Emec MTOWER PLUS Series Operating Instructions Manual
Text of Emec MTOWER PLUS Series Operating Instructions Manual
Read Carefully !
ENGLISH Version
R12-01-18
OPERATING INSTRUCTIONS F O R
“MTOWER PLUS” INSTRUMENT
This manual contains safety information that if ignored
can endanger life or result in serious injury. They are
indicated by this icon.
Keep the instrument protected from sun and water.
Avoid water splashes.
CD/PH/RH Version
all-guides
com
GENERAL SAFETY GUIDELINES
In emergencies the instrument should be switched off immediately! Disconnect the power cable
from the power supply!
When installing always observe local regulations!
Manufacturer is not liable for any unauthorized use or misuse of this product that may cause injury,
damage to persons and / or materials.
Caution!
Instrument
The “MTOWER PLUS” is a fully featured cooling towers controller with two-way biocide options and inhibitor / bleed
control.Cooling towers are heat removal devices used to transfer process waste heat to the atmosphere. Cooling towers
may either use the evaporation of water to remove process heat and cool the working fluid to near the wet-b
Unplug instrument from main power supply then perform connections to probes and / or selected outputs by following
the above picture. For easy understanding board has been divided into two parts: Power connections and I/O
connections.
Power Connections:
F1: General fuse (6.3AT)
F2: Circuit fuse (3.15AT)
Main power supply (from 90VAC
Standby / Proportional Outputs:
1: - D1 mV (Biocide1) 3: - Biocide2 5: - Pre-biocide1 7: - (Cl) 9: - pH 11: - Inhibitor
2 + D1 mV (Biocide1) 4: + Biocide2 6: + Pre-biocide1 8: + (Cl) 10: + pH 12: + Inhibitor
mA outputs (500 Ohm max resistive loa
Cooling tower basic knowledge.
What is a (wet, atmospheric) cooling tower?
A cooling tower is a heat rejection device, which extracts waste heat to the atmosphere though the cooling of a water
stream to a lower temperature. The type of heat rejection in a cooling tower is termed “evaporative” in that it allows a small
portion of the water being cooled