7.2.10 Flange EN (code 4)

H1 H FTF ØD Øk Ød ØL Connection type flange EN (code 4) 1), body material PVC-U (code 1) 2) MG DN NPS ød øD FTF H H1 øk øL n 20 15 1/2" 45.0 95.0 130.0 36.0 10.0 65.0 14.0 4 20 3/4" 58.0 105.0 150.0 38.0 12.0 75.0 14.0 4 25 1" 68.0 115.0 160.0 39.0 13.0 85.0 14.0 4 25 32 1¼" 78.0 140.0 180.0 41.0 15.0 100.0 18.0 4 40 ...

39 / 51

GEMÜ R649 eSyDrive 11.5 Connecting the valve electrically 1. Protect the electrical connections from direct contact with rain water. 2. Lay the cables and pipework so that neither condensate nor rain water can get into the plug unions. 3. Check that all plug cable glands and fittings are mechanic- ally secured. ð The cable must b ...

7.2.5 Union end inch (code 33, 3M, 3T)

GEM eSyDrive R649 L1 H1 H L2 R ØD Ød Connection type union end inch (code 33) 1), body material PVC-U (code 1) 2), diaphragm size 10 MG DN NPS ød øD H H1 L1 L2 R 10 15 1/2'' 21.4 43.0 30.0 15.0 90.0 128.0 G1 Connection type union end inch (code 33, 3M, 3T) 1), body material PVC-U (code 1) 2), diaphragm size 20 - 40 MG DN NPS � ...

38 / 51

GEM eSyDrive R649 GEMÜ R649 eSyDrive 11 Electrical connection 11 Electrical connection NOTICE Appropriate cable socket/appropriate mating connector! ▶ The appropriate cable socket and/or appropriate mating connector is included for X1, X3 and X4. ▶ The appropriate cable socket and/or appropriate mating connector is not included for X2. X3 X2 X4 ...

7.1 Actuator dimensions

GEM eSyDrive R649 B2 ØB B1 B3 A1 CT* A MG DN Actuator version A A1 Ø B B1 B2 B3 10 10 - 20 0A 230.0 44.0 68.0 126.0 160.0 190.0 20 15 - 25 E0 237.0 44.0 68.0 126.0 160.0 190.0 1A 299.0 83.0 82.0 132.0 172.0 250.0 25 32 1A 305.0 83.0 82.0 132.0 172.0 250.0 40 40, 50 1A 303.0 75.0 82.0 132.0 172.0 243.0 2A 360.0 124.0 134.0 157.0 224.0 296 ...

selectable using software

GEM eSyDrive R649 Voltage: 24 V DC Logic level "1": >14 V DC Logic level "0": < 8 V DC Input current: typ. 2.5 mA (at 24 V DC) 6.7.3 Analogue output signals 6.7.3.1 Actual value Output signal: 0/4 - 20 mA; 0 – 10 V DC (selectable using software) Output type: Active (AD5412) Accuracy: ≤ ±1% of full flow Temperature drift: ≤ ±0.1% / 1 ...

7.2.7 Union end Rp (code 7R)

GEM eSyDrive R649 D L1 L2 R H1 H Rp Connection type union end Rp (code 7R) 1), body material PVC-U (code 1) 2) MG DN NPS øD H H1 L1 L2 R Rp 20 15 1/2" 43.0 36.0 10.0 108.0 146.0 G 1 1/2 20 3/4" 53.0 38.0 12.0 108.0 152.0 G 1¼ 3/4 25 1" 60.0 39.0 13.0 116.0 166.0 G 1½ 1 25 32 1¼" 74.0 41.0 15.0 134.0 192.0 G 2 1¼ 40 40 1½" 83.0 63.2 23 ...

Dimensions in mm, MG = diaphragm size

GEM eSyDrive R649 GEMÜ R649 eSyDrive www.gemu-group.com 31 / 51 7 Dimensions ...

33 / 51

GEMÜ R649 eSyDrive 8.1 Connection X1 1 3 2 6 5 4 7-pin plug, Binder, type 693 Pin Signal name Pin 1 Uv, 24 V DC supply voltage Pin 2 Uv GND Pin 3 Relay output K1, common Pin 4 Relay output K1, make contact Pin 5 Relay output K2, common Pin 6 Relay output K2, make contact Pin PE Function earth 8.2 Connection X2 1 5 4 3 2 5-pin M12 ...

Pressure/temperature correlation PN 6

GEM eSyDrive R649 Valve body material Temperature in °C (valve body) Materials Code -10 0 5 10 20 25 30 40 50 60 70 80 PVC-U 1 - - - 6.0 6.0 6.0 4.8 3.6 2.1 0.9 - - PP 5 - - 6.0 6.0 6.0 6.0 5.1 4.2 3.3 2.4 - - PP-H N5 - - 6.0 6.0 6.0 6.0 5.1 4.2 3.3 2.4 - - PVDF 20 6.0 6.0 6.0 6.0 6.0 6.0 5.4 4.8 4.3 3.8 ...

8 / 51

GEM eSyDrive R649 GEMÜ R649 eSyDrive 4 Correct use WARNING Improper use of the product ▶ Risk of severe injury or death. ▶ Manufacturer liability and guarantee will be void. ● Only use the product in accordance with the operating conditions specified in the contract documentation and in this document. The product is designed for installation ...

40 / 51

GEM eSyDrive R649 GEMÜ R649 eSyDrive 11 Electrical connection 11.6 Connection diagram 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 6 6 7 8 eSyDrive X1 X2 X3 X4 Power supply Uv Uv GND 24 V DC K1 maximum 125 V AC / 48 V DC - 2A Relay output K1 maximum 125 V AC / 48 V DC - 2A Relay output K2 K2 eSyWeb / Modbus TCP Rx - (Ethernet) Tx + (Ethernet) Rx + (Ethernet ...

GEM eSyDrive R649 user guide recommended for: 415, R487 Victoria, 514, Q30, R478 Tugela.