as primary secondary piping using closely
spaced tees. A low-loss header offers additional benefits not provided by a pair of closely spaced tees. Viessmann therefore strongly
recommends and prefers the use of a low-loss header over closely spaced tees. See page 13 for low-loss header information.
5369 295 v1.2
0
500
1000
1500
0
1
2
3
4
5
6
0
3.3
6.6
9.8
13.1
16.4
19.7
2000
l/h
7
8
23
26
Supply head pressure (water)
0
2.2
4.4
6.6
8.8
GPM
H(ft.) H(m)
Fig. 11
H(ft.) H(m)
20.1
6.1
16.7
5.1
13.4
4.1
10.0
3.1
6.7
2.0
3.4
1.0
0
0
0
0
500
1000
1500
2000
2500
3000
3500
l/h
2.2
4.4
6.6
8.8
11
13.2
15.4 GPM
Supply head pressure (water)
Fig. 12
H(ft.) H(m)
33.5 10.2
30.1 9.2
8.2
26.8
7.1
23.4
6.1
20.1
5.1
16.7
4.1
13.4
3.1
10.0
2.0
6.7
1.0
3.4
0
0
0
0
1000
2000
3000
4000
5000
6000
7000
8000 l/h
4.4
8.8
13.2
17.6
22.0
26.4
30.8
35.2 GPM
Supply head pressure (water)
Fig. 13
System Flow Rates
11
Typical System Flow Rates
Table 2.
Model
WB2B
19
26
35
∆∆∆∆t for NG/LPG
Output (NG/LPG) Btu/h
61 000
85 000 114 000
20ºF rise (GPM)
6.1
8.5
11.4
25ºF rise (GPM)
4.9
6.8
9.1
30ºF rise (GPM)
4.1
5.7
7.6
35ºF rise (GPM)
3.5
4.9
6.5
40ºF rise (GPM)
3.1
4.3
5.7
Table 3.
Model
WB2B
45
60
∆∆∆∆t for NG/LPG
Output (NG/LPG) Btu/h
146 000
194 000
20ºF rise (GPM)
14.6
19.4
25ºF rise (GPM)
11.7
15.5
30ºF rise (GPM)
9.7
12.9
35ºF rise (GPM)
8.3
11.1
40ºF rise (GPM)
7.3
9.7
Table 4.
Model
WB2B
80
105
∆∆∆∆t for NG/LPG
Output (NG/LPG) Btu/h
260 000
350 000
20ºF rise (GPM)
26.0
35.0
25ºF rise (GPM)
20.8
28.0
30ºF rise (GPM)
17.3
23.3
35ºF rise (GPM)
14.9
20.0
40ºF rise (GPM)
13.0
17.5
Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds
boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly
recommends the installation of a low-loss header. Once the low-loss header is connected, the built-in low-loss header logic of the Vitodens
200-W boiler ensures the required ∆∆∆∆T across the system through the sensory communication between the low-loss header and the boiler.
See page 13 for low-loss header information.
5369 295 v1.2
Boiler max. flow rate 1400 L/h (6.2 GPM)
Boiler max. flow rate 3500 L/h (15.4 GPM)
Boiler max. flow rate 8000 L/h (35.2 GPM)
Heating Circuit / Boiler Pumps
Viessmann offers a variety of Grundfos heating circuit / boiler pumps which meet typical Vitodens system installation requirements (see
“Heating circuit pump (field supplied)“ or “Boiler pump (field supplied)” in the Installation Examples starting on page 29). See tables below
for recommended pumps. Refer to the graphs on page 10 for the proper waterside boiler friction loss calculations.
Pump selection must be based on accurate
system flow and pressure drop calculations
(incl. DHW sizing).
The following pumps have been selected based on boiler heat exchanger head loss and boiler piping to a low-loss header. Before
using the following pumps for a DHW tank application, find out the proper pressure drop through the tank, the required
temperature difference through the coil and system piping head loss of the domestic hot water.
Table 5.
Model
WB2B
19
26
35
Flow rate
20 ºF ∆∆∆∆t
6.1
8.5
11.4
25 ºF ∆∆∆∆t
4.9
6.8
9.1
30 ºF ∆∆∆∆t
4.1
5.7
7.6
35 ºF ∆∆∆∆t
3.5
4.9
6.5
40 ºF ∆∆∆∆t
3.1
4.3
5.7
Flow limitation L/h / GPM
1400 / 6.2
Recommended boiler pumps
Grundfos 15-58 (3-speed)
Taco 00R
Wilo Star S 21 FX
Table 6.
Model
WB2B 45
Flow rate
Boiler pressure
drop (ft.)
Recommended pump option 1
Grundfos
Recommended pump option 2
Grundfos
20 ºF ∆∆∆∆t
14.6
15.8
UPS 26-99FC, 115V, Speed3
25 ºF ∆∆∆∆t
11.7
10.0
UPS 26-99FC, 115V, Speed2
UP 26-64F, 115V
30 ºF ∆∆∆∆t
9.7
7.5
UPS 26-99FC, 115V, Speed2
35 ºF ∆∆∆∆t
8.3
5.8
UPS 26-99FC, 115V, Speed1
40 ºF ∆∆∆∆t
7.3
4.2
UPS 26-99FC, 115V, Speed1
Flow limitation L/h / GPM
3500 / 15.4
Table 7.
Model
WB2B 60
Flow rate
Boiler pressure
drop (ft.)
Recommended pump option 1
Grundfos
Recommended pump option 2
Grundfos
20 ºF ∆∆∆∆t
19.4
Not Recommended
Not Recommended
25 ºF ∆∆∆∆t
15.5
16.7
UPS 26-99FC, 115V, Speed3
30 ºF ∆∆∆∆t
12.9
12.6
UPS 26-99FC, 115V, Speed3
UP 26-64F, 115V
35 ºF ∆∆∆∆t
11.1
9.2
UPS 26-99FC, 115V, Speed2
UP 26-64F, 115V
40 ºF ∆∆∆∆t
9.7
7.5
UPS 26-99FC, 115V, Speed2
Flow limitation L/h / GPM
3500 / 15.4
5369 295 v1.2
IMPORTANT
Pump and Low-Loss Header Information
13
Heating Circuit / Boiler Pumps (continued)
Table 8.
Model
WB2B 80
Flow rate
Boiler pressure
drop (ft.)
Recommended pump
Grundfos
20 ºF ∆∆∆∆t
26.0
16.7
UPS 32-160/2, 115V, Speed1
25 ºF ∆∆∆∆t
20.8
9.2
UPS 26-99FC, 115V, Speed3
30 ºF ∆∆∆∆t
17.3
6.5
UPS 26-99FC, 115V, Speed2
35 ºF ∆∆∆∆t
14.9
4.8
UPS 26-99FC, 115V, Speed2
40 ºF ∆∆∆∆t
13.0
3.4
UPS 26-99FC, 115V, Speed2
Flow limitation L/h / GPM
8000 / 35.2
Table 9.
Model
WB2B 105
Flow rate
Boiler pressure
drop (ft.)
Recommended pump
Grundfos
20 ºF ∆∆∆∆t
35.0
30.0
UPS 32-160/2, 115V, Speed3
25 ºF ∆∆∆∆t
28.0
20.0
UPS 32-160/2, 115V, Speed2
30 ºF ∆∆∆∆t
23.3
12.5
UPS 32-160/2, 115V, Speed1
35 ºF ∆∆∆∆t
20.0
9.0
UPS 26-99FC, 115V, Speed3
40 ºF ∆∆∆∆t
17.5
6.4
UPS 26-99FC, 115V, Speed2
Flow limitation L/h / GPM
8000 / 35.2
Table 10. Sizing of Low-Loss Header in a Residential Single-Boiler Application
Boiler
Model
No. of
Boilers
Boiler
Max.
Flow Rate
Typical System Flow Rates
Viessmann
Temp. Sensor
Required
System ∆∆∆∆t
*1
20
11.0
25
13.9
30
16.8
35
16.1
40
13.4
°F
°C
WB2B 19
1
6.1
1385
System Flow Rate
LLH Required
LLH Model
6.1
1385
Yes
80/50
4.9
1108
Optional
80/50
4.1
924
Optional
80/50
3.5
792
Optional
80/50
3.1
693
Optional
80/50
GPM
L/h
Yes
WB2B 26
1
6.1
1385
System Flow Rate
LLH Required
LLH Model
8.5
1931
Yes
80/50
6.8
1544
Yes
80/50
5.7
1287
Optional
80/50
4.9
1103
Optional
80/50
4.3
965
Optional
80/50
GPM
L/h
Yes
WB2B 35
1
6.1
1385
System Flow Rate
LLH Required
LLH Model
11.4
2589
Yes
80/50
9.1
2071
Yes
80/50
7.6
1726
Yes
80/50
6.5
1480
Yes
80/50
5.7
1295
Optional
80/50
GPM
L/h
Yes
WB2B 45
1
15.4
3498
System Flow Rate
LLH Required
LLH Model
14.6
3316
Yes
80/50
11.7
2653
Optional
80/50
9.7
2211
Optional
80/50
8.3
1895
Optional
80/50
7.3
1658
Optional
80/50
GPM
L/h
Yes
WB2B 60
1
15.4
3498
System Flow Rate
LLH Required
LLH Model
19.4
4406
Yes
120/80
15.5
3525
Yes
80/50
12.9
2937
Optional
80/50
11.1
2518
Optional
80/50
9.7
2203
Optional
80/50
GPM
L/h
Yes
WB2B 80
1
35
7949
System Flow Rate
LLH Required
LLH Model
26.0
5905
Yes
120/80
20.8
4724
Yes
120/80
17.3
3937
Optional
120/80
14.9
3374
Optional
120/80
13.0
2953
Optional
120/80
GPM
L/h
Yes
WB2B 105
1
35
7949
System Flow Rate
LLH Required
LLH Model
35.2
7949
Yes
120/80
28.0
6359
Yes
120/80
23.3
5300
Yes
120/80
20.0
4542
Optional
120/80
17.5
3975
Optional
120/80
GPM
L/h
Yes
*1 For system ∆t < 20°F use low-loss header sizes for ∆t 20°F.
5369 295 v1.2
Low-Loss Header Information
14
Low-Loss Header Application (continued)
Table 11. Sizing of Low-Loss Header in a Commercial Multiple-Boiler Application
Boiler
Model
No. of
Boilers
Boiler
Max.
Flow
Rate
Total
Flow
Rate
Typical System Flow Rates
Viessmann
Temp.Sensor
Required *2
System ∆∆∆∆t *1
20
11.0
25
13.9
30
16.8
35
16.1
40
13.4
°F
°C
WB2B 45
2
15.4
3498
30.8
6995
System Flow Rate
LLH Required
LLH Model
29.2
6632
Yes
120/80
23.4
5306
Yes
120/80
19.5
4421
Yes
120/80
16.7
3790
Yes
120/80
14.6
3316
Yes
120/80
GPM
L/h
Yes
WB2B 45
3
15.4
3498
46.2
10493
System Flow Rate
LLH Required
LLH Model
43.8
9948
Yes
160/80
35.0
7958
Yes
120/80
29.2
6632
Yes
120/80
25.0
5685
Yes
120/80
21.9
4974
Yes
120/80
GPM
L/h
Yes
WB2B 45
4
15.4
3498
61.6
13991
System Flow Rate
LLH Required
LLH Model
58.4
13264
Yes
200/120
46.7
10611
Yes
200/120
38.9
8843
Yes
160/80
33.4
7579
Yes
120/80
29.2
6632
Yes
120/80
GPM
L/h
Yes
WB2B 60
2
15.4
3498
30.8
6995
System Flow Rate
LLH Required
LLH Model
38.8
8812
Yes
160/80
31.0
7050
Yes
120/80
25.9
5875
Yes
120/80
22.2
5036
Yes
120/80
19.4
4406
Yes
120/80
GPM
L/h
Yes
WB2B 60
3
15.4
3498
46.2
10493
System Flow Rate
LLH Required
LLH Model
58.2
13219
Yes
200/120
46.6
10575
Yes
200/120
38.8
8812
Yes
160/80
33.3
7554
Yes
120/80
29.1
6609
Yes
120/80
GPM
L/h
Yes
WB2B 60
4
15.4
3498
61.6
13991
System Flow Rate
LLH Required
LLH Model
77.6
17625
Yes
200/120
62.1
14100
Yes
200/120
51.7
11750
Yes
200/120
44.3
10071
Yes
160/80
38.8
8812
Yes
160/80
GPM
L/h
Yes
WB2B 80
2
35
7949
70
15899
System Flow Rate
LLH Required
LLH Model
52.0
11810
Yes
200/120
41.6
9448
Yes
160/80
34.7
7874
Yes
160/80
29.7
6749
Yes
160/80
26.0
5905
Yes
160/80
GPM
L/h
Yes
WB2B 80
3
35
7949
105
23848
System Flow Rate
LLH Required
LLH Model
78.0
17716
Yes
200/120
62.4
14173
Yes
200/120
52.0
11810
Yes
200/120
44.6
10123
Yes
200/120
39.0
8858
Yes
160/80
GPM
L/h
Yes
WB2B 80
4
35
7949
140
31797
System Flow Rate
LLH Required
LLH Model
104.0
23621
Yes
250/150
83.2
18897
Yes
250/150
69.3
15747
Yes
200/120
59.4
13498
Yes
200/120
52.0
11810
Yes
200/120
GPM
L/h
Yes
WB2B 105
2
35
7949
70
15899
System Flow Rate
LLH Required
LLH Model
70
15899
Yes
200/120
56
12719
Yes
200/120
47
10599
Yes
200/120
40
9085
Yes
160/80
35
7949
Yes
160/80
GPM
L/h
Yes
WB2B 105
3
35
7949
105
23848
System Flow Rate
LLH Required
LLH Model
105
23848
Yes
250/150
84
19078
Yes
250/150
70
15899
Yes
200/120
60
13627
Yes
200/120
53
11924
Yes
200/120
GPM
L/h
Yes
WB2B 105
4
35
7949
140
31797
System Flow Rate
LLH Required
LLH Model
140
31797
Yes
300/200
112
25438
Yes
250/150
93
21198
Yes
250/150
80
18170
Yes
200/120
70
15899
Yes
200/120
GPM
L/h
Yes
NOTE: for multiple boiler applications when using the the Vitodens 200-W, WB2B boilers, refer to the multiple boiler low-loss distribution
manifold installation instructions.
*1 For system ∆∆∆∆t < 20°F use low-loss header sizes for ∆∆∆∆t 20°F.
*2 Low-Loss sensor - standard equipment of the Vitocontrol-S WB2B: for use in multiple boiler applications.
5369 295 v1.2
Domestic Hot Water Production
Vitodens 200-W boilers can be used in conjunction with the stand-alone DHW storage tanks offered by Viessmann.
All Viessmann DHW storage tanks sold in North America are available in “Vitosilver” finish only.
Size and select the DHW storage tank based on the forecasted DHW consumption of the building in question.
For further technical information on DHW storage tanks, see the Vitocell-V Technical Data Manuals.
For the connection of a stand-alone DHW tank, installation fittings (field supplied), an external circulating pump for DHW production (field
supplied) and a DHW temperature sensor (optional equipment, see Viessmann Price List for order information) are required.
Legend
DR
Boiler heating return for domestic
hot water production
DS
Boiler heating supply for domestic
hot water production
HR
Heating Return
HS
Heating Supply
BD
Boiler Drain
BR
Boiler Return
BS
Boiler Supply
GC
Gas Connection
PRV
Pressure Relief Valve
BF
Boiler Fill
PG
Pressure Gage (not shown)
*1
See page 38 for alternate DHW connection.
An adequately sized precharged expansion
tank must be used. See Installation
Examples for details.
5369 295 v1.2
DR
HR
HS
DS
Fig. 14
PRV
BD
GC
BF
BS
BR
DS
*1 DHW Connections
(Field Supplied)
DR
Fig. 15
IMPORTANT
Domestic Hot Water Recirculation
DHW recirculation lines increase the level of comfort and convenience of the domestic hot water supply and reduce water consumption.
These advantages directly derive from the immediate availability of domestic hot water at all draw points.
Poor insulation of the DHW recirculation line, however, can result in considerable heat loss. Viessmann therefore recommends that
effective insulation be provided and used for DHW recirculation lines of 23 ft. / 7 m in length or longer.
Legend
DCW Domestic Cold Water
DHW Domestic Hot Water
TPV
Temperature and Pressure Relief
Valve (on tank - not shown)
R
DHW Recirculation Line
RP
DHW Recirculation Pump
5369 295 v1.2
Vitocell-V stand-alone DHW storage tank
DCW
DCW
DHW
R
RP
Fig. 16
Models WB2B 19, 26, 35
The Vitodens 200-W, models WB2B 19 to 35 comes with a template, which allows you to easily mark the location of the screws for the
mounting bracket and the location of the flue gas pipe on the wall.
1. Loosen the screws at the bottom of the
boiler.
2. Remove front enclosure panel.
3. Mount boiler onto the mounting bracket
and connect boiler to the installation
fittings.
5369 295 v1.2
A
C
B
Fig. 17
A Reference point top edge Vitodens 200-W
B Mounting bracket
C Vitodens 200-W mounting template
Legend
3.
2.
2x
1.
Fig. 18
Models WB2B 45, 60, 80, 105
The Vitodens 200-W, models WB2B 45 to105 comes with a template, which allows you to easily mark the location of the screws for the
mounting bracket and the location of the flue gas pipe on the wall.
1. Loosen the screws at the bottom of the
boiler.
2. Remove front enclosure panel.
3. Mount boiler onto the mounting bracket
and connect boiler to the installation
fittings.
5369 295 v1.2
A
C
B
A Reference point top edge Vitodens 200-W
B Mounting bracket
C Vitodens 200-W mounting template
Fig. 19
Legend
2x
1.
3.
2.
Fig. 20
Condensate Connection/Neutralization Unit
19
Condensate Connection
Install the condensate drain pipe with a suitable gradient.
Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (accessory).
Pipe ventilation must take place between
the siphon trap and the neutralization unit (if
applicable).
Condensate Connection for
Vitodens 200-W, models WB2B 19, 26, 35
Condensate Connection for
Vitodens 200-W, models WB2B 45, 60
Condensate Connection for
Vitodens 200-W, models WB2B 80, 105
Condensate Drainage and Neutralization
The condensate formed both in the
condensing boiler and in the flue gas pipe
must be discharged into the public sewage
system in accordance with all applicable
local regulations. The condensate produced
by a gas-fired heating system has a pH
value between 3 and 4.
Some local codes may require the use of a
separate neutralization unit to treat the
aggressive and corrosive nature of the
condensate. With a neutralization unit
installed, all condensate from the boiler and
the flue gas pipe enters into the
neutralization unit where it is treated and
released into the public sewage system with
a safe pH value of above 6.5.
The use of neutralization granulate
(performing the neutralizing process) is
dependent on the operation of the heating
system. To determine the required refill
amount, check granulate level several times
during the first year of operation. In some
cases one granulate fill may last an entire
year.
Contact Viessmann to order a neutralization
unit for the Vitodens 200-W boiler.
See Viessmann Price List for order
information.
The condensate discharge outlet to the
drainage system connection must be clearly
visible. It must be installed with a suitable
gradient and provided with a stench trap.
If the condensate outlet of the Vitodens
200-W boiler is lower than the drain, a
condensate pump must be used.
Only corrosion-resistant materials must be
used for condensate drainage purposes (e.g.
braided hose). Do not use galvanized
materials or materials containing copper for
piping, couplings etc.
The condensate drain must have a trap to
prevent flue gas leakage.
Please note that other requirements might
apply depending on local regulations and/or
project-specific details.
It is advisable to contact your local
waterworks office (authority responsible for
waste water regulations) well before
commencing with the installation of the
neutralization unit in order to establish
details of local regulations that apply.
The following table shows the concentration
of (effluent) substances (e.g. heavy metals)
contained in the waste water from the
Vitodens 200-W condensing boiler.
Table 12.
Condensate
(effluent)
substances
Values measured
in mg/L
(effluent)
substances
Vitodens 200-W
Lead
Cadmium
Chromium
Copper
Nickel
Zinc
Tin
< 0.01
< 0.005
< 0.01
< 0.01
< 0.01
< 0.05
< 0.05
5369 295 v1.2
IMPORTANT
Fig. 21
Fig. 22
Fig. 23
Venting Options / Electrical Connection / Boiler Control
Fig. 26
4
+
?
OK
0
1
2
3
0
+
RESET
s
?F
A
140
M o
Boiler temp.
20
Venting Options
For an overview of venting options refer to the appendix starting on page 42. For detailed information refer to the Installation Instructions
for the Vitodens 200-W, WB2B Venting System.
Electrical Connection
For an overview of the required wiring refer to pages 39 (for WB2B 19 to 60) and 40 (for WB2B 80 and 105).
Power Supply
The Vitodens 200-W is shipped with a
Power / Pump Module. The module requires
a 120 VAC power supply from a wall
receptacle. The module contains a 120/230
VAC step-up transformer to power the
Vitodens 200-W with 230 VAC. Refer to
the Installation Instructions shipped with the
module for wiring details, or reference the
“Overview of Electrical Connections” on
pages 39 and 40 of this manual.
Power Supply Connection of Accessories
The power supply connection of accessories
can be made directly at the boiler control.
The connection is activated and deactivated
with the system on/off switch.
The mixing valve accessory kit and the
Vitosolic control (if used) will require a
separate 120 VAC power supply from the
wall receptacle.
Wire cabling required for:
outdoor temperature sensor
Vitotronic 200-H, HK1M mixing valve
control
accessory kit for heating circuit with
mixing valve
Vitotrol 200 remote control
Vitotrol 300 remote control
remote switching of operating mode
remote disable
alarm output
On-Board Vitotronic 200, HO1 Outdoor Reset Control
The on-board Vitodens menu-driven Vitotronic 200, HO1 control provides the following:
5369 295 v1.2
Vent Connection, models WB2B 19, 26, 35
(with optional air intake openings on sides)
Vent Connection, models WB2B 45, 60, 80,105
Fig. 24
Fig. 25
Design and Functions
Modular Structure
The control unit contains:
System on/off switch, override/emission
test switch, fixed high limit, adjustable high
limit, digital display, micro-computer,
adjustment options for switching times, for
temperatures during normal and reduced
operation, domestic hot water temperature,
adjustment options for heating curves,
temperature scanning options, built-in
diagnostic system and fuses, reset button,
analogue pressure display.
Programming Unit
Illuminated display with plain text support
Adjustment and display of temperatures
and codes
All settings, main codings and fault
messages shown in plain text
Holiday program
Party button for switching to ”normal
operation” whenever required
Energy savings button for lowering the
desired room temperature by approx.
3.6°F / 2°C in normal operation
Rotary selector for the temperature in
standard mode
Keys:
- Program selection
- Holiday program
- Party and economy mode
- Temperature for reduced mode
- DHW temperature
- Emissions test function
- Time/date
Boiler-Specific Functions
The control unit adjusts the boiler water
temperature (= supply temperature of a
direct-connected heating circuit and/or a
heating circuit with mixing valve in conjunction
with the accessory kit for a heating circuit
with mixing valve) automatically and on a
continuous basis to individual outdoor
temperatures. The control has a DHW
temperature controller with DHW priority
switching (heating circuit pump off).
Functions
Outdoor reset control of boiler water
and/or supply temperature
Electronic maximum temperature limit
Demand-dependent heating circuit pump
and burner OFF control
Anti-seizing pump protection
Maintenance display
Heating system frost protection
Integral diagnostic system
DHW temperature control with priority
control
Auxiliary function for DHW heating
(short-term heating to a higher
temperature, gas fired central heating
boiler)
Adjusting switching times for the DHW
recirculation pump
0-10 V external signal input
Boiler pump contol output
Alarm output
Heating circuit pump control output
DHW pump control output
DHW recirculation pump control output
Control Characteristics
PI characteristics with modulating output.
Time Switch
Digital time switch.
Individual and 7-day program
Automatic daylight savings time
changeover
Automatic function for DHW heating and
DHW recirculation pump
Time, day and standard switching times
for space heating, DHW heating and the
DHW circulation pump are factory-set
Switching times are individually
programmable, i.e. up to four switching
periods per day
Shortest switching interval: 10 minutes
Power backup: 14 days.
Setting the Heating Programs
The heating system frost protection (see
frost protection function) applies to all
heating programs.
You can select the following heating
programs wiyh the program keys:
Heating and DHW
DHW only
Standby mode
External heating program changeover.
Summer Operation
Heating program “w“
The burner is only activated upon a call for
domestic hot water from the DHW storage
tank (controlled by DHW tank temperature
sensor).
Frost protection
The frost protection function will be
started when the ouside temperature
drops below approx. 34°F / +1°C.
With the frost protection function, the
heating circuit pump will be switched ON
and the boiler water is maintained at a
lower temperature of approx. 68°F /
20° C.
The DHW tank will be heated to approx.
68°F / +20°C.
The frost protection function will be
stopped when the outside temperature
rises above approx. 37°F / +3°C (default
settings).
Technical Data
Rated supply voltage:
120 VAC
Rated frequency:
60 Hz
Rated current:
12 A
Max. ambient
temperature
at operation:
32 to 104ºF
0 to 40ºC
Installation in living
spaces or boiler
rooms (standard
ambient
conditions)
when storing or
transporting:
–4 to +158ºF
–20 to +70ºC
Max. operating temp.
setting (space heating):
Models WB2B 19-60
165ºF / 74ºC
Models WB2B 80-105
176ºF / 80ºC
DHW production:
Models WB2B 19-60
165ºF / 74ºC
Models WB2B 80-105
176ºF / 80ºC
Setting fixed
high limit:
210ºF / 99ºC
(not adjustable)
Adjustment range
of DHW tank set-point
temperature:
50 to 154ºF
10 to 68ºC
Adjustment range
heating curves
Heating curve
slope
0.2 to 3.5
Heating curve
shift:
–12 to +33ºC
–13 to 40 K
5369 295 v1.2
Heating Curve Adjustment (slope and shift)
The control unit regulates the boiler water
temperature (= supply temperature of
heating circuit without mixing valve) and the
supply temperature of the heating circuit
with mixing valve (in conjunction with the
accessory kit for a heating circuit with
mixing valve) according to the outdoor
temperature. The boiler water temperature
is automatically raised by 0 to 72 F / 0 to
40 K higher than the currently required set
supply termperature (in the factory default
setting the differential temperature is
14.4 F / 8 K). See Start-up/Service
Instructions for coding address “9F” in
coding level 2.
The supply temperature that is required to
achieve a given room temperature depends
on the heating system and the thermal
insulation of the building that is being
heated.
The adjustment of the two heating curves is
used to match the boiler water temperature
and the supply temperature to these
conditions. The boiler water temperature is
limited upwards by the fixed high limit and
the temperature set for the electronic high
limit.
The supply temperature cannot rise above
the boiler water temperature.
Legend
Low temperature heating system, e.g.
radiant floor heating
Medium temperature heating system,
e.g. cast iron radiation, staple-up
radiant floor heating
High temperature heating system,
e.g. fintube radiation, fan coils
Boiler Temperature Sensor
The boiler temperature sensor is connected
at the control unit for weather-responsive
operation and is built into the boiler.
Max. ambient temperature
at operation:
32 to 266ºF
0 to 130ºC
when storing or
transporting:
– 4 to+158ºF
–20 to +70ºC
DHW Tank Temperature Sensor
Part No. 7179 114
Supplied with:
Cable length approx. 13 ft. / 3.75 m,
ready to plug in
All pipe connections are field supplied.
Specification
Max. ambient temperature
at operation:
32 to 194ºF
0 to
90ºC
when storing or transporting:
– 4 to+158ºF
–20 to+ 70ºC
Outdoor Temperature Sensor
Sensor location:
North or northwest wall of building
6.6 to 8.2 ft. / 2 to 2.5 m above ground
or in case of a multi-storey building
approx. halfway up the second floor
Electrical connection:
2-wire cable, max. cable length 115 ft. /
35 m with a wire size of min. AWG 16
copper
Cable to the outdoor sensor must not be
laid near line voltage wiring
(120/240 V)
Max. ambient temperature at
operation, when storing
or transporting:
–40 to+158ºF
–40 to +70ºC
5369 295 v1.2
0,2
2,4
2,6
2,8
3,0
3,2
3,4
90
80
70
60
50
40
30
0
-5
-10
-15
-20
5
10
2,0
2,2
0,4
0,6
0,8
1,0
1,2
1,4
-30
-25
1,8
1,6
Outdoor temperature
Boiler water or
flow temperature
Room -
set-point
temperature
194
176
158
140
122
104
86
ºF / ºC
ºC
ºF
50
41
32
23
14
5
-4
-13
-22
95
35
86
30
77
25
68
20
60
15
50
10
41
5
ºF
ºC
Fig. 27
A
C
B
Fig. 28 (dimensions in mm)
Vitotronic Control Accessories
Mixing Valve Actuator Accessory Kit,
Part No. 7133 392
The mixing valve actuator is mounted
directly on the Viessmann ¾ to 2½“ mixing
valve.
The mixing valve actuator is a motor-driven
control unit. The rotational direction is
reversible.
The mixing valve actuator comes with a
plug-in connector for a heating circuit pump,
supply temperature sensor (strap-on sensor
with 19.7 ft. / 6 m connecting cable),
power supply connecting cable (10 ft. / 3 m)
and a connecting cable (10 ft. / 3 m) for the
KM-BUS Expansion Module.
Rated voltage:
120 VAC
Rated frequency:
60 Hz
Rated current:
4 (2) A
Power consumption:
4 W
Max. ambient temperature
at operation:
32 to 104ºF
0 to
40ºC
when storing
or transporting:
–4 to +149ºF
–20 to
+65ºC
Relay output for
heating circuit pump:
4(2) A, 120 VAC
Actuator
torque:
3 Nm
Time of 90 º:
2 minutes
Supply Temperature Sensor
(strap-on sensor, included with mixing
valve actuator accessory kit),
Part No. 7133 895
Installed with a strapping band.
Cable length 19.7 ft. / 6 m, ready to plug in.
Max. ambient temperature
at operation:
32 to 212ºF
–0 to 100ºC
when storing
or transporting:
–4 to +149ºF
–20 to +70ºC
LON Communication Module
Part No. 7179 113
Electronic PCB for data exchange with the
Vitotronic 200-H, Vitocom 200 and for
connecting to a higher level building
management system.
LON Connecting Cable
(for data exchange between control units)
Cable length 23 ft / 7m, fully wired
LON Terminal End Resistor
Part No. 7143 497
To terminate the LON BUS at the first and
the last control unit.
KM BUS Expansion Module
Part No. 7133 393
To connect 2 to 9 devices (mixing valve
actuator, Vitotrol, input module, etc.) to the
single KM BUS connection of the boiler.
Specification
Lead lenght
10 ft / 3.0 m, fully wired
Permissable ambient
temperature
- during operation 32 to 104°F
0 to 40°C
- during storage and
transport
- 4 to+149°F
-20 to +65°C
Immersion temperature sensor
Part No. 7173 488
To capture the low loss temperature
Specification
Lead length
12 ft / 3.75 m,
fully wired
Permissable ambient
temperature
- during operation 32 to 194°F
0 to 90°C
- during storage and
transport
- 4 to+158°F
-20 to +70°C
5369 295 v1.2
Fig. 29
(dimensions in mm)
Fig. 30
(dimensions in mm)
Fig. 31
Fig. 32
(dimensions in mm)
Vitotronic Control Accessories
24
Vitotrol 200
Part No. 7450 017
KM BUS subscriber
The Vitotrol 200 remote control regulates
the heating program for one heating circuit
and the required set room temperature in
standard mode, from any room in the house.
The Vitotrol 200 is equipped with backlit
heating program selection keys as well as a
party and economy key.
The fault display shows faults on the
control unit.
WS function:
Installation anywhere in the building.
RS function:
Installation in the main living room on an
internal wall opposite radiators. Never install
inside shelf units, recesses, immediately by
a door or heat source (e.g. direct sunlight,
fireplace, TV set, etc.).
The integral room tempearutre sensor
captures the actual room temperature and
effects any necessary corrections of the
supply temperature as well as a rapid
heat-up at the start of the heating operation
(if appropriately programmed).
Connection:
2-core lead, length max. 164 ft / 50 m (even
if connecting several remote control units)
Never route this lead immediately next to
230/400 V cables
LV plug part of the standard delivery
Specification
Power supply via KM BUS
Power consumption
0.2 W
Protection class
III
Max. ambient temperature
at operation:
32 to 104ºF–
0 to
40ºC
when storing
or transporting:
–4 to+149ºF
–20 to +65 ºC
Set room temp. range
50 to
86ºF
10 to
30ºC
adjustable from
37 to
74ºF
3 to
23ºC or
63 to
99ºF
17 to
37ºC
The set room temperature for reduced mode
is adjusted at the control unit.
Vitotrol 300
Part No. 7248 907
KM BUS subscriber
The Vitotrol 300 remote control regulates
the required set room temperature for one
heating circuit in standard and reduced
mode, the heating program and the
switching times for central heating, DHW
heating and the DHW circulation pump.
The Vitotrol 300 provides a backlit display
as well as backlit heating program keys, a
party and economy key, automatic
summer/winter time changeover, keys for
holiday program, day and time.
WS function:
Installation at any point in the building.
RS function:
Installation in the main living room on an
internal wall opposite radiators. Never install
inside shelf units, niches, immediately by a
door or heat source (e.g. direct sunlight,
fireplace, TV set, etc.)
The integral room temperature sensor
captures the actual room tempeture and
affects any necessary correction of the
supply temperature as well as a rapid
heat-up at the start of the heating operation
(if suitable encoded).
Connection:
2-core lead, length max. 164 ft / 50 m (even
if connecting several remote control units)
Never route this lead immediately next to
230/400 V cables
LV plug part of the standard delivery
Specification
Power supply via KM BUS
Power consumption
0.5 W
Protection class
III
Max. ambient temperature
at operation:
32 to 104ºF–
0 to
40ºC
when storing
or transporting:
–4 to+149ºF
–20 to +65ºC
Set room temp. range
for standard mode
50 to 86ºF
10 to30ºC
adjustable from
37 to 74ºF
3 to 23ºC or
63 to 99ºF
17 to 37ºC
for reduced mode
37 to 99ºF
3 to 37ºC
Room Temperature Sensor,
Part No. 7133 379
Separate room temperature sensor as
supplement to the Vitotrol 200 and 300; to
be used if the the Vitotrol 200 or 300
cannot be installed inside the main living
room or in a suitable position where the unit
can capture and adjust the temperature.
Installation in the main living room on an
internal wall opposite radiators. Never install
inside shelf units, recesses, immediately by
a door or heat source (e.g. direct sunlight,
fireplace, TV set, etc.).
Connect the room temperature sensor to the
Vitotrol 200 or 300.
