Elcomponent AEM33 V 485 DIN Quick Start Manual

Text of Elcomponent AEM33 V 485 DIN Quick Start Manual

AEM33 V 485 DIN

INSTRUCTIONS This instrument is manufactured in compliance with EN61010-1 Cat III for nominal operating voltages of 400V L-L and 230V L-N, to ensure safe operation the user must comply with the following instructions: • Ensure that the supply voltage is correct. • The auxiliary mains supply is internally fused at 250V, 100mA Type 2. Exter

3-PHASE 3 OR 4-WIRE (*Optional Neutral)

SINGLE PHASE BALANCE VOLTAGE MODE NOTE: In Balanced Voltage Mode L1, L2 or L3 may be used as the voltage input to V1 as phase is assumed to be zero in all measurements. Balanced Voltage Mode must be selected in the programming Menu in order to obtain meaningful measurements. CAUTION: Ensure the sup

The RS485 output consists of 3 terminals (15, 16 & 17) at the

top left of the unit. These should be connected via the correct specification cable to the data bus. (Refer to Elcomponent for cable recommendations.) Terminal connections are as follows: 15 = A 16 = B 17 = 0 V ( A&B are signal cables.) NOTE: It is essential that the polarity is respected wh

To enter programming mode press

and simultaneously for 5 seconds. The CT primary value may then be set from the following nominal values (Secondary must by set for special Voltage Output CTs): 5, 10, 15, 20, 30, 40, 50, 60, 80, 100, 150, 200, 250, 300, 400, 500, 600, 800, 1000, 1200, 1250, 1500, 1600, 2000, 2400, 3000, 2500, 4000, 4500, 5000, 55

Elcomponent Measuring Instruments Owners Instructions: