Elcomponent AEM33 V 485 DIN Quick Start Manual
Text of Elcomponent AEM33 V 485 DIN Quick Start Manual
AEM33 V 485 DIN
INSTRUCTIONS
This instrument is manufactured in compliance with EN61010-1
Cat III for nominal operating voltages of 400V L-L and 230V L-N,
to ensure safe operation the user must comply with the
following instructions:
•
Ensure that the supply voltage is correct.
•
The auxiliary mains supply is internally fused at 250V,
100mA Type 2. Exter
3-PHASE 3 OR 4-WIRE (*Optional Neutral)
SINGLE PHASE
BALANCE VOLTAGE MODE
NOTE: In Balanced Voltage Mode L1, L2 or L3 may be used
as the voltage input to V1 as phase is assumed to be zero in
all measurements.
Balanced Voltage Mode must be selected in the programming
Menu in order to obtain meaningful measurements.
CAUTION: Ensure the sup
The RS485 output consists of 3 terminals (15, 16 & 17) at the
top left of the unit. These should be connected via the correct
specification cable to the data bus. (Refer to Elcomponent for
cable recommendations.) Terminal connections are as follows:
15 = A 16 = B 17 = 0 V ( A&B are signal cables.)
NOTE: It is essential that the polarity is respected wh
To enter programming mode press
and
simultaneously for 5 seconds. The CT primary value may then
be set from the following nominal values (Secondary must by
set for special Voltage Output CTs):
5, 10, 15, 20, 30, 40, 50, 60, 80, 100, 150, 200, 250, 300, 400,
500, 600, 800, 1000, 1200, 1250, 1500, 1600, 2000, 2400, 3000,
2500, 4000, 4500, 5000, 55