Electrical connection:
2-wire cable with a wire size of min. AWG
18 copper
The cable length between the control unit,
remote control unit and room temperature
sensor must not exceed 98 ft./30 m
Max. ambient temperature
at operation:
32 to 104ºF–
0 to
40ºC
when storing
or transporting:
–4 to+149ºF
–20 to +65ºC
5369 295 v1.2
Fig. 33
(dimensions in mm)
Fig. 34
(dimensions in mm)
Fig. 35
(dimensions in mm)
Accessories for Vitodens 200-W
Neutralization Unit for Single-Boiler
Applications
with neutralizing granulate
for models WB2B 19, 26, 35
Part No. 7134 231
for models WB2B 45, 60
Part No. 7134 232
for models WB2B 80, 105
Part No. 7264 769
Neutralization Pellets
for models WB2B 19, 26, 35, 45, 60
Part No. 9524 670
2 x 1.3 kg for refill or replacement purposes
for models WB2B 80, 105
Part No. 9521 702
8 kg for refill or replacement purposes
Fuel Conversion Label Kit (NG>LPG)
Part No. 7428 427
(included in boiler technical literature set)
The Vitodens 200-W, WB2B boiler comes
factory set for operation with natural gas.
All WB2B models can be field converted to
operate with liquid propane gas (as well as
back to natural gas as required). The kit
includes instructions and labels for field
conversion.
Low-Loss Header
–Type 80/50
Part No. 7134 230
(max. flow rate 17.6 GPM / 4 m3/h)
–Type 120/80
Part No. 7134 244
(max. flow rate 35.2 GPM / 8 m3/h)
–Type 160/80
Part No. 7134 293*1
(max. flow rate 44 GPM / 10 m3/h )
–Type 200/120
Part No. 7134 294*1
(max. flow rate 80 GPM / 18 m3/h )
When used in conjunction with the Vitodens
200-W boiler, the low-loss header acts as
hydraulic break, decoupling boiler and
system circuits from each other.
It is recommended to use the low-loss
header in applications in which the total
system flow rate exceeds the maximum (or
minimum) boiler flow rate.
For maximum boiler flow rates, see pages
10 and 11 in this manual.
Viessmann strongly recommends the use of
a low-loss header in cases where the
system head and flow rates are unknown.
*1Floor-mounted version (typically used for
multiple-boiler installations).
5369 295 v1.2
DN 40
Ø 145
310
Fig. 36
(dimensions in mm)
DN 40
Ø 145
400
Fig. 37
(dimensions in mm)
400
476
50
185
90
300
Fig. 38
(dimensions in mm)
Fig. 39
Accessories for Vitodens 200-W (continued)
Low-Loss Header (continued)
The temperature sensor connection [TS]
typically located at the top of the low-loss
header ensures low return temperatures to
the Vitodens 200-W boiler at all times,
increasing operational efficiency.
In addition, the low-loss header helps
eliminate air and debris [D] from the heating
system.
See figures on the right for an illustration of
the principle of operation.
The low-loss header is available in the
following sizes. Select the size based on the
maximum system flow rate of your
application.
Table 13.
Model No.
Max. system flow rate
Type 80/50
17.6 GPM / 4 m3/h
Type 120/80
35.2 GPM / 8 m3/h
Type 160/80*1
44 GPM / 10 m3/h
Type 200/120*1
80 GPM / 18 m3/h
*1Floor-mounted version (typically used for
multiple-boiler installations).
Legend
AB
Air Bleed
BR
Boiler Return
BS
Boiler Supply
BY
Bypass (with laminar flow)
D
Debris and/or air
DV
Drain Valve
SC
Sensor Cable
SR
System Return
SS
System Supply
TS
Viessmann Temperature Sensor
SW Sensor Well
Use only a Viessmann supplied temperature
sensor. Do not use any other
manufacturer’s temperature sensor.
Legend
T1
Boiler supply temperature
T2
Boiler return temperature
T3
System supply temperature
T4
System return temperature
Vprimary
Boiler circuit flow rate
Vsecondary
Heating circuit flow rate
Vbypass
Bypass flow rate
Qprimary
Heat supplied by boiler
Qsecondary
Heat consumed by system
Vprimary < Vsecondary
T1 > T3
T2 = T4
Qprimary = Qsecondary
T1 ± 167°F / 75°C
Vsecondary=Vprimary+Vbypass
When installing a low-loss header, the
system mixed supply temperature (T3) must
be calculated as follows:
T3=
T1 × Vprimary+T4 Vbypass
Vsecondary
5369 295 v1.2
DV
BS
SS
SR
BR
TS
BY
AB
D
Low-loss header design
(Type 80/50 or 120/80)
SC
SW
Fig. 40
T1
T2
Vprimary
Vsecondary
T3
T4
Principle of Operation
T4
Vbypass
Fig. 41
IMPORTANT
IMPORTANT
Boiler Standard Equipment / Combustion Management System
27
Standard Equipment
The Vitodens 200-W gas-fired condensing
boiler with Inox-Radial heat exchanger,
modulating MatriX cylinder burner for liquid
propane gas and natural gas (available on all
models), comes standard with:
pressure gage
installation fittings with 30 psig pressure
relief valve and air vent (no air vent for
models WB2B 80 and 105)
boiler control unit with outdoor
temperature sensor, power/pump module
– The boiler comes prewired and fully piped
internally for field connections and prewired.
– Venting material (coaxial) is to be supplied
by Viessmann only. Side wall vent
installations must include Viessmann
protective screen!
– Enclosure finish:
black steel, powder-coated white
– The Vitodens 200-W comes ready for use
with natural gas and can be fuel
converted to liquid propane gas in the
field.
- Power/Pump module
Wall mounting componentry
The following wall mounting components
are supplied with the Vitodens 200-W
boiler:
Mounting bracket
Mounting bolts
Installation fittings
Screws for mounting bracket on
– wood studs (2” x 4”)
– metal studs
– brick/concrete wall
Lambda Pro Combustion Management System
The combustion management system
utilizes the physical correlation between the
level of the ionization current and the air
factor λ. For all gas qualities, the maximum
ionization current results with air factor 1.
The ionization signal is evaluated by the
combustion management system, and the
air factor is adjusted to between λ=1.24
and 1.44. This range provides for an
optimum combustion quality. Thereafter, the
electronic gas valve regulates the required
gas volume based on the prevailing gas
quality.
To check the combustion quality, the CO2
content or the O2 content of the flue gas is
measured. The actual values enable the
prevailing air factor to be determined. The
relationship between the CO2 or O2 content
and air factor λ is illustrated in the table
below.
To achieve an optimum combustion control,
the system regularly performs an automatic
self-calibration; also after a power failure
(shutdown). For this, the combustion is
briefly regulated to max. ionization current
(equals air factor λ=1). The automatic
calibration is performed shortly after the
burner starts and lasts approx. 5 s. During
the calibration, higher than normal CO
emissions may occur briefly.
The combustion management system can
also be calibrated manually, e.g. after
maintenance or service work (coding
address “85”, see Start-up/Service
Instructions).
Table 14. Air factor λ - CO2/O2 content
Air factor λ
O2 content (%)
CO2 content (%) for natural gas
CO2 content (%) for liquid propane gas
1.24
4.4
9.2
10.9
1.27
4.9
9.0
10.6
1.30
5.3
8.7
10.3
1.34
5.7
8.5
10.0
1.37
6.1
8.3
9.8
1.40
6.5
8.1
9.6
1.44
6.9
7.8
9.3
The Vitodens 200-W, WB2B boilers come equipped with Lambda Pro, the industry’s first intelligent combustion management system. The
boiler adjusts automatically to any gas type and quality without the need for a fuel conversion kit.
5369 295 v1.2
Please note that in the following piping layout examples all pumps are field supplied.
The examples on the following pages depict
possible piping layouts of the Vitodens
200-W boiler equipped with Viessmann
System Technology.
For boiler and tank combinations, please
install only feasible combinations listed in
the Viessmann Price List.
Please note that the following examples are
simplified conceptual drawings only!
Piping and necessary componentry must be
field verified.
A low water cut-off (LWCO) must be
installed where required by local codes.
Proper installation and functionality in the
field is the responsibility of the heating
contractor.
DHW supply and return piping between
boiler DHW connections and the Viessmann
DHW tank connections, shall be a minimum
of 1” nominal pipe diameter (for models
WB2B 19 to 35) or 1¼” (for models WB2B
45 to105) DHW connection outlet sizes
provided on the boiler and the DHW tank).
This will ensure the residual head of the
field supplied pump is fully utilized to
overcome the resistance of the DHW heat
exchanger coil and to provide sufficient
water flow to the boiler heat exchanger.
In non-Viessmann DHW tank applications,
perform, in addition to the above, accurate
calculations for DHW tank coil pressure drop
versus boiler pump (field supplied) residual
head to ensure sufficient water flow to the
boiler heat exchanger. Failure to heed the
above instructions may cause boiler
short-cycling and inadequate DHW supply.
5369 295 v1.2
IMPORTANT
If a DHW storage tank other than a
Viessmann Vitocell 100 or 300 tank is
used, the installer must verify proper
operation of the Viessmann DHW tank
temperature sensor with the original
manufacturer of the tank. Viessmann
strongly recommends the installation of a
temperature tempering valve in the DHW
supply line.
WARNING
IMPORTANT
System Layout 1
Vitodens 200-W, WB2B with a direct-connected heating circuit
Legend
AV Air vent (models WB2B 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature sensor
Remote control Vitotrol 300 (optional)
Heating circuit
Heating circuit pump sÖ
DHW circulating pump sA
DHW storage tank
DHW tank temperature sensor
I
Expansion tank
J
Flow check valve
DHW recirculation pump sK
Power/Pump module
M
Optional purge tee (field supplied)
Installation of ...
radiator heating circuit (high-temp. circuit)
DHW production
... with the following flow conditions:
The flow rate of the heating circuit is less
than the maximum possible water flow rate
of the Vitodens 200-W WB2B boiler (see
page 10 for maximum water flow rate of
boiler).
The use of a low-loss header is strongly
recommended if the maximum water flow
rate in the application concerned exceeds
the values shown in the applicable table on
page 11, or if the system flow rates are
unknown.
The low-loss header is available as
accessory part.
See following pages for installation
examples with a low-loss header.
DHW circulating pump
must pump into
the Vitodens 200-W boiler (as illustrated).
5369 295 v1.2
5
1
PRV
TPV
A
B
C
K
AV
M
D
E
F
G
H
L
J
Fig. 42
I
IMPORTANT
System Layout 2
Vitodens 200-W, WB2B with a direct-connected heating circuit and low-loss header
Legend
AV Air vent (models WB2B 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature sensor
Remote control Vitotrol 300 (optional)
Heating circuit
Boiler pump sÖ
DHW circulating pump sA
DHW storage tank
DHW tank temperature sensor
I
Expansion tank
J
Flow check valve
DHW recirculation pump sK
Power/Pump Module
M
Low-loss header
N
Optional purge tee (field supplied)
O
Viessmann temperature sensor for
low-loss header
P
Heating circuit pump 20A
Installation of ...
radiator heating circuit (high-temp. circuit)
DHW production
... with the following flow conditions:
The flow rate of the heating circuit is
greater than the maximum possible water
flow rate of the Vitodens 200-W WB2B
boiler (see page 10 for maximum water flow
rate of boiler).
The use of a low-loss header is strongly
recommended if the maximum water flow
rate in the application concerned exceeds
the values shown on page 11, or if the
system flow rates are unknown.
The low-loss header is available as
accessory part.
Please note location of expansion tank I
and flow check valve J .
DHW circulating pump
must pump into
the Vitodens 200-W WB2B boiler (as
illustrated).
DHW circulating pump
must pump into
the Vitodens 200 boiler (as illustrated).
