Elcomponent AEM32 Operation & User’s Manual
Text of Elcomponent AEM32 Operation & User’s Manual
AEM32 DIN User Manual
Safety
This instrument is manufactured in compliance with EN61010-1 cat. III for nominal operating
voltages of 400V L-L and 230V L-N. To ensure safe operation the user must comply with the
following instructions:
Ensure that the supply voltage is correct.
The auxiliary mains supply is internally fused at 250V, 100mA Type 2, exte
AEM32 DIN User Manual
Connection of the current input
The AEM32 is suitable for use with current transformers (CTs) with 5A secondary output. Metering
quality CTs of Class 1 accuracy with a minimum rating of 2.5VA are recommended.
Connections should be made according to the diagrams below.
CAUTION: The instrument is internally fused at 250V 100mA. External
AEM32 DIN User Manual
Pulse output connections
CAUTION: The pulse output contacts are rated at 100mA AC/DC, 100V max. Under no
circumstances should this rating be exceeded.
The output has a telltale LED on the front panel which flashes ‘on’ to indicate a pulse being
generated.
The pulse connections are as follows: Terminals 13 & 14
The contacts are volt
AEM32 DIN User Manual
Programming
CT SET-UP
The instrument must be set up for the CTs to which it is connected. This need only be done once,
after which the setting is maintained in memory for the life of the unit regardless of whether it is
powered up or not.
To enter programming mode press
and
simultaneously
for 5 seconds. The unit shows the CT primary
AEM32 DIN User Manual
Technical Characteristics
Connection:
3 Phase 3 or 4 wire Unbalanced,
3 Phase Balanced,
Single Phase Load
Inputs:
Voltage: 400/230V 3 Phase 3/4 wire
Current: 5A – External CTs. Fully isolated.
Burden:
<0.1VA per phase Current/Voltage
Pulse Output:
Opto isolated volt free contact
Rating: 100mA ac/dc, 100V ac/dc max
Value: 1 pulse per