YOKOGAWA EJX510B Operation & User’s Manual
Read Online
Read the YOKOGAWA EJX510B Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
Yokogawa Electric Corporation
EJX510B and EJX530B
Absolute and Gauge Pressure
Transmitters
IM 01C27F01-01EN
IM 01C27F01-01EN
2nd Edition
EJX510B and EJX530B
Absolute and Gauge Pressure Transmitters
IM 01C27F01-01EN 2nd Edition
2nd Edition: Aug. 2010 (YK)
All Rights Reserved, Copyright © 2010, Yokogawa Electric Corporation
Contents
1.
Introduction................................................................................................ 1-1
1.1
Safe Use of This Product ..................................................................................1-2
1.2
Radio Wave.........................................................................................................1-3
1.3
Warranty..............................................................................................................1-3
1.4
Trademarks.........................................................................................................1-3
1.5
ATEX Documentation........................................................................................1-4
2.
Handling Cautions..................................................................................... 2-1
2.1
Model and Specifications Check......................................................................2-1
2.2
Unpacking...........................................................................................................2-1
2.3
Storage................................................................................................................2-1
2.4
Selecting the Installation Location .................................................................2-2
2.5
Pressure Connection.........................................................................................2-2
2.6
Restrictions on Use of Radio Transceivers....................................................2-3
2.7
Insulation Resistance and Dielectric Strength Test.......................................2-3
2.8
Installation of an Explosion-Protected Instrument........................................2-4
2.8.1
FM Approval........................................................................................2-4
2.8.2
CSA Certification.................................................................................2-5
2.9
EMC Conformity Standards..............................................................................2-5
2.10
Pressure Equipment Directive (PED)
...................................................2-5
2.11
Low Voltage Directive........................................................................................2-6
2.12
Regulatory Compliance for Radio and Telecommunication.........................2-7
2.12.1
Radio and Telecommunications Terminal Equipment Directive (R&TTE)
.....................................................................................................2-7
2.12.2
FCC compliance.................................................................................2-7
2.12.3
Industry Canada (IC) compliance.......................................................2-7
3.
Component Names................................................................................... 3-1
4.
Installation.................................................................................................. 4-1
4.1
Precautions ........................................................................................................4-1
4.2
Mounting.............................................................................................................4-1
4.3
Rotating Transmitter Section............................................................................4-2
4.4
Changing the Direction of Integral Indicator .................................................4-2
4.5
Changing the direction of the antenna............................................................4-3
Installing Impulse Piping.......................................................................... 5-1
5.1
Impulse Piping Installation Precautions.........................................................5-1
5.1.1
Connecting Impulse Piping to a Transmitter.......................................5-1
5.1.2
Routing the Impulse Piping.................................................................5-1
5.2
Impulse Piping Connection Examples............................................................5-2
6.
Grounding.................................................................................................. 6-1
7.
Operation.................................................................................................... 7-1
7.1
Preparation for Starting Operation..................................................................7-1
7.2
Zero Point Adjustment......................................................................................7-2
7.3
Starting Operation.............................................................................................7-2
7.4
Connecting to the Field Wireless Network......................................................7-3
7.5
Shutting Down the Transmitter........................................................................7-4
8.
Setting Parameters.................................................................................... 8-1
8.1
Environment for parameter setting..................................................................8-1
8.2
Preparing Software for the Configuration Tool..............................................8-1
8.3
Setting Parameters............................................................................................8-2
8.3.1
Parameter Usage and Selection.........................................................8-2
8.3.2
Function Block and Menu Tree...........................................................8-3
8.3.3
Parameters for Wireless Communication.........................................8-10
8.3.4
Tag and Device Information.............................................................. 8-11
8.3.5
Unit.................................................................................................... 8-11
8.3.6
Range Change.................................................................................. 8-11
8.3.7
Output Signal Low Cut Mode Setup................................................. 8-11
8.3.8
Integral Indicator Scale Setup...........................................................8-12
8.3.9
Unit for Displayed Temperature........................................................8-12
8.3.10
Zero Point Adjustment and Span Adjustment...................................8-12
8.3.11
Software Write Protect......................................................................8-14
8.3.12
Switching to Deep Sleep Mode.........................................................8-14
8.3.13
Switching to Silence Mode................................................................8-14
8.4
Self-Diagnostics...............................................................................................8-15
8.4.1
Identify Problems by Using the Communicator................................8-15
8.4.2
Checking with Integral Indicator........................................................8-17
9.
Maintenance............................................................................................... 9-1
9.1
Overview.............................................................................................................9-1
9.2
Calibration Instruments Selection...................................................................9-1
9.3
Calibration..........................................................................................................9-1
9.4
Disassembly and Reassembly.........................................................................9-3
9.4.1
Replacing the Integral Indicator..........................................................9-3
9.4.2
Replacing the RF Assembly................................................................9-4
9.4.3
Replacing the CPU Assembly.............................................................9-4
9.4.4
Cleaning and Replacing the Capsule Assembly................................9-5
Replacing the Battery Pack................................................................9-5
9.4.6
Replacing the Batteries.......................................................................9-6
9.4.7
Handling Batteries...............................................................................9-6
9.5
Troubleshooting.................................................................................................9-7
9.5.1
Basic Troubleshooting........................................................................9-7
9.5.2
Troubleshooting Flowcharts................................................................9-8
9.5.3
Alarms and Countermeasures..........................................................9-10
10.
Parameter Summary............................................................................... 10-1
11.
General Specifications........................................................................... 11-1
11.1
Standard Specifications.................................................................................. 11-1
11.2
Model and Suffix Codes.................................................................................. 11-3
11.3
OPTIONAL SPECIFICATIONS......................................................................... 11-3
11.4
Dimensions....................................................................................................... 11-5
Revision Information................................................................................................i
Thank you for purchasing the DPharp EJX Absolute
and Gauge Pressure transmitter.
Your EJX Pressure Transmitter was precisely
calibrated at the factory before shipment. To ensure
both safety and efficiency, please read this manual
carefully before you operate the instrument.
NOTE
This manual covers the EJX510B absolute
pressure transmitter and EJX530B gauge
pressure transmitter.
Unless otherwise stated, the illustrations in
this manual are of the EJX530B differential
pressure transmitter. Users of the other models
should bear in mind that certain features of their
instrument will differ from those shown in the
illustrations of the EJX530B.
Model
EJX510B
EJX530B
Regarding This Manual
• This manual should be provided to the end
user.
• The contents of this manual are subject to
change without prior notice.
• All rights reserved. No part of this manual may
be reproduced in any form without Yokogawa’s
written permission.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited
to, implied warranty of merchantability and
fitness for a particular purpose.
• If any question arises or errors are found, or if
any information is missing from this manual,
please inform the nearest Yokogawa sales
office.
• The specifications covered by this manual are
limited to those for the standard type under the
specified model number break-down and do not
cover custom-made instruments.
• Please note that changes in the specifications,
construction, or component parts of the
instrument may not immediately be reflected
in this manual at the time of change, provided
that postponement of revisions will not cause
difficulty to the user from a functional or
performance standpoint.
• Yokogawa assumes no responsibilities for this
product except as stated in the warranty.
• If the customer or any third party is harmed by
the use of this product, Yokogawa assumes
no responsibility for any such harm owing to
any defects in the product which were not
predictable, or for any indirect damages.
• The following safety symbols are used in this
manual:
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death or serious
injury.
CAUTION
Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
injury or physical damage. It may also be used to
alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software
in this manner may damage it or lead to system
failure.
NOTE
Draws attention to information essential for
understanding the operation and features.
1.1 Safe Use of This Product
For the safety of the operator and to protect the
instrument and the system, please be sure to follow
this manual’s safety instructions when handling this
instrument. If these instructions are not heeded,
the protection provided by this instrument may be
impaired. In this case, Yokogawa cannot guarantee
that the instrument can be safely operated. Please
pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an
engineer or technician who has an expert
knowledge of this device. Operators are not
allowed to carry out installation unless they
meet this condition.
• With high process temperatures, care must
be taken not to burn yourself by touching the
instrument or its casing.
