 12 Digital Inputs, including 2 Analog,

3 HSC/Shaft-encoder inputs  12 Transistor Outputs General Description All of the controllers covered in this guide are micro-PLC+HMIs, rugged programmable logic controllers that comprise built-in operating panels

Vision™PLC+HMI Installation Guide

2 Unitronics Alert Symbols and General Restrictions When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Danger The identified danger causes physical and property damage. Warning The identified danger could cause physical and property damage. Caution Caution Use ca

Before you begin, note that the mounting panel cannot be more than 5 mm thick.

UL listed models: To meet the UL508 standard, panel-mount the device on the flat surface of a Type 1 enclosure. 1. Make a panel cut-out of the appropriate size:  V130/V350/V130J/V350J: 92x92 mm (3.622”x3.622”).

Vision™PLC+HMI Installation Guide

4 Unitronics V430J DIN-rail Mounting (V130/V350/V130J/V350J) 1. Snap the controller onto the DIN rail as shown in the figure to the right. 2. When properly mounted, the controller is squarely situated on the DIN-rail as shown in the figure to the right.

 Do not touch live wires.

 Install an external circuit breaker. Guard against short-circuiting in external wiring.  Use appropriate circuit protection devices.  Unused pins should not be connected. Ignoring this directive may damage the device.  Double-check all wiring before turning on the power supply. Ca

Vision™PLC+HMI Installation Guide

6 Unitronics Input Jumper Settings The tables below show how to set a specific jumper to change input functionality. To access the I/O jumpers, you must open the controller according to the instructions beginning on page 11.  Incompatible jumper settings and wiring connections may seriously damage the controller.  Do

pnp (source) Input

Input wiring HSC input wiring Shaft-encoder Analog Input Analog input wiring, current (2/3-wire) Analog input wiring, current (4-wire), Voltage  Shields should be connected at the signal’s source.  The 0V signal of the analog input must be connected to the controller’s 0V.

Vision™PLC+HMI Installation Guide

8 Unitronics Transistors Outputs  Outputs 0 to 6 can be used as PWM outputs. Power Supply The controller requires an external 24VDC power supply.  The power supply must include double insulation. Outputs must be rated as SELV/PELV/Class2/Limited Power.  Use separate wires to connect the functional earth line (pin

These models comprise a built-in RS232/RS485 serial port (Port 1)

 V430J/ V350/V350J These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1). Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications via Port 1. When the PC is disconnected,

Vision™PLC+HMI Installation Guide

10 Unitronics Setting RS232/RS485 Communication Parameters, V430J This port may be set to either RS232 or RS485 via DIP switches: The table shows the DIP switches factory default settings. Use the table to adapt the settings. Switch Settings 1 2 3 4 5 6 RS232* ON OFF OFF ON OFF OFF RS485 OFF ON ON OFF OFF OFF RS485 with te