5369 295 v1.2
1
PRV
TPV
5
A
B
C
K
M
D
E
F
G
H
L
N
O
AV
5
J
I
P
Fig. 43
IMPORTANT
IMPORTANT
IMPORTANT
System Layout 3
Vitodens 200-W, WB2B with...
– DHW storage tank
– one heating circuit with mixing valve and system separation
Legend
AV
Air vent (WB2B models 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature
Remote control Vitotrol 300 (optional)
Underfloor heating circuit
Mixing valve temperature sensor
F1
Heating circuit pump
F2
Heating circuit pump
located upstream of heat exchanger
(see IMPORTANT note to the right)
Plate heat exchanger for system
separation
Accessory kit for heating circuit with
mixing valve
I
DHW circulating pump sA
J
DHW storage tank
DHW tank temperature sensor
Expansion tank
M DHW recirculation pump sK
N Power/Pump module
O Optional purge tee (field supplied)
P Flow check valve
Installation of ...
underfloor heating circuit with 3-way
mixing valve and system separation
(low-temp. circuit)
DHW production
... with the following flow conditions:
The flow rate of the heating circuit is less
than the maximum possible water flow rate
of the Vitodens 200-W WB2B boiler.
See page 10 for maximum water flow rate
of the Vitodens 200-W WB2B boilers.
The use of a low-loss header is
recommended if the system water flow rate
is unknown.
The low-loss header is available as
accessory part.
See following pages for installation
examples with a low-loss header.
System separation is required of underfloor
heating systems employing non-oxygen
diffusion barrier tubing.
All components on the secondary side of
the heat exchanger must be made of
corrosion-resistant materials.
DHW circulating pump I
must pump into
the Vitodens 200-W WB2B boiler (as
illustrated).
Sizing of field-supplied pump F2 is critical
for proper boiler operation in this system
layout. See page 10 for the supply head
pressure drop of the boiler. An undersized
pump may cause short-cycling and/or
improper operation of the boiler. Viessmann
STRONGLY recommends using a low-loss
header and a boiler pump in this system
layout.
5369 295 v1.2
TPV
AV
Y
I
F1
F2
5
1
Y
Y
PRV
PRV
J
O
2
M
N
P
Fig. 44
IMPORTANT
IMPORTANT
IMPORTANT
System Layout 4
Vitodens 200-W, WB2B with...
– DHW storage tank
– one direct-connected heating circuit
– one heating circuit with a mixing valve
Legend
AV Air vent (WB2B models 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature sensor
Remote control Vitotrol 300 (optional)
Under floor heating circuit
Radiator heating circuit
Heating circuit pump
Mixing valve temperature sensor
Accessory kit for heating circuit with
mixing valve
I
Domestic hot water storage tank
J
DHW tank temperature sensor
Expansion tank
Optional purge tee (field supplied)
DHW supply and return piping
DHW recirculation pump sK
O
Power/Pump module
P
Boiler pump sÖ
Q DHW circulating pump sA
R Flow check valve
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way
mixing valve (low-temp. circuit)
DHW production
... with the following flow conditions:
1. The water flow rate (output) of the
radiator heating circuit is at least 30%
greater than that of the under floor heating
circuit.
2. The total flow rate of the two heating
circuits is less than the maximum possible
water flow rate of the Vitodens 200-W
WB2B boiler (see page 10 for max. water
flow rate).
The use of a low-loss header is strongly
recommended if the maximum water flow
rate in the application concerned exceeds
the values shown on page 11, or if the
system flow rates are unknown.
The low-loss header is available as
accessory part.
See following pages for additional
installation examples with a low-loss
header.
The 3-way mixing valve, built-in to achieve
the low-temperature level of the under floor
heating circuit, is controlled by an accessory
kit for a heating circuit with mixing valve.
DHW circulating pump Q must pump into
the Vitodens 200-W WB2B boiler (as
illustrated).
5369 295 v1.2
PRV
TPV
A
B
C
K
M
D
E
F
H
L
O
AV
G
I
N
1
V
2
5
R
Q
J
P
M
Fig. 45
IMPORTANT
System Layout 5
Vitodens 200-W, WB2B with...
– DHW storage tank
– one heating circuit with mixing valve
– one heating circuit without mixing valve and low-loss header
Legend
AV Air vent (WB2B models 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature sensor
Remote control Vitotrol 300 (optional)
Under floor heating circuit
Radiator heating circuit
Heating circuit pump
20A
F1
Heating circuit pump
Mixing valve temperature sensor
Kit for heating circuit with mixing valve
I
Domestic hot water storage tank
J
DHW tank temperature sensor
Expansion tank
Optional purge tee (field supplied)
DHW supply and return piping
DHW circulating pump sK
Q
DHW circulating pump sA
R
Low-loss header
S
Viessmann temperature sensor for
low-loss header
T
Flow check valve
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way
mixing valve (low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating
circuits is greater than the maximum
possible water flow rate of the Vitodens
200-W WB2B boiler (see page 11 for
maximum water flow rate of boiler).
The use of a low-loss header is strongly
recommended. The low-loss header is
available as accessory part.
The 3-way mixing valve, built-in to achieve
the low-temperature level of the under floor
heating circuit, is controlled by an accessory
kit for a heating circuit with mixing valve.
Please note location of expansion tank
and flow check valve T.
DHW circulating pump Q must pump into
the Vitodens 200-W WB2B boiler (as
illustrated).
5369 295 v1.2
PRV
TPV
A
B
C
K
M
D
E
F
H
L
N
O
T
AV
5
1
2
5
G
I
R
Q
M
P
S
J
F1
Fig. 46
IMPORTANT
IMPORTANT
System Layout 6
Vitodens 200-W, WB2B with...
– DHW storage tank
– two heating circuits with a mixing valve and low-loss header
Legend
AV Air vent (WB2B models 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature sensor
Remote control Vitotrol 300 (optional)
Under floor heating circuit
Heating circuit pumps
Mixing valve temperature sensor
Accessory kit for heating circuit with
mixing valve
Vitotronic 200-H, HK1M with LON
communication module*1
I
DHW storage tank
J
DHW tank temperature sensor
Expansion tank
Optional purge tee (field supplied) for
easier air removal
Low-loss header
Viessmann temperature sensor for
low-loss header
O
DHW supply and return piping
P
DHW circulating pump sK
Q
Power/Pump Module
R
Boiler pump sÖ
S
DHW circulating pump sA
T
Flow check valve
Installation of different heating circuits...
two heating circuits with 3-way mixing
valve (low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating
circuits is greater than the maximum
possible water flow rate of the Vitodens
200-W WB2B boiler (see page 11 for
maximum water flow rate of boiler).
The use of a low-loss header is strongly
recommended. The low-loss header is
available as accessory part.
The 3-way mixing valve, built-in to achieve
the low-temperature level of the under floor
heating circuit, is controlled by an accessory
kit for a heating circuit with mixing valve
. The second under floor heating circuit is
supplied by a field supplied circulation
controlled by an accessory kit or a
Vitotronic 200-H, HK1M mixing valve
control
. If more than two heating circuits
with mixing valves are to be connected,
they can be controlled by a Vitocontrol
multi-boiler control. Contact your local
Viessmann Technical Sales Representative
for details.
*1Requires...
- LON communication module 200-H HK1M
- Boiler LON communication module
- LON cable
- End resistors
Please note location of expansion tank
and flow check valve T.
DHW circulating pump S must pump into
the Vitodens 200-W WB2B boiler (as
illustrated).
5369 295 v1.2
1
TPV
2
5
2
PRV
A
B
C
D
E
F
G
H
I
K
L
M
N
O
S
AV
R
T
D
E
F
P
Q
5
O
J
Fig. 47
IMPORTANT
IMPORTANT
System Layout 7
Vitodens 200-W, WB2B with...
– direct-connected heating circuit
– one heating circuit with system separation
Legend
AV Air vent (WB2B models 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature sensor
Remote control Vitotrol 300 (optional)
Under floor heating circuit
Heating circuit pump
Plate heat exchanger for system
separation
Heating circuit pump
Mixing valve temperature sensor
I
Accessory kit for heating circuit with
mixing valve
J
DHW storage tank
DHW tank temperature sensor
Expansion tanks
Optional purge tee (field supplied)
DHW supply and return piping
O
DHW recirculation pump sK
P
Boiler pump sÖ
Q
DHW circulating pump sA
R
Power/pump module
S
Flow check valve
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way
mixing valve (low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating
circuits is less than the maximum possible
water flow rate of the Vitodens 200-W
WB2B boiler (see page 11 for maximum
water flow rate of boiler).
The use of a low-loss header is strongly
recommended if the maximum water flow
rate in the application concerned exceeds
the max. boiler flow rate, or if the system
flow rates are unknown. The low-loss
header is available as accessory part.
The 3-way mixing valve, built-in to achieve
the low-temperature level of the under floor
heating circuit, is controlled by an accessory
kit for a heating circuit with mixing valve
I . The boiler pump sÖ supplies the
radiator heating circuit and the plate heat
exchanger for system separation.
The pressure drop (secondary circuit) of the
plate heat exchanger
must be less/equal
to the pressure drop of the 3-way mixing
valve. This must be taken into account
when sizing the plate heat exchanger.
DHW circulating pump Q must pump into
the Vitodens 200-W WB2B boiler (as
illustrated).
5369 295 v1.2
TPV
PRV
A
B
C
D
G
I
K
L
M
N
S
R
E
F
P
Q
5
1
V
2
O
AV
N
J
Fig. 48
IMPORTANT
IMPORTANT
System Layout 8
Vitodens 200-W, WB2B with...
– DHW storage tank
– low-loss header
– multiple heating circuits with mixing valves
When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance.
Legend
AV Air vent (WB2B models 19 to 60 only)
PRV Pressure relief valve
TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with
Vitotronic 200, HO1 outdoor reset
control
Outdoor temperature
Boiler pump sÖ
Vitocontrol or Vitotronic 200-H,
HK1S*1
Mixing valve temperature sensor
Heating circuit pumps
Accessory kit for heating circuit with
mixing valve*2
Heating circuits with mixing valves
I
Viessmann temperature sensor for
low-loss header
J
Low-loss header
DHW circulating pump sA
DHW tank temperature sensor
DHW storage tank
Expansion tank
O
DHW recirculation pump sK
P
Power/Pump module
Q
Flow check valve
*1Contact your local Sales Representative
for details.
*2Vitotronic 200-H, HK1M mixing valve
control with LON communication module
can be used instead of the accessory kit
and Vitocontrol.
Please note location of expansion tank
and flow check valve Q.
Pumps
and
must pump into the
Vitodens 200-W WB2B boiler (as
illustrated).
5369 295 v1.2
5
1
PRV
5
2
2
AV
A
B
C
D
E
E
E
F
F
F
G
G
G
H
H
H
K
L
M
N
O
P
Q
2
TPV
I
J
Fig. 49
IMPORTANT
IMPORTANT
System Layout 9
Multiple (up to four) Vitodens 200-W, models WB2B 45 to 105 with...
– multiple heating circuits with mixing valves
– low-loss header
When designing a multiple Vitodens system as shown above, please reference applicable multiple Vitodens technical documentation, and
contact your local Viessmann Sales Representative for further assistance.
This installation example depicts a
possible piping layout for multiple
Vitodens 200-W, WB2B boilers equipped
with Viessmann System Technology.
Please note that this example is based on
a simplified conceptual drawing only!
Piping and necessary componentry must
be field verified.
A low water cut-off (LWCO) must be
installed where required by local codes.
Proper installation and functionality in the
field is the responsibility of the heating
contractor.
