ABB 41-661.2A Instruction Leaflet

Brand: ABB
Category: Relays
Model: 41-661.2A (Instruction Leaflet)
File Type: PDF
File Size: —
Pages: 12
Text of ABB 41-661.2A Instruction Leaflet

ABB 41-661.2A ABB Power T&D Company Inc.

Relay Division Coral Springs, FL 33065 RCL Effective: February 1966 Supersedes I.L 41-661.2 Dated May 1984 Automatic ReclosingRelay Q Denotes Change From Superseded issue in FT-21 Case CAUTION Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment, make sure that all moving parts operate freely, inspect the contacts to see

periphery of the drum. Cams #4 and #5 consist of

show contact positions as a function of the drum screws which can be set at any point on the © position. Fig. 4 is based on the factory cam periphery of the drum. Cam #14 is a single adjustment—immediate, 15 and 45 second reclo- micarta block, located to the rear of the cam #5 sures, with one drum revolution in 60 seconds, position and held by a #5 cam screw. O It is further assumed in Fig.

Internal Schematic of the RCL Relay in Type FT21 Case

4 Courtesy of NationalSwitchgear.com

ABB 41-661.2A the breaker immediately trip again, contacts Y5

and X8 will be open to prevent premature ener- gization of the breaker close circuit. COMPLETE OPERATING SEQUENCE Fault-Trip -Immediate Reclosure 0 Refer to Fig. 5. With the timing drum in the “Start” position, a #3 cam spring will be holding contact #3 closed. The breaker switch contacts 52b and 52bb close, energizing the motor 79M through contact #I, and the drum begins to ro- tate. At th

ABB 41-661.2A tion in 60 seconds. Contact ft4 is set to close in

the lockout position. Contact #14 is set to close in the start position for instantaneous trip lock- out after the first reclosure. The standard relay is shipped with the X and Y coil and motor coil resistors connected. With these connections the X and Y coils may be used at 125 volts d-c or 240 volts a-c; the motor, at 240 volts a-c. unit after each ft3 contact closure. The #5 screws should

The factory settings of the standard relay are:

Coil Resistors in series with X and Y, and motor: X a n d Y r a t i n g . . . . 125 Vdc/24 0 Vat Motor ratin g . . . . . . . . . 240 V 60 cycles Motor spee d . . . . . . 1 revolution in 60 seconds Contact Settings . . . .See Fig. 4 The following checks may be performed to determine if the relay, as received from the fac- tory, is in serviceable condition. Energize the X, Y and