• Never loosen the process connector nuts when
the instrument is installed in a process. This can
lead to a sudden, explosive release of process
fluids.
• When draining condensate from the pressure
detector section, take appropriate precautions
to prevent the inhalation of harmful vapors and
the contact of toxic process fluids with the skin
or eyes.
• When removing the instrument from a
hazardous process, avoid contact with the fluid
and the interior of the meter.
• All installation shall comply with local installation
requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an
engineer or technician who has an expert
knowledge of this instrument. Operators are not
permitted to carry out wiring unless they meet
this condition.
(c) Maintenance
• Please carry out only the maintenance
procedures described in this manual. If you
require further assistance, please contact the
nearest Yokogawa office.
• Care should be taken to prevent the build up of
dust or other materials on the display glass and
the name plate. To clean these surfaces, use a
soft, dry cloth.
(d) Explosion Protected Type Instrument
• Users of explosion proof instruments should
refer first to Section 2.8 (Installation of an
Explosion-Protected Instrument) of this manual.
• The use of this instrument is restricted to those
who have received appropriate training in the
device.
• Take care not to create sparks when accessing
the instrument or peripheral devices in a
hazardous location.
• Repair or modification to this instrument by
customer will cause malfunction of explosion
protect function and hazardous situation. If you
need to repair or modification, please contact
the nearest Yokogawa office.
(e) Modification
• Yokogawa will not be liable for malfunctions or
damage resulting from any modification made
to this instrument by the customer.
WARNING
-
Do not loosen bolts or nuts used for
connecting impulse piping to the transmitter
pressure-detector section when they are
pressured because loosen bolts or nuts
causes spout of process liquid.
-
Take appropriate care to avoid contact with
the body or eyes, or inhalation of vapors
when venting or draining if the accumulated
liquid (or gas) is toxic or harmful.
-
Take appropriate care to avoid contact with
the body or eyes, or inhalation of vapors
when the transmitter is removed from
process for maintenance if process liquid is
toxic or harmful.
CAUTION
This instrument is certified as explosion
protected type instrument. Structure, installing
location, maintenance and repair of this
instrument are restricted. Violation of this
restriction causes hazardous situation. Users of
explosion proof type instruments should refer
first to section 2.8 “Installation of an Explosion-
Protected Instrument” of this manual.
1.2 Radio Wave
IMPORTANT
-
This instrument is equipped with a wireless
module which is designated as a certification
of construction type as a wireless
facility for 2.4 GHz band low-power data
communication system of the Radio Act.
Refer to 2.12 “Regulatory Compliance for
Radio and Telecommunication” for detail.
-
Due to the designated certification of
construction type, users may be subject to
legal punishment in case of:
- Disassembling or modifying the wireless
module or antenna in this instrument
- Peeling off the certification label attached
to the wireless module in this instrument
-
Preventing interference with other wireless
stations
The operating frequency bandwidth of this
instrument may overlap the same range
as industrial devices, scientific devices,
medical devices, microwave ovens, licensed
premises radio stations and non-licensed
specified low-power radio stations for mobile
object identification systems used in factory
production lines.
Before using this instrument, ensure that
neither a premises radio station nor specified
low power radio station for mobile object
identification systems is in use nearby.
If this instrument causes radio wave
interference to a wireless station for mobile
object identification systems, promptly
change the frequency being used or turn
off the source of radio wave emissions.
Then, contact a Yokogawa office regarding
countermeasures to prevent interference,
such as setting up partitions.
1.3 Warranty
• The warranty shall cover the period noted on
the quotation presented to the purchaser at the
time of purchase. Problems occurring during
the warranty period shall basically be repaired
free of charge.
• If any problems are experienced with this
instrument, the customer should contact the
Yokogawa representative from which this
instrument was purchased or the nearest
Yokogawa office.
• If a problem arises with this instrument,
please inform us of the nature of the problem
and the circumstances under which it
developed, including the model specification
and serial number. Any diagrams, data and
other information you can include in your
communication will also be helpful.
• The party responsible for the cost of fixing the
problem shall be determined by Yokogawa
following an investigation conducted by
Yokogawa.
• The purchaser shall bear the responsibility for
repair costs, even during the warranty period, if
the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in
accordance with the design specifications.
- Use of the product in question in a location
not conforming to the standards specified by
Yokogawa, or due to improper maintenance
of the installation location.
- Failure or damage due to modification or
repair by any party except Yokogawa or an
approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after
delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.
1.4 Trademarks
In this document, trademarks or registered
trademarks are not marked with “™” or “®”.
Product names and company names in this
document are trademarks or registered trademarks
of the respective companies.
1.5 ATEX Documentation
This is only applicable to the countries in European Union.
GB
DK
I
E
NL
SF
P
F
D
S
LT
LV
PL
EST
SLO
H
BG
RO
M
CZ
SK
GR
<2. Handling Cautions>
2-1
IM 01C27F01-01EN
2.
Handling Cautions
This chapter provides important information on how
to handle the transmitter. Read this carefully before
using the transmitter.
EJX Series transmitters are thoroughly tested at the
factory before shipment. When taking delivery of an
instrument, visually check them to make sure that
no damage occurred during shipment.
Also check that all transmitter mounting hardware
and a bar magnet shown in figure 2.1 is included.
If the transmitter is ordered without the mounting
bracket and the process connector, the transmitter
mounting hardware will not be included. After
checking the transmitter, carefully repack it in its
box and keep it there until you are ready to install it.
U-bolt Nut (L type)
Mounting bracket
U-bolt (L type)
U-bolt (S type)
U-bolt Nut
(S type)
F0201.ai
Figure 2.1
Transmitter Mounting Hardware
2.1 Model and Specifications
Check
The model name and specifications are written on
the name plate attached to the case.
: Refer to USER'S MANUAL.
Made in Japan
TOKYO 180-8750 JAPAN
MODEL
SUFFIX
SUPPLY
OUTPUT
MWP
mA DC
V DC
STYLE
CAL
RNG
NO.
F0202.ai
Figure 2.2
Name Plate
2.2 Unpacking
Keep the transmitter in its original packaging to
prevent it from being damaged during shipment.
Do not unpack the transmitter until it reaches the
installation site.
2.3 Storage
The following precautions must be observed when
storing the instrument, especially for a long period.
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or subject to water
seepage/leaks.
• Vibration and shock are kept to a minimum.
• It has an ambient temperature and relative
humidity within the following ranges.
• For maximum battery life, storage
temperature should not exceed 30°C.
Ambient temperature:
–40 to 85°C without integral indicator
–30 to 80°C with integral indicator
Relative humidity:
0% to 100% R.H.
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it carefully in
the packaging that it was originally shipped with.
(c) If the transmitter has been used, thoroughly
clean the chambers inside the cover flanges, so
that there is no process fluid remaining inside.
Before placing it in storage, also make sure that
the pressure-detector is securely connected to
the transmitter section.
NOTE
When storing the instrument with a battery
pack, it is recommended to put the instrument in
Deep Sleep mode to conserve the batteries. For
details on how to switch to Deep Sleep mode,
refer to subsection 8.3.12 “Switching to Deep
Sleep Mode”.
<2. Handling Cautions>
2-2
IM 01C27F01-01EN
2.4 Selecting the Installation
Location
The transmitter is designed to withstand severe
environmental conditions. However, to ensure
that it will provide years of stable and accurate
performance, take the following precautions when
selecting the installation location.
(a) Wireless Communication
The installation location of this transmitter must
meet the following conditions:
- Adjust the direction of the antenna to be
in the upright position regardless of the
orientation of this transmitter. See section 4
for adjusting the antenna.
- Install the transmitter at least 1.5m above the
ground or floor.
F0203.ai
1.5m or over
- Ensure that there are no obstacles such as
walls or pipes within a 30-cm radius of each
antenna.
- Confirm that each field wireless equipment
compliant with ISA100.11a can see the
antenna of other devices which locate within
its own communication range. In the star
topology network, the visibility to the antenna
of gateway is a mandatory clause.
(b) Ambient Temperature
Avoid locations subject to wide temperature
variations or a significant temperature gradient.
