Quick Start Guide

00825-0100-4160, Rev CC February 2021 Rosemount ™ 2160 Wireless Level Detector Vibrating Fork

About this guide...........................................................................................................................3

Installation................................................................................................................................... 6 Configuration...................................................

About this guide

This Quick Start Guide provides basic guidelines for the Rosemount 2160. Refer to the Rosemount 2160 Reference Manual for more instructions. The manual and this guide are also available electronically at Emerson.com/ Rosemount. 1.1 Safety messages NOTICE Power module considerations. Each Power Module contains two "C" size primary lithium/t

Shipping considerations for wireless products.

The unit was shipped to you without the power module installed. Remove the power module prior to shipping. Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are regulated in transportation by the U. S. Department of Transportation, and are also covered by IAT

Process leaks could result in death or serious injury.

Ensure the level detector is handled carefully. If the process seal is damaged, gas might escape from the vessel (tank) or pipe. WARNING Physical access Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional

Fork alignment in a pipe installation

The fork is correctly aligned by positioning the groove or notch as indicated (Figure 2-1). Figure 2-1: Correct Fork Alignment for Pipe Installation OK A B OK A B A. Tri Clamp process connections have a circular notch B. Threaded process connections have a groove 2.2 Fork alignment in a vessel (tank) i

Mounting the threaded version

2.3.1 Threaded vessel (tank) or pipework connection Procedure 1. Seal and protect the threads. Use anti-seize paste or PTFE tape according to site procedures. A gasket may be used as a sealant for BSPP (G) threaded connections. 2. Screw the level detector into the process connection. Note Tighten using the hexagon nut only.

Threaded flange connection

Procedure 1. Place the customer-supplied flange and gasket on the vessel (tank) nozzle. A A. Gasket (customer supplied) 2. Tighten the bolts and nuts with sufficient torque for the flange and gasket. 3. Seal and protect the threads. Use anti-seize paste or PTFE tape according to site procedures. A gasket may be used as a seal