5369 295 v1.2
Vitocontrol-S
Boiler 1
Boiler 2
Boiler 3
Boiler 4
PRV
PRV
PRV
PRV
TPV
DHW Tank
Low-Loss
Header
Common
Supply
Temperature
Sensor
5
5
M
M
Fig. 50
IMPORTANT
If a DHW storage tank other than a
Viessmann Vitocell 100 or 300 tank is
used, the installer must verify proper
operation of the Viessmann DHW tank
temperature sensor with the original
manufacturer of the tank. Viessmann
strongly recommends the installation of a
temperature tempering valve in the DHW
supply line.
WARNING
The following piping diagram reflects an alternative connection for the DHW tank only and applies to system layouts 2, 5,
6 and 8. The boiler control pump logic function must be programmed in the Start-up/Service Instructions. .
*Note:
When using a low loss header in the
system, the DHW connections can be made
downstream of the low loss header. See
Vitodens 200-W WB2B Start-up/Service
Instructions for applicable system coding
information (see coding level 2):
00: ...
A2: ...
5b: ...
5369 295 v1.2
M
5
1
2
5
PRV
TPV
Alternative
location
of the expansion tank
*
*
Fig. 51
Boiler Control Board GC130
X9.3
X9.4
X
X11
LON
KMK
9
X8
X7
1
20
40
N
L
145
144
143
50
20
21
20A
28
L G N
40
L2
N
L
N
L
N
L
EXTERNAL
DEMAND
EXTERNAL
SIGNAL
0--10 V
-- +
120VAC
M
120VAC
M
120VAC
M
M
120VAC
120VAC
RE--CIRC.
PUMP
FAULT
ALARM
OUTPUT
BOILER
PUMP
DHW
PUMP
SYSTEM
PUMP
1 2 3
1 2 3
1 2 3
L1
G
N
3
1 2
145
SAFETY DEVICE
LOW WATER CUT--OFF
120VAC
RECEPTACLE
WALL
--TYPICAL
A
P2
P1
L2
L1
SWITCH
DISCONNECT
MAIN POWER SUPPLY
120V, 60HZ, 12A
N
MAIN
L
G
3
1 2
145
3
1 2
144
3
1 2
143
50
20
21
20A
40
N
L
Vitotronic 050
HK1M
LON
120/230 Transformer
Power/Pump module
4
3
2
1
X1
LON
X2
LON
X1
KMK1KMK2
A8
Fig. 52
DHW
39
Overview of Electrical Connections, Models WB2B 19, 26, 35, 45 and 60
Legend
!
Outdoor Temperature Sensor
?
Flow Temp. Sensor/Low-Loss
Header
%
DHW Temperature Sensor
sÖ
Boiler Pump
20A System Pump
sA
DHW Pump
sK
DHW Recirculation Pump
fÖ
Power Suppl
gÖ
Fault Alarm Output
aVD External Blocking Terminals 2-3
External Demand Terminals 1-2
External Heating Program
Changeover Terminals 1-2
(Allocation of this function is set via
Coding Address 91.)
aVF External 0-10 V Signal
aVG KM BUS to Power/Pump Module /
Accessories
L
Low water cut-off (field supplied)
M
Power/Pump Module
A1
Main PCB (GC130 Ignition Module)
A6
Coding Card
A7
Connection Adaptor
A8
LON/Cascade Communication
Module(Accessory)
X
Electrical Interfaces
5369 295 v1.2
Boiler Control Board GC131
X
X11
LON
KMK
9
X7
1
20
40
N
L
145
144
143
50
20
21
20A
28
L G N
40
L2
N
L
N
L
N
L
EXTERNAL
DEMAND
EXTERNAL
SIGNAL
0--10 V
-- +
120VAC
M
120VAC
M
120VAC
M
M
120VAC
120VAC
DHW
PUMP
FAULT
ALARM
OUTPUT
BOILER
PUMP
DHW
PUMP
SYSTEM
PUMP
1 2 3
1 2 3
1 2 3
L1
G
N
3
1 2
145
SAFETY DEVICE
LOW WATER CUT--OFF
120VAC
RECEPTACLE
WALL
--TYPICAL
A
P2
P1
L2
L1
SWITCH
DISCONNECT
MAIN POWER SUPPLY
120V, 60HZ, 12A
N
MAIN
L
G
3
1 2
145
3
1 2
144
3
1 2
143
50
20
21
20A
40
N
L
Vitotronic 200--H
HK1M
LON
120/230 Transformer
Power/Pump module
X8.10
X8.11
X8
4
3
2
1
X1
LON
X2
LON
X1
KMK1KMK2
A8
RE--CIRC.
Fig. 53
40
Overview of Electrical Connections, Models WB2B 80 and 105
Legend
!
Outdoor Temperature Sensor
?
Flow Temp. Sensor/Low-Loss Header
%
DHW Temperature Sensor
sÖ
Boiler Pump
20A System Pump
sA
DHW Pump
sK
DHW Recirculation Pump
fÖ
Power Supply
gÖ
Fault Alarm Output
aVD External Blocking Terminals 2-3
External Demand Terminals 1-2
External Heating Program Changeover
Terminals 1-2 (Allocation of this
function is set via Coding Address 91.)
aVF External 0-10 V Signal
aVG KM BUS to Power/Pump Module /
Accessories
L
Low water cut-off (field supplied)
M
Power/Pump Module
A1
Main PCB (GC131 Ignition Module)
A6
Coding Card
A7
Connection Adaptor
A8
LON/Cascade Communication
Module (Accessory)
X
Electrical Interfaces
5369 295 v1.2
System Design Considerations
IN THE COMMONWEALTH OF MASSACHUSETTS...
-this product shall be installed by a licensed plumber or gas fitter.
-the flexible connector (if used) cannot exceed 36”.
-any level type shutoff used must be of tee handle type.
Boiler location
As a direct vent appliance, the Vitodens
200-W can be installed for room air
independent operation (sealed combustion)
regardless of size and ventilation method of
the room in which it is located.
The Vitodens 200-W can be installed, for
example, in the main living area of a house,
in non-ventilated utility rooms, cupboards,
closets and alcoves with no clearance
required from combustible materials, as well
as in attics with a direct outlet for the flue
gas/fresh air system. Follow all local and
national codes.
Flue gas system
Viessmann PPS (Polypropylene) concentric
flue gas/fresh air systems for room air
independent operation (sealed combustion)
and side wall venting are tested to ANSI
Z21.13 - CSA 4.9 - 2000 standards and are
certified together with the Vitodens 200-W
boiler as a constructional unit.
The Vitodens 200-W boiler may also be
vented vertically, using an AL29-4C® special
stainless steel, single-wall, room air
dependent venting system (UL listed for
category IV).
For a more detailed description of the direct
vent and single-wall vent system, please
refer to the Vitodens 200-W Venting
System Installation Instructions.
Flue gas temperature protection
Flue pipes used for the Vitodens 200-W are
suitable for max. flue gas temperatures of
up to 230°F / 110°C.
No flue gas temperature protection is
required as the maximum permissible flue
gas temperature is not exceeded in any
operating condition or in the event of
malfunctioning.
Low water cut-off
A low water cut-off may be required by
local codes. If the boiler is installed above
the radiation level, a low water cut-off
device of approved type must be installed in
all instances. An approved type low water
cut-off device must be provided by the
heating contractor. Do not install an
isolation valve between the boiler and the
low water cut-off.
System layout
The max. boiler water temperature for
space heating and DHW production is
–165°F / 74°C for models WB2B 19 to
60 or –176°F / 80°C for models WB2B 80
and105.
To minimize distribution losses,
Viessmann recommends that the heating
and domestic hot water systems be based
on a maximum boiler supply temperature
of 158°F / 70°C.
Due to the low return temperatures
required for gas condensing, no mixing
valves should be used in the heating
circuit whenever possible. If mixing valves
are required, e.g. for multi-circuit systems
or underfloor heating systems, only 3-way
mixing valves must be used.
Do not use 4-way mixing valves with
condensing boilers.
Water connections
Vitodens 200-W boilers can be used in any
fully pumped hot water heating system.
Minimum system pressure is 0.8 bar/12 psig.
Chemical corrosion protection products
Corrosion does not typically occur in sealed
heating systems which have been correctly
installed and are correctly operated.
Many manufacturers of plastic pipes
recommend the use of chemical additives.
In this case, only those commercially
available corrosion protection products
approved for boilers with domestic hot
water heating via single-wall heat
exchangers (instantaneous plate heat
exchangers or DHW tanks) must be used.
Underfloor heating systems
For underfloor heating systems Viessmann
recommends the use of plastic tubing with
an oxygen diffusion barrier in order to
prevent the diffusion of oxygen through
tubing. If plastic tubing without an oxygen
diffusion barrier is used in underfloor
heating systems, Viessmann recommends
that such systems be separated from the
boiler with a heat exchanger.
Underfloor heating systems and heating
circuits containing a very large volume of
water must be connected to the boiler via a
3-way mixing valve; please refer to the
applicable installation example in this
manual.
Oxygen diffusion barrier
underfloor tubing
The boiler warranty does not cover leaks
resulting from corrosion caused by the use
of underfloor plastic tubing without an
oxygen diffusion barrier. Such systems must
have the non-oxygen diffusion barrier tubing
separated from the boiler with a heat
exchanger. Viessmann recommends the use
of underfloor plastic tubing with an oxygen
diffusion barrier.
Water quality
Treatment for boiler feed water should be
considered in areas of known problems,
such as where a high mineral content and
hardness exist. In areas where freezing
might occur, an antifreeze may be added to
the system water to protect the system.
Please adhere to the specifications given by
the antifreeze manufacturer. Do not use
automotive silicate based antifreeze. Please
observe that an antifreeze/water mixture
may require a backflow preventer within the
automatic water feed and influence
components such as diaphragm expansion
tanks, radiation, etc. Maximum antifreeze
content is 50% for the Vitodens 200-W
boiler. Do not use antifreeze other than
specifically made for hot water heating
systems. System also may contain
components which might be negatively
affected by antifreeze. Check total system
frequently when filled with antifreeze.
Advise system operator/ultimate owner that
system is filled with a glycol mix.
The heating contractor must provide a
MSDS (Material Safety Data Sheet) for the
antifreeze used to the system
operator/ultimate owner.
Warranty
Our warranty does not cover damages
resulting from the following:
– installation or service by unqualified and
unlicensed personnel.
– attempting to perform any repair work on
the boiler other than that mentioned in the
boiler literature.
– tampering with or attempting, without
Viessmann permission, to readjust
the factory settings of the
–combination gas valve
–combustion air opening of the
burner blower
– leaks resulting from corrosion caused by
the use of underfloor plastic tubing
without an oxygen diffusion barrier.
For detailed warranty information, please
read warranty sheet supplied with product.
5369 295 v1.2
Vitodens 200-W Venting Alternatives
Venting Alternatives
Vent System Diameter
Viessmann Coaxial PPs Vent 1
Stainless Steel Vent 2
CPVC Vent 3
Type
Max. Equivalent Length (EqL)
60/100
80/125
100/150
3”
4”
2”
3”
4”
Diameter
Horizontally Vented
WB2B-19
EqL
33 / 10
43 / 13
52 / 16
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-26
EqL
33 / 10
43 / 13
52 / 16
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-35
EqL
26 / 8
36 / 11
49 / 15
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-45
EqL
33 / 10
43 / 13
98 / 30
148 / 45
98 / 30
148 / 45
ft. / m
WB2B-60
EqL
33 / 10
43 / 13
98 / 30
148 / 45
98 / 30
148 / 45
ft. / m
WB2B-80
EqL
43 / 13
131 / 40
131 / 40
ft. / m
WB2B-105
EqL
43 / 13
131 / 40
131 / 40
ft. / m
See Page(s)
44
46-49
50-53
Page
Vertically Vented
WB2B-19
EqL
30 / 9
39 / 12
52 / 16
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-26
EqL
30 / 9
39 / 12
52 / 16
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-35
EqL
23 / 7 34 / 10.5
49 / 15
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-45
EqL
33 / 10
43 / 13
98 / 30
148 / 45
98 / 30
148 / 45
ft. / m
WB2B-60
EqL
20 / 6
33 / 10
98 / 30
148 / 45
98 / 30
148 / 45
ft. / m
WB2B-80
EqL
43 / 13
131 / 40
131 / 40
ft. / m
WB2B-105
EqL
43 / 13
131 / 40
131 / 40
ft. / m
See Page(s)
45
46-49
50-53
Page
1 Sealed combustion, coaxial vent material to be supplied by Viessmann only.
2 Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
3 CPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
Always follow Viessmann venting installation instructions 5368 815.