If the location is exposed to radiant heat from
plant equipment, provide adequate thermal
insulation and/or ventilation.
(c) Ambient Atmosphere
Do not install the transmitter in a corrosive
atmosphere. If this cannot be avoided, there
must be adequate ventilation.
(d) Shock and Vibration
Although the transmitter is designed to be
relatively resistant to shock and vibration, an
installation site should be selected where this is
kept to a minimum.
(e) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is
certified for installation in a hazardous area
containing specific gas types. See subsection
2.8 “Installation of an Explosion-Protected
Transmitters.”
2.5 Pressure Connection
WARNING
• Never loosen the process connector bolts
when an instrument is installed in a process.
The device is under pressure, and a loss of
seal can result in a sudden and uncontrolled
release of process fluid.
• When draining toxic process fluids that have
condensed inside the pressure detector,
take appropriate steps to prevent the contact
of such fluids with the skin or eyes and the
inhalation of vapors from these fluids.
The following precautions must be observed
in order to safely operate the transmitter under
pressure.
(a) Make sure that all the process connector bolts
are tightened firmly.
(b) Make sure that there are no leaks in the impulse
piping.
(c) Never apply a pressure higher than the
specified maximum working pressure.
<2. Handling Cautions>
2-3
IM 01C27F01-01EN
2.6 Restrictions on Use of Radio
Transceivers
IMPORTANT
Although the transmitter has been designed to
resist high frequency electrical noise, if a radio
transceiver is used near the transmitter or its
external wiring, the transmitter may be affected
by high frequency noise pickup. To test this, start
out from a distance of several meters and slowly
approach the transmitter with the transceiver
while observing the measurement loop for noise
effects. Thereafter use the transceiver outside
the range where the noise effects were first
observed.
2.7 Insulation Resistance and
Dielectric Strength Test
Since the transmitter has undergone insulation
resistance and dielectric strength tests at the factory
before shipment, normally these tests are not
required. If the need arises to conduct these tests,
heed the following:
(a) Do not perform such tests more frequently than
is absolutely necessary. Even test voltages that
do not cause visible damage to the insulation
may degrade the insulation and reduce safety
margins.
(b) Never apply a voltage exceeding 500 V DC
(100 V DC with an internal lightning protector)
for the insulation resistance test, nor a voltage
exceeding 500 V AC (100 V AC with an internal
lightning protector) for the dielectric strength
test.
(c) The procedure for conducting these tests is as
follows:
•
Insulation Resistance Test
1) Remove the battery pack. See subsection 9.4.5
for details on how to remove it.
2) Short-circuit the battery connection terminals in
the terminal box.
3) Turn OFF the insulation tester. Then connect
the insulation tester plus (+) lead wire to the
shorted battery connection terminals and the
minus (–) leadwire to the grounding terminal.
4) Turn ON the insulation tester power and
measure the insulation resistance. The voltage
should be applied as briefly as possible to verify
that the insulation resistance is at least 20 MΩ.
5) After completing the test and being very careful
not to touch exposed conductors disconnect the
insulation tester and connect a 100 kΩ resistor
between the grounding terminal and the short-
circuiting battery connection terminals. Leave
this resistor connected at least one second to
discharge any static potential. Do not touch the
terminals while it is discharging.
NOTE
When storing the instrument with a battery
pack, it is recommended to put the instrument in
Deep Sleep mode to conserve the batteries. For
details on how to switch to Deep Sleep mode,
refer to subsection 8.3.12 “Switching to Deep
Sleep Mode”.
•
Dielectric Strength Test
1) Remove the battery pack. See subsection 9.4.5
for details on how to remove it.
2) Short-circuit the battery connection terminals in
the terminal box.
3) Turn OFF the dielectric strength tester. Then
connect the tester between the shorted battery
connection terminals and the grounding
terminal. Be sure to connect the grounding lead
of the dielectric strength tester to the ground
terminal.
4) Set the current limit on the dielectric strength
tester to 10 mA, then turn ON the power and
gradually increase the test voltage from ‘0’ to
the specified voltage.
5) When the specified voltage is reached, hold it
for one minute.
6) After completing this test, slowly decrease the
voltage to avoid any voltage surges.
NOTE
When storing the instrument with a battery
pack, it is recommended to put the instrument in
Deep Sleep mode to conserve the batteries. For
details on how to switch to Deep Sleep mode,
refer to subsection 8.3.12 “Switching to Deep
Sleep Mode”.
<2. Handling Cautions>
2-4
IM 01C27F01-01EN
2.8 Installation of an Explosion-
Protected Instrument
If a customer makes a repair or modification to an
intrinsically safe instrument and the instrument is
not restored to its original condition, its intrinsically
safe construction may be compromised and the
instrument may be hazardous to operate. Please
contact Yokogawa before making any repair or
modification to an instrument.
CAUTION
This instrument has been tested and certified
as being intrinsically safe. Please note that
severe restrictions apply to this instrument’s
construction, installation, external wiring,
maintenance and repair. A failure to abide by
these restrictions could make the instrument a
hazard to operate.
2.8.1 FM Approval
Caution for FM intrinsically safe type. (Following
contents refer “DOC. No. IFM037-A20”)
Note 1. Model EJX Series Differential, gauge
and absolute pressure transmitters with
optional code /FS17 are applicable for use
in hazardous locations.
• Applicable Standard: FM3600, FM3610,
FM3611, FM3810
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D. Class II, Division 1,
Groups E, F & G and Class III, Division 1,
Class I, Zone 0 in Hazardous Locations, AEx
ia IIC
• Nonincendive for Class I, Division 2, Groups
A, B, C & D. Class II, Division 2, Groups F &
G and Class III, Division 1, Class I, Zone 2,
Groups IIC, in Hazardous Locations.
• Enclosure: NEMA 4X (Indoors and outdoors)
• Temperature Class: T4
• Ambient temperature: -50 to 70°C
Note 2. Installation
• Installation should be in accordance with
ANSI/ISA RP12.6 “Installation of Intrinsically
Safe Systems for Hazardous (Classified)
Locations” and the National Electric Code
(ANSI/NFPA 70).
• Dust-tight conduit seal must be used when
installed in a Class II, III, Group E, F and G
environments.
• Note a warning label worded
“SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY,” and
“INSTALL IN ACCORDANCE WITH DOC.
No. IFM037-A20”.
Note 3. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void
Factory Mutual Intrinsically safe and
Nonincendive Approval.
Transmitter
Hazardous Location
[Intrinsically Safe]
Class I, II, III, Division 1,
Groups A,B,C,D,E,F,G
Class I, Zone 0
in Hazardous (Classified)
Locations
AEx ia IIC
[Nonincendive]
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Class I, Zone 2, Group IIC,
in Hazardous (Classified)
Locations
F0204.ai
Note 4. Battery Pack
USE ONLY YOKOGAWA BATTERY PACK
F9915MA or F9915NS.
Note 5. Special Conditions for safe use
POTENTIAL ELECTROSTATIC CHARGING
HAZARD-SECURE DISTANCE OF 100MM
FROM ANTENNA.
DO NOT OPEN WHEN CL II, III, DIV 1,2
ATMOSPHERE IS PRESENT.
<2. Handling Cautions>
2-5
IM 01C27F01-01EN
2.8.2 CSA Certification
Caution for CSA Intrinsically safe type. (Following
contents refer to “DOC No. ICS030”)
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with
optional code /CS17 are applicable for use
in hazardous locations
Certificate: 2325443
[For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2
No.0.4, C22.2 No.25, C22.2 No.94, C22.2
No.157, C22.2 No.213, C22.2 No.61010-1
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1,
Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division2,
Groups A, B, C&D, Class II, Division2,
Groups F&G, Class III, Division1
• Enclosure: Type 4X,
• Temp. Code: T4
• Amb. Temp.:-50 to 70°C
• Process Temperature: 120°C max.
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-0,
CAN/CSA E60079-11, IEC 60529:2001-02
• Ex ia IIC T4
• Ambient Temperature: -50 to 70°C
• Max. Process Temp.: 120°C
• Enclosure: IP66 and 67
Note 2. Installation
• Installation should be in accordance with
Canadian Electrical Code Part I and Local
Electrical Code.
