cables. The connection is designed to be strapped to the pipe or mounted on the wall at the start of the heating cable circuit. These installation instructions should be used in conjunction with the IceStop, XL-Trace and HWAT System Installation and Operation Manuals ...
5 4 • Score around and down the outer jacket of the heating cable 3 1/8 inches from the end. • Remove the outer jacket. • Place the metal clip over the base of the exposed braid. Do not cut through metal braid or inner jacket. 1 2A 3 2B • Using the plastic cable ties, attach* the bracket ...
6B 6A • Pull exposed braid back over metal clip. 8 • Insert prepared heating cable end into connector. Push until heating cable is fully inserted and end is visible through opening in connection cover plate. HWAT Only IceStop and XL-Trace Only 3 1/8" 1" 9 • For HWAT only: Apply HWAT label o ...
attach heating cable to pipe. • Apply insulation, cladding and warning labels. • Terminate power wiring in user-supplied junction box. • Using glass cloth tape, attach heating cable to pipe. • Apply insulation, cladding and warning labels. • Terminate power wiring i ...
by pressing until it snaps in place. • Complete heating cable installation and install a drip loop as shown. • Protect heating cable from sharp edges. Power Connection • Connect user-supplied 1/2-inch conduit by following step 11 on page 4. • Apply Electric De-Icing and Snow ...
1" 2 1 • Remove exposed braid. • Push end seal completely onto heating cable. End Seal Installation 3 1/8" 1" IceStop and XL Trace HWAT IceStop and XL-Trace HWAT H W A T IceStop and XL-Trace Note: The end seal is designed to be installed only once; it cannot be removed from the heating cabl ...
Troubleshooting Guide Problem Solution Braid�clips�are�missing. The braid clips are attached to the cardboard packing insert under the lid. The braid clips must be used to ensure a ground connection. If clips are missing or lost, call Tyco Thermal Controls at (800) 545-6258. Mounting brac ...
© 2011 Tyco Thermal Controls LLC INST-172 PN 511491-000 H55092 05/11 Tyco, HWAT, IceStop, RayClic, and XL-Trace are registered and/or unregistered trademarks of Tyco Thermal Controls LLC or its affiliates. TORX is a registered trademark of Textron., Inc. Worldwide Headquarters T ...
Raychem RayClic-PC user guide recommended for: TraceTek TT3000 SERIES, FTC-XC, pyrotenax Alloy 825, JBS-100-EP, C25-100.
⚠️ Download Safety
The Cables and connectors Installation instructions manual (8 pages) is completely safe to download (last scan date: 22/07/2026).
Related PDF Instructions for Raychem RayClic-PC:
-
Raychem HTC-915 Temperature Controller Manual , 8 pages
-
Raychem E-150 Food Saver Installation instructions manual, 12 pages
-
Raychem TraceTek TTDM Control Unit Installation instructions, 2 pages
-
Raychem FrostGuard-ECO Controller Installation manual, 34 pages
-
Raychem Gardian W51 Cables and connectors Installation instructions manual, 8 pages
-
Raychem C25-100 Cables and connectors Manual , 22 pages