5369 295 v1.2
Vitodens 200-W Venting Alternatives
Venting Alternatives
Vent System Diameter
Viessmann Coaxial PPs Vent 1
Stainless Steel Vent 2
CPVC Vent 3
Type
Max. Equivalent Length (EqL)
60/100
80/125
100/150
3”
4”
2”
3”
4”
Diameter
Horizontal Intake /
Vertically Vented
WB2B-19
EqL
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-26
EqL
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-35
EqL
148 / 45
180 / 55
115 / 35
148 / 45
180 / 55
ft. / m
WB2B-45
EqL
98 / 30
148 / 45
98 / 30
148 / 45
ft. / m
WB2B-60
EqL
98 / 30
148 / 45
98 / 30
148 / 45
ft. / m
WB2B-80
EqL
131 / 40
131 / 40
ft. / m
WB2B-105
EqL
131 / 40
131 / 40
ft. / m
See Page(s)
54-55
54-55
Page
Select vent material based on vent configuration, preferred material, and necessary
maximum equivalent length.
Always follow Viessmann venting installation instructions.
- Do not common vent Vitodens 200-W with any other appliance.
- Layouts on the following pages are for illustrative purposes only.
- Do not use Price List for installation purposes. This is not a design tool.
1 Sealed combustion, coaxial vent material to be supplied by Viessmann only.
2 Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
3 CPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
5369 295 v1.2
Coaxial PPs Vent System
Vent System 1
Vent System Diameter
Vent System
60/100
80/125
100/150
Diameter
Horizontally Vented
Maximum Equivalent
WB2B
Length (EqL)
-19/-26
33 / 10
-19/-26
43 / 13
-19/-26
52 / 16
ft. / m
WB2B
-35
26 / 8
-35
36 / 11
-35
49 / 15
ft. / m
WB2B
-45/-60
33 / 10
-45-105
43 / 13
ft. / m
Room Air
Independent Operation
Important!
As a starting point, please
pay attention to boiler vent
connection size
Basic Horizontal Vent Kit
Venting pieces can be ordered
individually, or as a convenient
kit using the Order No. to the
right; Basic Vent Kit includes
one of each of the items num-
bered 2 to 5, and two
Mounting Clips 6.
7424 119
7424 120
7424 121
Order No.
1 Boiler Vent Pipe Adaptor
included with boiler
A
Flue Transition
110/150 to 100/150 only
not shown - required WB2B 80/105
—
—
7424 115
Order No.
B
A
Combustion Air Intake
A
A
Adaptor, coaxial
60/100 to 80/125
not shown - only for WB2B 19/26/35
Adaptor, coaxial
60/100 to 100/150
not shown - only for WB2B 19/26/35
Adaptor, coaxial
80/125 to 100/150
not shown - only for WB2B 45/60
—
—
—
7424 112
—
—
—
7424 113
7424 114
Order No.
Order No.
Order No.
Combustion Air Intake
Flue Gas Outlet
B
A
2 90° Elbow
EqL=1.6ft. / 0.5m
7424 094
7424 095
7424 096
Order No.
3 Straight Pipe 2
3.3ft. / 1m
7424 091
7424 092
7424 093
Order No.
4 Vent Termination
2.6ft. / 0.8m
7424 100
7424 101
7424 102
Order No.
5 Protective Screen 1
7134 237
Order No.
6 Mounting Clip 2 (each)
7424 109
7424 110
7424 111
Order No.
Other Available Vent Pieces
not shown in illustration above
Sliding Coupling
1.25ft. / 0.4m
7424 106
7424 107
7424 108
Order No.
Straight Pipe 2
1.6ft. / 0.5m
7424 088
7424 089
7424 090
Order No.
5369 295 v1.2
45° Elbow (Set of 2)
EqL=1.0ft. / 0.3m
7424 097
7424098
7424 099
Order No.
1 PPs coaxial vent material must be ULC S-636 certified for Category IV boilers. Do not mix non-ULC S-636 with ULC S-636 venting.
Side wall venting installation must include Viessmann Protective Screen!
2 Order 1 Mounting Clip for each straight length of vent pipe installed.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 elbows may be installed in the vent system; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
Coaxial PPs Vent System (continued)
Vent System 1
Vent System Diameter
60/100
80/125
100/150
Diameter
Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
-19/-26
30 / 9
-19/-26
39 / 12
-19/-26
52 / 16
ft. / m
WB2B
-35
23 / 7
-35/-45
33 / 10
-35
49 / 15
ft. / m
WB2B
-60
20 / 6
-45
43 / 13
ft. / m
WB2B
-60
33 / 10
ft. / m
WB2B
-80-105
43 / 13
ft. / m
5369 295 v1.2
1 Boiler Vent Pipe Adaptor
included with boiler
Independent Operation
A
A
Flue Transition
110/150 to 100/150 only
not shown - required WB2B 80/105
—
—
7424 115
97.—
Order No.
CDN$
Important!
Adaptor, coaxial
60/100 to 80/125
not shown - only for WB2B 19/26/35
Adaptor, coaxial
60/100 to 100/150
not shown - only for WB2B 19/26/35
Adaptor, coaxial
80/125 to 100/150
not shown - only for WB2B 45/60
—
—
—
7424 112
108.—
—
—
—
7424 113
170.—
7424 114
131.—
Order No.
CDN$
Order No.
CDN$
Order No.
CDN$
Important!
As a starting point, please pay
attention to boiler vent
connection size shown on page
2.6-14.
2 90° Elbow
EqL=1.6ft. / 0.5m
7424 094
76.—
7424 095
108.—
7424 096
158.—
Order No.
CDN$
connection size shown on page
2.6-14.
6 Mounting Clip 2 (each)
7424 109
15.—
7424 110
19.—
7424 111
29.—
Order No.
CDN$
8 Sliding Coupling
1.25ft. / 0.4m
7424 106
76.—
7424 107
86.—
7424 108
97.—
Order No.
CDN$
9 Straight Pipe 2
1.6ft. / 0.5m
Straight Pipe 2
3.3ft. / 1m
7424 088
59.—
or
7424 091
86.—
7424 089
76.—
or
7424 092
108.—
7424 090
108.—
or
7424 093
131.—
Order No.
CDN$
Order No.
CDN$
45° Elbow (Set of 2)
EqL=1ft. / 0.3m
7424 097
131.—
7424 098
143.—
7424 099
201.—
Order No.
CDN$
Vent Termination
3.9ft. / 1.2m
7424 103
268.—
7424 104
363.—
7424 105
449.—
Order No.
CDN$
Combustion Air Intake
Flue Gas Outlet
B
A
Roof Flashing
and Storm Collar
(B-Vent material or better)
field
supplied
1 PPs coaxial vent material must be ULC S-636 certified for Category IV boilers. Do not mix non-ULC S-636 venting with ULC S-636 venting.
2 Order 1 mounting clip for each straight length of vent pipe installed.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 elbows may be installed in the vent system; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
Stainless Steel Vent System
Vent System 1
Vent System Diameter
3”
4”
Diameter
Horizontally Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-19...-35
148 / 45
-19...-35
180 / 55
ft. / m
Room Air
Independent Operation
1 Boiler Vent Adaptor
included with boiler
b
Independent Operation
2 Adaptor, for stainless steel
60/100 to 80/125
(outer shell removed)
7424 112
Order No.
a
A
B
3 Adaptor(s), stainless steel
80mm to 3”
3” to 4”
(not shown)
field
supplied
—
field
supplied
and
field
supplied
A
4 Venting Support 2
field supplied
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
Combustion Air Intake
A
6 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
Combustion Air Intake
Flue Gas Outlet
B
A
7 2” to 3” or 2” > 4”
field supplied
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
9 Bird Screen c/w Termination
for stainless steel
field supplied
5369 295 v1.2
1 Boiler Vent Adaptor
included with boiler
b
Dependent Operation
B
2 Adaptor, for stainless steel
60/100 to 80/125
(outer shell removed)
7424 112
Order No.
A
A
B
3 Adaptor(s), stainless steel
80mm to 3”
3” to 4”
(not shown)
field
supplied
—
field
supplied
and
field
supplied
4 Venting Support 2
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
C
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
a = zero
Flue Gas Outlet
Air Opening
B
C
9 Bird Screen c/w Termination
for stainless steel
field supplied
1 Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
Stainless Steel Vent System (continued)
Vent System 1
Vent System Diameter
3”
4”
Diameter
Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-19...-35
148 / 45
-19...-35
180 / 55
ft. / m
A
Room Air
Independent Operation
B
1 Boiler Vent Adaptor
included with boiler
A
Independent Operation
B
2 Adaptor, for stainless steel
60/100 to 80/125
(outer shell removed)
7424 112
Order No.
b
3 Adaptor(s), stainless steel
80mm to 3”
3” to 4”
(not shown)
field
supplied
—
field
supplied
and
field
supplied
a
4 Venting Support 2
field supplied
a
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
6 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
A
7 2” to 3” or 2” to 4”
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
8 Combustion Air Intake Vent Material 3
field supplied
Flue Gas Outlet
B
9 Bird Screen c/w Termination
field supplied
Room Air
Dependent Operation
B
1 Boiler Vent Adaptor
included with boiler
2 Adaptor, for stainless steel
60/100 to 80/125
(outer shell removed)
7424 112
Order No.
A
A
b
3 Adaptor(s), stainless steel
80mm to 3”
3” to 4”
(not shown)
field
supplied
—
field
supplied
and
field
supplied
4 Venting Support 2
field supplied
Combustion Air Intake
A
C
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
Combustion Air Intake
Flue Gas Outlet
Air Opening
a = zero
B
A
C
9 Bird Screen c/w Termination
for stainless steel
field supplied
1 Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
5369 295 v1.2
Stainless Steel Vent System (continued)
Vent System 1
Vent System Diameter
3”
4”
4”
Diameter
Horizontally Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-45/-60
98 / 30
-45/-60
148 / 45
-80/-105
131 / 40
ft. / m
Room Air
Independent Operation
1 Boiler Vent Adaptor
included with boiler
b
Independent Operation
2 Double-Pipe Adaptor
7189 822
7373 253
Order No.
a
A
B
3 Adaptor(s), stainless steel
80mm to 3”
(order 2 pcs)
3” to 4”
(order 2 pcs)
(not shown)
110mm to 4” (order 2 pcs)
field
supplied
—
—
field
supplied
and
field
supplied
—
—
—
field
supplied
4 Venting Support 2
field supplied
A
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
9 Bird Screen c/w Termination
for stainless steel
field supplied
b
Room Air
Dependent Operation
1 Boiler Vent Adaptor
included with boiler
b
B
2 Adaptor, stainless steel
80mm to 3”
field
supplied
field
supplied
—
B
A
3 Adaptor, stainless steel
3” to 4”
110mm to 4”
—
—
field
supplied
field
supplied
—
field
supplied
4 Venting Support 2
field supplied
a = zero
Combustion Air Intake
Flue Gas Outlet
Air Opening
B
A
C
C
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
a = zero
9 Bird Screen c/w Termination
for stainless steel
field supplied
1 Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
5369 295 v1.2
Stainless Steel Vent System (continued)
Vent System 1
Vent System Diameter
3”
4”
4”
Diameter
Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-45/-60
98 / 30
-45/-60
148 / 45
-80/-105
131 / 40
ft. / m
A
Room Air
Independent Operation
B
1 Boiler Vent Adaptor
included with boiler
A
Independent Operation
B
2 Double-Pipe Adaptor
7189 822
7373 253
Order No.
a
b
3 Adaptor(s), stainless steel
80mm to 3”
(order 2 pcs)
3” to 4”
(order 2 pcs)
(not shown)
110mm to 4” (order 2 pcs)
field
supplied
—
—
field
supplied
and
field
supplied
—
—
—
field
supplied
a
4 Venting Support 2
field supplied
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
Combustion Air Intake
A
8 Combustion Air Intake Vent Material 3
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
9 Bird Screen c/w Termination
for stainless steel
field supplied
Room Air
Dependent Operation
B
1 Boiler Vent Adaptor
included with boiler
2 Adaptor, stainless steel
80mm to 3”
field
supplied
field
supplied
—
b
3 Adaptor, stainless steel
3 to 4”
110mm to 4”
—
—
field
supplied
field
supplied
—
field
supplied
A
4 Venting Support 2
field supplied
Combustion Air Intake
A
C
5 ULC/UL listed Stainless Steel Vent
Material 1 for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
field supplied
Combustion Air Intake
Flue Gas Outlet
Air Opening
a = zero
B
A
C
9 Bird Screen c/w Termination
for stainless steel
field supplied
1 Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
5369 295 v1.2
I M P O R T A N T :
Do not use any DWV plumbing
pipes to vent this boiler.