• Do not alter drawing without authorization
from CSA.
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation of America is prohibited and will
void Canadian Standards Intrinsically safe
and nonincendive Certification.
Transmitter
Hazardous Location
[Intrinsically Safe]
Group IIC, Zone 0
Class I, II, III, Division 1,
Groups A,B,C,D,E,F,G
[Nonincendive]
Class I, II, Division 2,
Groups A,B,C,D,F,G
Class III, Division 1
F0205.ai
Note 3. Battery Pack
• Use only YOKOGAWA battery pack
F9915MA or F9915NS.
Note 4. Special Conditions for safe use
• Potential electrostatic charging hazard -
secure distance of 100mm from antenna.
2.9 EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in
industrial locations), EN61326-2-3
CAUTION
This instrument is a Class A product, and it is
designed for use in the industrial environment.
Please use this instrument in the industrial
environment only.
2.10 Pressure Equipment
Directive (PED)
(1) General
• EJX Series pressure transmitters are
categorized as pressure accessories under
the vessel section of directive 97/23/EC, which
corresponds to Article 3, Paragraph 3 of PED,
denoted as Sound Engineering Practice (SEP).
• EJX110B-MS, EJX110B-HS,
EJX110B-VS, EJX510B-D, and
EJX530B-D can be used above 200 bar and
therefore considered as a part of a pressure
retaining vessel where category III, Module H
applies. These models with option code /PE3
conform to that category.
<2. Handling Cautions>
2-6
IM 01C27F01-01EN
(2) Technical Data
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas
Group of fluid: 1 and 2
Model
Capsule
code
PS
(bar)*1
V(L)
PS·V
(bar·L)
Category*2
EJX110B
L
160
0.01
1.6
Article 3,
Paragraph 3
(SEP)
M, H, V
250
0.01
2.5
EJX110B
with code
/PE3
M, H, V
250
0.01
2.5
III
EJX310B
L, M, A, B
160
0.01
1.6
Article 3,
Paragraph 3
(SEP)
EJX430B
H, A, B
160
0.01
1.6
Article 3,
Paragraph 3
(SEP)
EJX510B
A, B, C
100
0.1
10
Article 3,
Paragraph 3
(SEP)
D
700
0.1
70
EJX510B
with code
/PE3
D
700
0.1
70
III
EJX530B
A, B, C
100
0.1
10
Article 3,
Paragraph 3
(SEP)
D
700
0.1
70
EJX530B
with code
/PE3
D
700
0.1
70
III
*1:
PS is maximum allowable pressure for vessel itself.
*2:
Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
(3) Operation
CAUTION
• The temperature and pressure of fluid should
be maintained at levels that are consistent
with normal operating conditions.
• The ambient temperature should be
maintained at a level that is consistent with
normal operating conditions.
• Please take care to prevent water hammer
and the like from inducing excessive
pressures in pipes and valves. If phenomena
are likely, install a safety valve or take
some other appropriate measure to prevent
pressure from exceeding PS.
• Take appropriate measures at the device or
system level to protect transmitters if they
are to be operated near an external heat
source.
2.11 Low Voltage Directive
Applicable standard: EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to
which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is
adhering. " 2 " applies to normal indoor
atmosphere. Normally, only non-conductive
pollution occurs. Occasionally, however,
temporary conductivity caused by condensation
must be expected.
(2) Installation Category I
"Overvoltage category (Installation category)"
describes a number which defines a transient
overvoltage condition. It implies the regulation
for impulse withstand voltage. " I " applies to
electrical equipment which is supplied from the
circuit when appropriate transient overvoltage
control means (interfaces) are provided.
<2. Handling Cautions>
2-7
IM 01C27F01-01EN
2.12 Regulatory Compliance
for Radio and
Telecommunication
Please confirm that a installation region fulfills a
standards, require additional regulatory information
and approvals, contact to Yokogawa Electric
Corporation.
2.12.1 Radio and Telecommunications
Terminal Equipment Directive
(R&TTE)
We, Yokogawa Electric Corporation hereby declare
that this equipment, model EJX-L series is in
compliance with the essential requirements and
other relevant provisions of Directive 1999/5/EC.
The CE declaration of conformity for R&TTE for this
product can be found at http://www.yokogawa.com/
fld/
NOTE
France restricts outdoor use to 10mW
(10dBm) EIRP in the frequency range of 2,454
- 2,483.5MHz. Installation in France must
configure the network with configuration tool
not to use channel 10 to 14. To configure the
network, refer to IM 01W01F01-01EN.
2.12.2 FCC compliance
This device complies with Part 15 of FCC Rules.
Operation is subject to the following two conditions:
(1) this device may not cause interference, and (2)
this device must accept any interference, including
interference that may cause undesired operation of
this device.
Co-located:
This transmitter must not be co-located or operated
in conjunction with any other antenna or transmitter.
FCC WARNING:
Changes or modifications not expressly approved
by the party responsible for compliance could void
the user’s authority to operate the equipment.
NOTE
This equipment has been tested and found
to comply with the limits for a Class A digital
device, pursuant to part 15 of he FCC Rules.
These limits are designed to provide reasonable
protection against harmful interference when
the equipment is operated in a commercial
environment.
This equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual,may cause harmful interference to radio
communications. Operation of this equipment
in a residential area is likely to cause harmful
interference in which case the user will be
required to correct the interference at his own
expense.
2.12.3 Industry Canada (IC) compliance
This Class A digital apparatus complies with
Canadian ICES-003.
French: Cet appareil numérique de la classe A est
conforme à la norme NMB-003 du Canada.
Operation is subject to the following two conditions:
(1) this device may not cause interference, and (2)
this device must accept any interference, including
interference that may cause undesired operation of
the device.
<3. Component Names>
3-1
IM 01C27F01-01EN
3.
Component Names
WR E
D
F0301.ai
H
L
E
D
H
L
E
D
YES (Note 2)
(Write disabled)
NO
(Write enabled)
Zero-adjustment
screw
Ground terminal
RF assembly
CPU assembly
Not in use
Write protection switch
Transmitter
section
Amplifier Cover
Mounting
screw
Integral
indicator
Slide
switch
Hardware write protection switch (WR)
Write Protection
Write Protection
Switch Position
(Note 1)
Pressure-detector
section
Note 1:
Set the switch as shown in the figure above to set the write protection. The hardware write protection switch is set to E side. Set
to H side for the switch of not-in-use.
Note 2:
When the switch is D side (write protection setting), provisioning is acceptable. For details of provisioning, refer to section 7.4 “
Connecting to the Field Wireless Network “.
Figure 3.1
Component Names
Table 3.1
Display Symbol
Display Symbol
Meaning of Display Symbol
▲
The output signal being zero-adjusted is increasing.
▼
The output signal being zero-adjusted is decreasing.
Write protect function is enabled.
Before installing the transmitter, read the cautionary
notes in section 2.4, “Selecting the Installation
Location.” For additional information on the ambient
conditions allowed at the installation location, refer
to section11.1 “Standard Specifications.”
NOTE
To connect this transmitter to the Field Wireless
Network, information for connecting to the field
wireless devices needs to be set beforehand.
Refer to 7.4 “Connecting to the Field Wireless
Network.”
IMPORTANT
• When welding piping during construction,
take care not to allow welding currents to
flow through the transmitter.
• Do not step on this instrument after
installation.
• For the EJX530B whose capsule code is A,
B or C, the pipe of the atmospheric opening
is located on the pressure detecting section.
The opening must not face upward. See
subsection 5.1.1.
• D capsule of EJX530B is of sealed gauge
reference and the change in atmospheric
pressure may affect the measurement.
4.2 Mounting
■
The impulse piping connection port of the
transmitter is covered with a plastic cap to
protect against dust. This cap must be removed
before connecting the piping. (Be careful not
to damage the threads when removing these
caps. Do not insert a screw driver or other
tool between the cap and the port threads to
remove the cap.)
■
The transmitter can be mounted on a nominal
50 mm (2-inch) pipe using the mounting bracket
supplied, as shown in Figure 4.1.
