Kara BACnet Gateway

Page 22 The M-Bus:BACnet Gateway is a BACnet Application Specific Controller (B-ASC) The selected M-Bus Meter Records will converted to BACnet Analog Objects A B-ASC intended for use in a specific application and supports limited programmability. It enables specification of the following: • Ability to provide the values ...

Kara BACnet Gateway

Kara Systems BACnet:M-Bus Page 12 Host Name: Enter the name for the device IP-Address: Enter the IP number for the device for the target LAN. Subnet-mask: The IP Mask of the Target LAN. For example 255.255.0.0 Default gateway: The default IP number of the IP-Gateway/Router of the target LAN Domain Name Server: The DNS Server of your target LAN, if ...

Kara BACnet Gateway

Kara Systems BACnet:M-Bus Page 18 5.3 4.3 Meter Configuration 5.3.1 Reading Interval: Meters are read periodically. You can set the reading interval in minutes for a specific meter or you can set this interval for all meters by clicking on the “Set Interval for ALL Meters”. The default value is one minute. 5.3.2 Record No: This is the record n ...

Kara BACnet Gateway

Kara Systems BACnet:M-Bus Page 11 Click on “Administration” and then on “Network Configuration” Step 3: Configure the Network Configuration of the target LAN. ...

Kara BACnet Gateway

Kara Systems BACnet:M-Bus Page 14 4.2.2 BACnet Broadcast Management Device (BBMD) If the “BACnet Workstation Operator “ or other BACnet device which needs to establish a bind with the “M-Bus:BACnet Gateway” is located on a different IP sub-network, you have to register the device IP number in the “BBMD Registration dialog”. The default ...

Kara BACnet Gateway

Page 21 On the left side the BACnet browser shows a tree of all the BACnet Objects grouped in object-type. When you click on an element on the tree an object list or a configuration dialog is displayed on the right hand side. 8 RECOVERY A recovery procedure is needed if for some reason you forgot the admin-password of the ...