ECL Comfort 210, 296 and 310, return temperature

limitation 1.0 Table of Contents 1.0 Table of Contents ............................................. 1 1.1 Important safety and product information.................... 2 2.0 Settings........................................................... 5 2.1 Return temperature limitation in a master / sla ...

Important safety and product information

1.1.1 Important safety and product information This Installation Guide is an appendix to installation guides associated with ECL application keys produced as from September 2013 and contains only a description of the return temperature limitation functionality in a master / slave system. The return temperature lim ...

Automatic update of controller software (firmware):

The software of the controller is updated automatically when the key is inserted (as of controller version 1.11 (ECL 210 / 310) and version 1.58 (ECL 296)). The following animation will be shown when the software is being updated: Progress bar During update: • Do not remove the KEY If the key is removed b ...

This product should be dismantled and its components

sorted, if possible, in various groups before recycling or disposal. Always follow the local disposal regulations. 4 | © Danfoss | 2017.08 VI.GU.W2.02 ECL Comfort 210, 296 and 310, return temperature limitation ...

Return temperature limitation in a master / slave system

The circuit 1 menu for return temperature limit parameters contains an additional parameter "DHW, ret. T limit" (= Domestic Hot Water, return temperature limit). When a slave in a master / slave system is in DHW-tank heating / charging mode, the desired flow temperature value is transf ...

MENU > Settings > Return temperature limitation in a master /

slave system Demand offset 11017 Circuit Setting range Factory setting 1 OFF / 1 ... 20 K OFF The desired flow temperature in heating circuit 1 can be influenced by the demand for a desired flow temperature from another controller (slave) or another circuit. OFF: The desired flow temperature in ci ...

Several controllers in the same system

When ECL Comfort controllers are interconnected by means of the ECL 485 communication bus (cable type: 2 x twisted pair), the master controller will broadcast the following signals to the slave controllers: • Outdoor temperature (measured by S1) • Time and date • DHW tank heating / charging a ...

SLAVE controller: How to react on a DHW tank heating /

charging activity sent from the MASTER controller The slave receives information about a DHW tank heating / charging activity in the master controller and can be set to close the selected heating circuit. ECL controller versions 1.48 (as from August 2013): The master receives information abo ...

SLAVE controller: How to make use of the outdoor temperature

signal and send information about the desired flow temperature back to the MASTER controller The slave controller receives information about outdoor temperature and date / time. The master controller receives information about the desired flow temperature from slave controllers with an ...

10| © Danfoss | 2017.08

VI.GU.W2.02 ECL Comfort 210, 296 and 310, return temperature limitation ...