■
The user should prepare the mating gasket for
the transmitters with Process connection code
8 and 9. See Figure 4.2.
Horizontal pipe mounting
F0401.ai
Vertical pipe mounting
50 mm (2-inch) pipe
U-bolt (L)
U-bolt (S)
Mounting bracket
U-bolt nut (S)
U-bolt nut (L)
U-bolt nut (L)
Mounting bracket
50 mm (2-inch) pipe
U-bolt (L)
U-bolt (S)
U-bolt nut (S)
Figure 4.1
Transmitter Mounting
Gasket
F0402.ai
Figure 4.2
Gasketing
Tighten the hexagonal nut part of the capsule
assembly. See Figure 4.3.
F0403.ai
Capsule assembly
Figure 4.3
Tightening Transmitter
4.3 Rotating Transmitter Section
WARNING
Intrinsic safe type transmitters must be, as a rule,
do not rotate transmitter section if it is powered.
In case you need to rotate when the transmitter
is powered, using gas detector and confirm no
existence of explosive gas before rotating.
The transmitter section can be rotated
approximately 360° (180° to either direction or
360° to one direction from the original position at
shipment, depending on the configuration of the
instrument.) It can be fixed at any angle within
above range.
1) Remove the five setscrews that fasten the
transmitter section and capsule assembly,
using the Allen wrench.
2) Rotate the transmitter section slowly and stop
it at designated position. For the EJX530B
whose capsule code is A, B or C, the pipe of
the atmospheric opening may interfere with
the stopper and disturb further rotation. In that
case, screw off the pipe first, rotate the housing,
and then screw in the pipe by hand again.
3) Tighten the five setscrews to a torque of 1.5
N·m.
IMPORTANT
Do not rotate the transmitter section more than
the above limit.
Stopper
Setscrew
Transmitter section
Pressure-detector section
F0404.ai
Figure 4.4
Rotating Transmitter Section
4.4 Changing the Direction of
Integral Indicator
WARNING
Intrinsic safe type transmitters must be, as a
rule, remove a battery pack in non-hazardous
area before open/close the Amplifier Cover or
disassembling and reassembling the Integral
Indicator.
An integral indicator can be installed in the following
three directions. Follow the instructions in section
9.4.1 for removing and attaching the integral
indicator.
4.5 Changing the direction of
the antenna
Adjust the direction of the antenna to be in the
upright position. Figure 4.5 show factory setup
antenna position. If the transmitter is installed to
horizontal impulse piping, follow the procedure
below and change the antenna position.
1) Loosen the two mounting screws at the bottom
of the antenna by using a 2.5mm Allen wrench
(see Figure 4.5).
2) Press forward and down 90 degrees by rotating
the axis at the bottom of the antenna.
3) Tighten the two screws to a torque of 1.5 N-m
by using a torque wrench. When doing this, be
careful not leave a gap between the antenna
and housing.
F0405.ai
Figure 4.5
Mounting Screw Position
F0406.ai
Figure 4.6
Adjusting Antenna Position
<5. Installing Impulse Piping>
5-1
IM 01C27F01-01EN
5.
Installing Impulse Piping
5.1 Impulse Piping Installation
Precautions
The impulse piping that connects the process
outputs to the transmitter must convey the process
pressure accurately. If, for example, gas collects in
a liquidfilled impulse line, or the drain for a gas-filled
impulse line becomes plugged, it will not convey the
pressure accurately. Since this will cause errors in
the measurement output, select the proper piping
method for the process fluid (gas, liquid, or steam).
Pay careful attention to the following points when
routing the impulse piping and connecting the
impulse piping to a transmitter.
5.1.1 Connecting Impulse Piping to a
Transmitter
IMPORTANT
The transmitter can be installed in horizontal
impulse piping configuration, tilting the
transmitter's position up to 90°. When tilting,
observe that the pipe (for Model EJX530A
with measurement span code A, B, and C) is
positioned horizontal downwards, or any place
between them, as shown in Figure 5.1 The
zero-adjustment screw must be positioned
downwards for all the models.
F0501.ai
Zero-adjustment screw
Pipe
(backside of the instrument)
The pipe (open to atmosphere) is positioned horizontal.
If the zero-adjustment screw is positioned other than
downwards after installation, rotate the housing until it is
positioned downwards.
Figure 5.1
Horizontal Impulse Piping Connection
5.1.2 Routing the Impulse Piping
(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous
material in the process piping gets into the impulse
piping, pressure measurement errors may result. To
prevent such problems, the process pressure taps
must be angled as shown in figure 5.2 according to
the kind of fluid being measured.
NOTE
• If the process fluid is a gas, the taps must be
vertical or within 45° either side of vertical.
• If the process fluid is a liquid, the taps must
be horizontal or below horizontal, but not
more than 45° below horizontal.
• If the process fluid is steam or other
condensing vapor, the taps must be
horizontal or above horizontal, but not more
than 45° above horizontal.
[Gas]
Pressure
taps
Process
piping
[Steam]
[Liquid]
45°
45°
45°
45°
45°
45°
F0502.ai
Figure 5.2
Process Pressure Tap Angle
(For Horizontal Piping)
(2) Position of Process Pressure Taps and
Transmitter
If condensate (or gas) accumulates in the impulse
piping, it should be removed periodically by
opening the drain (or vent) plugs. However, this will
generate a transient disturbance in the pressure
measurement, and therefore it is necessary to
position the taps and route the impulse piping so
that any extraneous liquid or gas generated in the
leadlines returns naturally to the process piping.
• If the process fluid is a gas, then as a rule the
transmitter must be located higher than the
process pressure taps.
• If the process fluid is a liquid or steam, then as a
rule the transmitter must be located lower than
the process pressure taps.
<5. Installing Impulse Piping>
5-2
IM 01C27F01-01EN
(3) Impulse Piping Slope
The impulse piping must be routed with only an
upward or downward slope. Even for horizontal
routing, the impulse piping should have a slope of
at least 1/10 to prevent condensate (or gases) from
accumulating in the pipes.
(4) Preventing Freezing
If there is any risk that the process fluid in the
impulse piping or transmitter could freeze, use a
steam jacket or heater to maintain the temperature
of the fluid.
NOTE
After completing the connections, close the
valves on the process pressure taps (main
valves), the valves at the transmitter (stop
valves), and the impulse piping drain valves,
so that condensate, sediment, dust and other
extraneous material cannot enter the impulse
piping.
5.2 Impulse Piping Connection
Examples
Figure 5.3 shows examples of typical impulse
piping connections. Before connecting the
transmitter to the process, study the transmitter
installation location, the process piping layout,
and the characteristics of the process fluid
(corrosiveness, toxicity, flammability, etc.), in order
to make appropriate changes and additions to the
connection configurations.
Note the following points when referring to these
piping examples.
• If the impulse line is long, bracing or supports
should be provided to prevent vibration.
• The impulse piping material used must
be compatible with the process pressure,
temperature, and other conditions.
• A variety of process pressure tap valves (main
valves) are available according to the type
of connection (flanged, screwed, welded),
construction (globe, gate, or ball valve),
temperature and pressure. Select the type of
valve most appropriate for the application.
F0503.ai
Tee
Stop
valve
Stop
valve
Drain valve
Drain plug
Union
or
flange
Union
or
flange
Tap valve
Figure 5.3
Impulse Piping Connection Examples
Always ground the transmitter case in accordance
with national and local electrical codes. The most
effective transmitter case grounding method is
a direct connection to earth ground with minimal
impedance.
F0601.ai
Ground terminal
Figure 6.1
Ground Terminal
CAUTION
Grounding is recommended for safe operation.
7.1 Preparation for Starting
Operation
This section describes the operation procedure for
the EJX530B as shown in figure 7.1.
NOTE
It is required to set security and network
information to enable the transmitter to be
connected to the Field Wireless Network. For
more details, refer to section 7.4 “Connecting to
the Field Wireless Network”.
NOTE
Check that the process pressure tap valves,
drain valves, and stop valves are closed.
(a) Follow the procedures below to introduce
process pressure into the impulse piping and
transmitter.
1) Open the tap valve (main valve) to fill the
impulse piping with process fluid.
