Unitronics Vision V130-33-T2 Installation Manual
Text of the manual
12 Digital Inputs, including 2 Analog,
3 HSC/Shaft-encoder inputs
12 Transistor Outputs
General Description
All of the controllers covered in this guide are micro-PLC+HMIs, rugged programmable logic controllers
that comprise built-in operating panels
Vision™PLC+HMI Installation Guide
2
Unitronics
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Caution
Use ca
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
UL listed models:
To meet the UL508 standard, panel-mount the device on the flat surface of a Type 1 enclosure.
1. Make a panel cut-out of the appropriate size:
V130/V350/V130J/V350J: 92x92 mm (3.622”x3.622”).
Vision™PLC+HMI Installation Guide
4
Unitronics
V430J
DIN-rail Mounting (V130/V350/V130J/V350J)
1. Snap the controller onto the DIN rail as
shown in the figure to the right.
2. When properly mounted, the controller is
squarely situated on the DIN-rail as
shown in the figure to the right.
Do not touch live wires.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
Ca
Vision™PLC+HMI Installation Guide
6
Unitronics
Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 11.
Incompatible jumper settings and wiring connections may seriously damage the controller.
Do
pnp (source) Input
Input wiring
HSC input wiring
Shaft-encoder
Analog Input
Analog input wiring, current (2/3-wire)
Analog input wiring, current (4-wire), Voltage
Shields should be connected at the signal’s source.
The 0V signal of the analog input must be connected to the controller’s 0V.
Vision™PLC+HMI Installation Guide
8
Unitronics
Transistors Outputs
Outputs 0 to 6 can be used as PWM outputs.
Power Supply
The controller requires an external 24VDC power supply.
The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
Use separate wires to connect the functional
earth line (pin
These models comprise a built-in RS232/RS485 serial port (Port 1)
V430J/ V350/V350J
These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1).
Note that physically connecting a PC to the controller via USB suspends RS232/RS485
communications via Port 1. When the PC is disconnected,
Vision™PLC+HMI Installation Guide
10
Unitronics
Setting RS232/RS485 Communication Parameters, V430J
This port may be set to either RS232 or RS485 via DIP switches:
The table shows the DIP switches factory default settings. Use the table to adapt the settings.
Switch Settings
1
2
3
4
5
6
RS232*
ON
OFF
OFF
ON
OFF
OFF
RS485
OFF
ON
ON
OFF
OFF
OFF
RS485 with
te