Appendix
53
CPVC Vent System
Vent System 1
Vent System Diameter
2”
3”
4”
Diameter
Horizontally Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-19...-35
115 / 35
-19...-35
148 / 45
-19...-35
180 / 55
ft. / m
Room Air
Independent Operation
1 Boiler Vent Adaptor
included with boiler
b
Independent Operation
2 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
a
A
B
3 Adaptor(s), CPVC
2” to 3”
3” to 4”
(not shown)
—
—
field
supplied
—
field
supplied
and
field
supplied
A
4 Venting Support 2
field supplied
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
Combustion Air Intake
A
6 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
Combustion Air Intake
Flue Gas Outlet
B
A
7 2” to 3” or 2” to 4”
field supplied
Flue Gas Outlet
B
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
9 Bird Screen (set of 2)
for CPVC
7134 780
7134 781
7134 782
Order No.
5369 295 v1.2
1 Boiler Vent Adaptor
included with boiler
b
B
2 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
A
A
B
3 Adaptor(s), CPVC
2” to 3”
3” to 4”
(not shown)
—
—
field
supplied
—
field
supplied
and
field
supplied
4 Venting Support 2
field supplied
Combustion Air Intake
Flue Gas Outlet
Air Opening
B
A
C
C
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
a = zero
Air Opening
C
9 Bird Screen (set of 2)
for CPVC
7134 780
7134 781
7134 782
Order No.
1 CPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
I M P O R T A N T :
Do not use any DWV plumbing
pipes to vent this boiler.
Appendix
55
CPVC Vent System (continued)
Vent System 1
Vent System Diameter
Vent System
2”
3”
4”
Diameter
Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-19...-35
115 / 35
-19...-35
148 / 45
-19...-35
180 / 55
ft. / m
A
Room Air
Independent Operation
B
1 Boiler Vent Adaptor
included with boiler
A
Independent Operation
B
2 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
b
3 Adaptor(s), CPVC
2” to 3”
3” to 4”
(not shown)
—
—
field
supplied
—
field
supplied
and
field
supplied
4 Venting Support 2
field supplied
a
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
6 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
7 2” to 3” or 2” to 4”
field supplied
Combustion Air Intake
B
A
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
Flue Gas Outlet
B
9 Bird Screen (set of 2)
for CPVC
7134 780
7134 781
7134 782
Order No.
Room Air
Dependent Operation
B
1 Boiler Vent Adaptor
included with boiler
2 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
A
A
b
3 Adaptor(s), CPVC
2” to 3”
3” to 4”
(not shown)
—
—
field
supplied
—
field
supplied
and
field
supplied
4 Venting Support 2
field supplied
Combustion Air Intake
A
C
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
Combustion Air Intake
Flue Gas Outlet
Air Opening
a = zero
B
A
C
9 Bird Screen (set of 2)
for CPVC
7134 780
7134 781
7134 782
Order No.
1 CPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
5369 295 v1.2
I M P O R T A N T :
Do not use any DWV plumbing
pipes to vent this boiler.
Appendix
57
CPVC Vent System (continued)
Vent System 1
Vent System Diameter
3”
4”
4”
Diameter
Horizontally Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-45/-60
98 / 30
-45/-60
148 / 45
-80/-105
131 / 40
ft. / m
Room Air
Independent Operation
1 Boiler Vent Adaptor
included with boiler
b
Independent Operation
2 Double-Pipe Adaptor
7189 822
7373 253
Order No.
a
A
B
3 Adaptor(s), CPVC
80mm to 3”
(order 2 pcs)
3” to 4”
(order 2 pcs)
(not shown)
110mm to 4” (order 2 pcs)
7134 770
—
—
7134 770
and
field
supplied
—
—
—
7134 771
Order No.
Order No.
4 Venting Support 2
field supplied
A
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
9 Bird Screen (set of 2)
for CPVC
7134 781
7134 782
Order No.
5369 295 v1.2
5369 295 v1.2
1 Boiler Vent Adaptor
included with boiler
b
2 Flue Adaptor, CPVC
7134 770
7134 771
Order No.
A
B
3 Adaptor(s), CPVC
3” to 4”
—
field
supplied
C
4 Venting Support 2
field supplied
a = zero
Combustion Air Intake
Flue Gas Outlet
Air Opening
B
A
C
C
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
9 Bird Screen (set of 2)
for CPVC
7134 781
7134 782
Order No.
1 CPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
I M P O R T A N T :
Do not use any DWV plumbing
pipes to vent this boiler.
Appendix
59
CPVC Vent System (continued)
Vent System 1
Vent System Diameter
3”
4”
4”
Diameter
Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-45/-60
98 / 30
-45/-60
148 / 45
-80/-105
131 / 40
ft. / m
A
Room Air
Independent Operation
B
1 Boiler Vent Adaptor
included with boiler
A
Independent Operation
B
2 Double-Pipe Adaptor
7189 822
7373 253
Order No.
a
b
3 Adaptor(s), CPVC
80mm to 3”
(order 2 pcs)
3” to 4”
(order 2 pcs)
(not shown)
110mm to 4” (order 2 pcs)
7134 770
—
—
7134 770
field
supplied
—
—
—
7134 771
Order No.
Order No.
a
4 Venting Support 2
field supplied
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
Combustion Air Intake
A
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
9 Bird Screen (set of 2)
for CPVC
7134 781
7134 782
Order No.
Room Air
Dependent Operation
B
1 Boiler Vent Adaptor
included with boiler
2 Flue Adaptor, CPVC
7134 770
7134 771
Order No.
b
3 Adaptor(s), CPVC
3” to 4”
—
field
supplied
—
A
4 Venting Support 2
field supplied
C
Combustion Air Intake
Flue Gas Outlet
B
A
5 ULC/UL listed CPVC Vent Material 1
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
a = zero
Flue Gas Outlet
Air Opening
B
C
9 Bird Screen (set of 2)
for CPVC
7134 781
7134 782
Order No.
1 CPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
5369 295 v1.2
I M P O R T A N T :
Do not use any DWV plumbing
pipes to vent this boiler.
Appendix
60
CPVC or Stainless Steel Vent System
Vent System 1
Vent System Diameter
2”
3”
4”
Diameter
Hybrid Vent System
Horizontal Intake / Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-19...-35
115 / 35
-19...-35
148 / 45
-19...-35
180 / 55
ft. / m
5369 295 v1.2
5369 295 v1.2
1 Boiler Vent Adaptor
included with boiler
Independent Operation
B
2 Adaptor, for stainless steel
60/100 to 80/125
(outer shell removed)
7424 112
Order No.
2 Adaptor(s), CPVC
60 to 2”
7134 769
Order No.
3 Adaptor(s), stainless steel
80mm to 3”
3” to 4”
(not shown)
—
—
field
supplied
—
field
supplied
and
field
supplied
b
3 Adaptor(s), CPVC
2” to 3”
3” to 4”
(not shown)
—
—
field
supplied
—
field
supplied
and
field
supplied
a
4 Venting Support 2
field supplied
a
A
5 ULC/UL listed
Stainless Steel Vent Material 1a
for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
or
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
5 ULC/UL listed
CPVC Vent Material 1b
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
6 Adaptor(s), CPVC
60mm to 2”
7134 769
Order No.
7 2” to 3” or 2” to 4”
field supplied
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
9 Bird Screen c/w Termination
for stainless steel
or
field supplied
9 Bird Screen (Set of 2)
for CPVC
7134 780
7134 781
7134 782
Order No.
1aStainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
1bCPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
I M P O R T A N T :
Do not use any DWV plumbing
pipes to vent this boiler.
Appendix
62
CPVC or Stainless Steel Vent System (continued)
Vent System 1
Vent System Diameter
Vent System
3”
4”
4”
Diameter
Hybrid Vent System
Horizontal Intake / Vertically Vented
Maximum Equivalent
WB2B
Length (EqL)
a + b
-45/-60
98/30
-45/-60
148 / 45
-80/-105
131/40
ft. / m
Room Air
Independent Operation
1 Boiler Vent Adaptor
included with boiler
Independent Operation
B
2 Double-Pipe Adaptor
7189 822
7373 253
Order No.
3 Adaptor(s), stainless steel
80mm to 3”
(order 2 pcs)
3” to 4”
(order 2 pcs)
(not shown)
110mm to 4” (order 2 pcs)
or
field
supplied
—
—
field
supplied
and
field
supplied
—
—
—
field
supplied
a
b
A
3 Adaptor(s), CPVC
80mm to 3”
(order 2 pcs)
3” to 4”
(order 2 pcs)
(not shown)
110mm to 4” (order 2 pcs)
7134 770
—
—
7134 770
and
field
supplied
—
—
—
7134 771
Order No.
Order No.
A
4 Venting Support 2
field supplied
Combustion Air Intake
A
5 ULC/UL listed
Stainless Steel Vent Material 1a
for EqL calculations, use:
45° Elbow EqL=2ft. / 0.6m
90° Elbow EqL=3ft. / 0.9m
or
field supplied
Combustion Air Intake
Flue Gas Outlet
B
A
5 ULC/UL listed
CPVC Vent Material 1b
for EqL calculations, use:
45° Elbow EqL=3ft. / 0.9m
90° Elbow EqL=5ft. / 1.5m
field supplied
8 Combustion Air Intake Vent Material
Allowable materials: see note below 3
field supplied
9 Bird Screen c/w
Termination
for stainless steel
or
field supplied
5369 295 v1.2
9 Bird Screen (Set of 2)
for CPVC
7134 780
7134 781
7134 782
Order No.
1aStainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers.
Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
1bCPVC vent material must be ULC/UL listed, for Category IV boilers. Suggested source: IPEX Inc.
2 Boiler cannot support weight of vent system. Support venting as prescribed in vent manufacturer’s installation instructions.
3 Combustion air supply pipe may be made of the following materials: ABS, CPVC, PVC, or stainless steel.
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length.
Always follow Viessmann venting installation instructions 5368 815.
Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario • N2V 2G5 • Canada
Tel. (519) 885-6300 • Fax (519) 885-0887
www.viessmann.ca • [email protected]
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island • 02886 • USA
Tel. (401) 732-0667 • Fax (401) 732-0590
www.viessmann-us.com • [email protected]
64