2) Gradually open the stop valve to introduce
process fluid into the transmitter pressure-
detector section.
3) Confirm that there is no pressure leak in
the impulse piping, transmitter, or other
components.
(b) Turn on the power and connect the Field
Wireless Devices to the field wireless network.
(c) Using the configuration tool, confirm that
the transmitter is operating properly. Check
parameter values or change the setpoints as
necessary.
Integral Indicator’s indication can be used
to confirm that the transmitter is operating
properly. For details on how to confirm refer to
subsection 8.4 “Self-Diagnostics”.
ISA100 devices display self-diagnostic
information in an easy-to-understand manner
using four categories (Check function,
Maintenance required, Failure, and Off
specification) according to NAMUR NE107*
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field
Devices”
F0701.ai
Union or flange
Vent plug (Fill plug)
Tap valve
Stop valve
Tee
Drain valve
Drain plug
Union or flange
Figure 7.1
Liquid Pressure Measurement
(Gauge Pressure Transmitters)
■
Confirm that transmitter is operating
properly by Integral Indicator
If the transmitter is faulty, an error code is displayed.
F0702.ai
Self-diagnostic error on the integral
indicator (Faulty transmitter)
Figure 7.2
Integral Indicator with Error Code
NOTE
If any of the above errors are indicated on
the display of the integral indicator or the
configuration tool, refer to subsection 9.5.3 for
the corrective action.
Verify and Change Transmitter
Parameter Setting and Values
The parameters related to the following items are
minimum required to be set for operation, and set at
factory as specified in order. Confirm or change the
parameters if needed.
• Measurement range (measurement lower/
upper limit, unit)
7.2 Zero Point Adjustment
After completing preparations for operating the
transmitter, adjust the zero point. There are two
zero point adjusting ways.
IMPORTANT
Do not turn off the power to the transmitter
immediately after performing a zero point
adjustment. Powering off within 30 seconds of
performing this procedure will return the zero
point to its previous setting.
(1) When you can obtain the Low Range Value
from the actual measured value of 0%
(0kPa, atmospheric pressure);
Using the transmitter’s zero-adjustment
screw
Before adjusting zero point, make sure followings.
• That the External zero trim parameter
(EXTERNAL_ZERO_TRIM) is “Trim on”. For
details, refer to section 8 “Setting Parameters”.
• Use a slotted screwdriver to turn the zero-
adjustment screw. Turn the screw clockwise
to increase the output or counterclockwise to
decrease the output.
The zero point adjustment can be made with
a resolution of 0.01% of the setting range. The
degree of zero adjustments varies with the screw
turning speed turn the screw slowly to make a fine
adjustment, quickly to make a rough adjustment.
IMPORTANT
When zeroing with the zero-adjustment screw,
turn the screw firmly until ▲ or ▼ mark is
displayed on the integral indicator since there
exists mechanical dead-band of the screw.
Using the Configuration Tool
Refer to subsection 8.3.10 “Zero Point Adjustment
and Span Adjustment”.
(2) When you cannot obtain the Low Range
Value from the actual measured value of
0%;
Adjust the transmitter output value matches to
the actual measured value obtained by precise
pressure measurement equipment.
[Example]
The measuring range of 50 to 250 kPa : the actual
measured value of 130kPa.
130–50
250–50
Actual measured value=
x100=40.0%
Using the transmitter’s zero-adjustment
screw
Turn the zero adjustment screw to adjust the
transmitter.
Using the Configuration Tool
Refer to subsection 8.3.10 “Zero Point Adjustment
and Span Adjustment”.
7.3 Starting Operation
After the zero point adjustment is completed, the
transmitter is already the operating status. Follow
the procedure below.
1) Confirm the operating status. If the output
signal exhibits wide fluctuations (hunting) due to
periodic variation in the process pressure, use
the communicator to dampen the transmitter
output value. Confirm the hunting using a
receiving instrument or the integral indicator, set
the suitable damping time constant.
2) After confirming the operating status, perform
the following.
IMPORTANT
• Close the terminal box cover and the
amplifier cover. Screw each cover in tightly
until it will not turn further.
• Tighten the zero-adjustment cover mounting
screw to secure the cover.
7.4 Connecting to the Field
Wireless Network
■
Preparation work prior to connecting to a
Field Wireless Network
This transmitter does not need to be connected
with a physical wire. Instead of physical wiring, it
is necessary to set the field wireless devices to
communicate with before installing the transmitter.
This transmitter supports provisioning via infrared
communication using a provisioning device and
can be securely connected to a network. If the
provisioning information is not set, the transmitter
cannot be connected to the field wireless network.
Provisioning:
Provisioning is work to set the security and
network information to enable the transmitter to
be connected to the field wireless network. This
transmitter supports a provisioning method:
the OOB (out-of-band) method using infrared
communication.
For details on provisioning using a provisioning
device, and procedure for connecting the
transmitter to the Field Wireless Network, refer
to the User’s Manual, YFGW710 Field Wireless
Integrated Gateway (IM 01W01F01-01EN).
F0703.ai
within 30cm
Figure 7.3
Provisioning Example
■
Provisioning work
This subsection describes provisioning work using
FieldMate as the provisioning device.
Provisioning work performs provisioning for
each field wireless device using FieldMate and
an infrared adapter. If Yokogawa-recommended
infrared device is used for provisioning, distance
between the transmitter glass window and the
infrared device should be within 30cm. For details of
Yokogawa-recommended infrared device, refer to
subsection 9.2 “Calibration Instruments Selection”.
Perform the following provisioning tasks.
• Setting provisioning information
• Creating a provisioning information file
1) Setting provisioning information
Set the device tag and network ID using a
FieldMate provisioning function. The device
tag, network ID, and join key are set in the Field
Wireless Device. It is not necessary to input
a join key because FieldMate automatically
generates it.
Setting device tag
The device tag is used for the user to
recognize the Field Wireless Device.
Setting network ID
This is the network ID for the field wireless
network to which the field wireless device is
connected. Set a value from 2 to 65535.
The field wireless device is connected to the
field wireless network corresponding to the
network ID set by provisioning work.
2) Creating a provisioning information file
The following provisioned information is stored
in the provisioning information file.
• Network ID
• Device tag
• EUI64
• Join key
• Provisioner (name of the user who performed
provisioning work by FieldMate)
• Date (Time and date when provisioning was
performed by FieldMate)
This provisioning information file is required to
load from the Field Wireless Configurator to the
Field Wireless Integrated Gateway. Store the
file carefully.
Connecting to a field wireless network
The action after installing the battery pack varies
depending on the silence setting.
In case of factory setting, mounting the battery pack
automatically starts a search for the field wireless
network. When the Field Wireless Integrated
Gateway is found, the instrument enters the join
status.
When the Field Wireless Integrated Gateway is not
found and a specified time has elapsed, a cycle of a
one-hour pause and six-minutes search is repeated
until the instrument can join the field wireless
network.
For details on the procedure to switch to silence
mode, refer to subsection 8.3.13 “Switching to
Silence Mode.”
Boot
Ready
and pause
Deep Sleep
Ready
Confirm
connecting status
Join
(Disconnect)
(Connect)
(Search failure)
(Search start)
(Search start)
Silence mode OFF
Silence mode ON
Configuration Tool
Configuration Tool
(Search failure)
F0704.ai
Mounting battery pack
Figure 7.4
Wireless Connection Process
NOTE
If the transmitter searches the Field Wireless
Network for long time at low ambient
temperature condition, sometimes error “AL.70
LOW.BAT” is displayed on the Integral Indicator.
Even though using new batteries, it can occur. It
occurs because of battery characteristics. After
joining to the Field Wireless Network, this error
will be cleared within one hour if battery has no
failure.
7.5 Shutting Down the
Transmitter
Shut down the transmitter as follows.
1) Remove the battery pack or set the transmitter
to deep sleep mode by the Configuration Tool.
2) Close the low pressure stop valve.
3) Open the equalizing valve.
4) Close the high pressure stop valve.
5) Close the high pressure and low pressure tap
valves.
NOTE
• Whenever shutting down the transmitter for
a long period, remove the process line that is
in the transmitter.
• The equalizing valve must be left OPEN.
• Refer to subsection 9.4.5 “Replacing the
Battery Pack” for the battery pack removing.
• When storing the instrument with a battery
pack inserted, it is recommended to put the
instrument into deep sleep mode to conserve
battery power. For details on how to switch to
deep sleep mode, refer to subsection 8.3.12
“Switching to the Deep Sleep Mode.”
<8. Setting Parameters>
8-1
IM 01C27F01-01EN
8.
Setting Parameters
This transmitter can remotely handle range
changes, Tag No. setup, monitoring of self-
diagnostic results, and Zero-Point Adjustment, etc.
according to communication with a configuration
tool.
8.1 Environment for parameter
setting
After installing the battery pack, perform
provisioning and have the transmitter join the field
wireless network.
This transmitter supports the OOB(out-of-band)
method using the infrared communication as a
provisioning method. Refer to Subsection 7.4
“Connecting to the Field Wireless Network” for
details of the provisioning.
F0801.ai
Infrared port
Figure 8.1
Infrared port of the transmitter
8.2 Preparing Software for the
Configuration Tool
Before using the configuration tool, confirm that CF/
DD and DeviceDTM for your transmitter (wireless
EJX) are installed in the configuration tool.
CF/DD and DeviceDTM are provided by CD-ROM
attached to YFGW710 Field Wireless Integrated
Gateway.
Refer to YFGW710 Field Wireless Integrated
Gateway (GS 01W01F01-01EN) for details.
CF (Capabilities File)/DD (Device Description)
A CF file contains information, such as the
vendor of the field device, its model and
revision, available types of process data (flow
rate, temperature, pressure, etc.), and number
of data items. A DD file contains the information
on parameters, such as data structures and
attributes.
DeviceDTM
DeviceDTM (Device Type Manager) is driver
software for field devices provided based on the
FDT (Field Device Tool) technology.
The configuration tool allows confirming the device
information. For details on how to confirm the
device information using the configuration tool,
refer to the General Specifications, YFGW710 Field
Wireless Integrated Gateway (GS 01W01F01-
01EN).
Refer to subsection 9.2 “calibration Instruments
Section” for a configuration tool of our
recommendation.
<8. Setting Parameters>
8-2
IM 01C27F01-01EN
8.3 Setting Parameters
8.3.1 Parameter Usage and Selection
Before setting a parameter, please see the following
table for a summary of how and when each
parameter is used.
IMPORTANT
After setting and sending data with the
configuration tool, wait 30 seconds before
turning off the transmitter. If it is turned off
too soon, the settings will not be stored in the
transmitter.
Table 8.1
Parameter Usage and Selection
Item
Description
Tag No
Sets the tag No. as Device Tag (Software Tag). Sixteen characters
(alphanumeric characters, including - and •) can be set.
Output
The process variable and the diagnostic result can be output.
Either or all of differential pressure (AI1:PV), static pressure (AI2:PV),
temperature(AI3:PV) of capsule or amplifier and self-diagnostic
information (UAPMO:DIAG_STATUS) can be set to the output
Range
Adjust the range corresponding for 0% to 100%.
The unit of the range, input value at 0% (LRV) and input value at 100%
(URV) is set.
Note: LRV and URV can be set within the range of -32000 to 32000.
Damping time constant
Adjust the output response speed for 0% to 100%.
It can be set within the range of 0.00 to 100.00 seconds.
The setting becomes invalid in the intermittent mode.
Output signal low cut mode
Used mainly to stabilize output near 0 if output signal is the square root
mode. Two modes are available: forcing output to 0% for input below a
specific value, or changing to proportional output for input below a specific
value.
Integral indicator range of scale and unit
Sets one of pressure value, or temperature value for the integral indicator
scale.
Note: LRV and URV can be set within the range of -32000 to 32000.
Unit for displayed temperature
Sets a temperature unit to be displayed.
Range with actual input applied
Range corresponding for 0% to 100% signal is set with actual input
applied.
The output setting can be done just 100% to user’s reference pressure
output.
However, when shipping it, the calibration is done in high accuracy as for
DPharp. Please do the span setting by a usual range setting.
Zero Point Adjustment and Span Adjustment
Handle Zero Point Adjustment and Span Adjustment.
There are two methods of Zero Point Adjustment, using external zero-
adjustment screw and using configuration tool.
Reset adjustment
Reset all setting of zero and span adjustment, etc.
Software write protect
Prohibit writing the setting data.
Operational mode
Set the operational mode of the sensor and integral indicator, etc.
<8. Setting Parameters>
8-3
IM 01C27F01-01EN
8.3.2 Function Block and Menu Tree
(1) Function Block
The function of this transmitter is shown below. A specific function might not be able to be used according to
the configuration tool used. When a configuration tool of our recommendation is used, the software attached to
the Field Wireless Integrated Gateway is necessary for setting the dotted line part.
Refer to Subsection 9.2 “Calibration Instruments Selection” for a configuration tool of our recommendation.
The setting of differential pressure(Al2 block) is invalid in this instrument. The output value of Al2 object and the
output status are “0.0”(zero), “Uncertain” respectively.
•Configuration
•Diagnostics/Alerts
•Power Status
•Identification
(UAPMO)
•APP Download
(UDO)
•Configuration
•Others
(CO)
•Block Info
•Configuration
(TRANSDUCER)
•UAPMO
•UDO
•CO
•TRANSDUCER
•AI1(DP)
•AI2(SP)
•AI3(ET)
Online Menu
•UAP_OPTION
•HW_WRITE_PROTECT
•ST_REV
•RESET_ENERGY_LEFT
•RADIO_SILENCE
(Configuration)
•DIAG_STATUS
•DIAG_STATUS_DETAIL[0]
•DIAG_SWITCH
•DIAG_CONFIG
(Diagnostics/Alerts)
•VERSION_REVISION
•CTS_VERSION
•ITS_VERSION
•IDENT_NUMBER
(Identification)
•DESCRIPTION
•STATE
•MAX_BLOCK_SIZE
•LAST_BLOCK_DOWNLOADED
•ERROR_CODE
(APP Download)
•COMM_ENDPOINT
•COMM_CONTRACT
•PUB_ITEM_MAX
•PUB_ITEM_NUM
•PUB_ITEM
(Configuration)
•REVISION
(Others)
•Network address of remote endpoint
•Transport layer port at remote endpoint
•Object ID at remote endpoint
•Stale data limit
•Data publication period
•Ideal publication phase
•PublishAutoRetransmit
•Configuration status
(COMM_ENDPOINT)
•ContractID
•Contract_Status
•Actual_Phase
(COMM_CONTRACT)
•ObjectID
•AttributeID
•AttributeIndex
•Size
(PUB_ITEM)
•TAG_DESC
(Block Info)
•AUTO_RECOVERY
•MODEL
•SENSOR_SN
•MEASUREMENT_RATE
•MEASURE_MODE
•WIRELESS_STATUS
•DISPLAY_SEL
•LCD_MODE
•SPECIAL_CMD
•SPECIAL_ORDER_ID
•UNIT_SEL1
•DISPLAY_UNIT1
(Configuration)
F0802-1.ai
•ENERGY_LEFT
•POWER_SUPPLY_STATUS
(Power Status)
<8. Setting Parameters>
8-4
IM 01C27F01-01EN
•Block Info
•Block Mode
•Dynamic Variables
•Configuration
•Calibration
•Others
(AI1 DP)
•TAG_DESC
(Block Info)
•Target
•Actual
•Permitted
•Normal
(Block Mode )
•PV
•SIMULATION
(Dynamic Variables)
•SIMULATE_SWITCH
•TRANSDUCER_VALUE
•SIMULATE_VALUE
(SIMULATION)
•Status
•Value **
(PV)
•Status
•Value
(TRANSDUCER_VALUE)
•Status
•Value
(SIMULATE_VALUE)
•Block Mode
•CONC_OID
•SCALE *
•PV_FTIME
(Configuration)
(Block Mode)
•Target
•Actual
•Permitted
•Normal
(SCALE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
•UPPER_LIM
•LOWER_LIM
•PV_RANGE *
•LIN_TYPE *
•FLOW_CONSTANT *
•LOW_CUTOFF
•LOWCUT_MODE *
•H/L_SWAP *
•T_ZERO_CMP *
•TEMP_ZERO *
•TEMP_SELECT *
(Others)
(PV_RANGE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
F0802-2.ai
•Block Mode
•CAL_CMD *
•CAL_STATUS
•CAL_POINT_HI *
•CAL_POINT_LO *
•CAL_MIN_SPAN
•EXTERNAL_ZERO_TRIM *
(Calibration)
(Block Mode)
•Target
•Actual
•Permitted
•Normal
Online Menu (continued)
*:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
**:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
<8. Setting Parameters>
8-5
IM 01C27F01-01EN
•Block Info
•Block Mode
•Dynamic Variables
•Configuration
•Others
(AI2 SP)
•TAG_DESC
(Block Info)
•Target
•Actual
•Permitted
•Normal
(Block Mode )
•PV
•SIMULATION
(Dynamic Variables)
•SIMULATE_SWITCH
•TRANSDUCER_VALUE
•SIMULATE_VALUE
(SIMULATION)
•Status
•Value **
(PV)
•Status
•Value
(TRANSDUCER_VALUE)
•Status
•Value
(SIMULATE_VALUE)
•Block Mode
•CONC_OID
•SCALE *
•PV_FTIME
(Configuration)
(Block Mode)
•Target
•Actual
•Permitted
•Normal
(SCALE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
•UPPER_LIM
•LOWER_LIM
•PV_RANGE *
•LIN_TYPE *
•FLOW_CONSTANT *
•LOW_CUTOFF
•CAL_CMD *
•CAL_STATUS
•CAL_POINT_HI *
•CAL_POINT_LO *
•CAL_MIN_SPAN
•SP_VALUE_TYPE *
•SP_SELECT *
(Others)
(PV_RANGE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
F0802-3.ai
Online Menu (continued)
*:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
**:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
<8. Setting Parameters>
8-6
IM 01C27F01-01EN
•Block Info
•Block Mode
•Dynamic Variables
•Configuration
•Others
(AI3 ET)
•TAG_DESC
(Block Info)
•Target
•Actual
•Permitted
•Normal
(Block Mode )
•PV
•SIMULATION
(Dynamic Variables)
•SIMULATE_SWITCH
•TRANSDUCER_VALUE
•SIMULATE_VALUE
(SIMULATION)
•Status
•Value **
(PV)
•Status
•Value
(TRANSDUCER_VALUE)
•Status
•Value
(SIMULATE_VALUE)
•Block Mode
•CONC_OID
•SCALE *
•PV_FTIME
(Configuration)
(Block Mode)
•Target
•Actual
•Permitted
•Normal
(SCALE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
•SENSOR_RANGE
•TERTIARY_VALUE_SEL *
(Others)
(SENSOR_RANGE)
•EU at 100%
•EU at 0%
•Units Index **
•Decimal **
F0802-4.ai
Online Menu (continued)
*:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
**:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
<8. Setting Parameters>
8-7
IM 01C27F01-01EN
(2) Menu Tree
The menu tree of a configuration tool of our recommendation is shown below. Refer to Subsection 9.2
“Calibration Instruments Selection” for a configuration tool of our recommendation.
•UAPMO
•TRANSDUCER
•AI1 DP
•AI2 SP
•AI3 Temp
•Device Configuration
•Diagnostic
•Process Variable
(Device Configuration)
Online Menu
F0803-1.ai
•Configure/Setup
(UAPMO)
•Configure/Setup
(TRANSDUCER)
•UAP_OPTION
•HW_WRITE_PROTECT
•ST_REV
•RESET_ENERGY_LEFT
•RADIO_SILENCE
(Configuration)
•VERSION_REVISION
•CTS_VERSION
•ITS_VERSION
•IDENT_NUMBER
(Identification)
•AUTO_RECOVERY
•MODEL
•SENSOR_SN
•MEASUREMENT_RATE
•MEASURE_MODE
•WIRELESS_STATUS
•DISPLAY_SEL
•LCD_MODE
•SPECIAL_CMD
•SPECIAL_ORDER_ID
•UNIT_SEL1
•DISPLAY_UNIT1
(Configuration/Calibration)
•TAG_DESC
(Block Info)
•Configure/Setup
(AI1 DP)
•Target
•Actual
•Permitted
•Normal
(Block Mode)
•Block Mode
•CONC_OID
•SCALE *
•PV_FTIME
(Configuration)
•Target
•Actual
•Permitted
•Normal
(Block Mode)
•Block Mode
•CAL_CMD *
•CAL_STATUS
•CAL_POINT_HI *
•CAL_POINT_LO *
•CAL_MIN_SPAN
•EXTERNAL_ZERO_TRIM *
(Calibration)
•Target
•Actual
•Permitted
•Normal
(Block Mode)
•UPPER_LIM
•LOWER_LIM
•PV_RANGE *
•LIN_TYPE *
•FLOW_CONSTANT *
•LOW_CUTOFF
•LOWCUT_MODE *
•H/L_SWAP *
•T_ZERO_CMP *
•TEMP_ZERO *
•TEMP_SELECT *
(Others)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
(PV_RANGE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
(SCALE)
•TAG_DESC
(Block Info)
*:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
<8. Setting Parameters>
8-8
IM 01C27F01-01EN
•Configure/Setup
(AI2 SP)
F0803-2.ai
•TAG_DESC
(Block Info)
•UPPER_LIM
•LOWER_LIM
•PV_RANGE *
•LIN_TYPE *
•FLOW_CONSTANT *
•LOW_CUTOFF
•CAL_CMD*
•CAL_STATUS
•CAL_POINT_HI *
•CAL_POINT_LO *
•CAL_MIN_SPAN
•SP_VALUE_TYPE *
•SP_SELECT *
(Others)
•Target
•Actual
•Permitted
•Normal
(Block Mode)
•EU at 100%
•EU at 0%
•Units Index *
•Decimal *
(PV_RANGE)
(Block Mode)
•Target
•Actual
•Permitted
•Normal
(AI3 Temp)
(Block Info)
•TAG_DESC
•SENSOR_RANGE
•TERTIARY_VALUE_SEL *
(Others)
•Block Mode
•CONC_OID
•SCALE *
•PV_FTIME
(Configuration)
•Target
•Actual
•Permitted
•Normal
(Block Mode)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
(SCALE)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
(PV_REMGE)
•Configure/Setup
•Block Mode
•CONC_OID
•SCALE *
•PV_FTIME
(Configuration)
•Target
•Actual
•Permitted
•Normal
(Block Mode)
•EU at 100% *
•EU at 0% *
•Units Index *
•Decimal *
(SCALE)
Device Configuration (continued)
Online Menu (continued)
*:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
<8. Setting Parameters>
8-9
IM 01C27F01-01EN
•UAPMO
(Diagnostic)
F0803-3.ai
•Device Diagnostics
(UAPMO)
•DIAG_STATUS
•DIAG_STATUS_DETAIL[0]
•DIAG_SWITCH
•DIAG_CONFIG
(Diagnostics/Alerts)
•ENERGY_LEFT
•POWER_SUPPLY_STATUS
(Power Status)
•AI1 DP
•AI2 SP
•AI3 Temp
(Process Variable)
•Process Variable
(AI1 DP)
•PV
•SIMULATION
(Dynamic
Variables)
•Status
•Value**
(PV)
•SIMULATE_SWITCH
•TRANSDUCER_VALUE
•SIMULATE_VALUE
(SIMULATION)
•Status
•Value
(TRANSDUCER_
VALUE)
•Status
•Value
(SIMULATE_
VALUE)
•Process Variable
(AI2 SP)
•PV
•SIMULATION
(Dynamic
Variables)
•Status
•Value**
(PV)
•SIMULATE_SWITCH
•TRANSDUCER_VALUE
•SIMULATE_VALUE
(SIMULATION)
•Status
•Value
(TRANSDUCER_
VALUE)
•Status
•Value
(SIMULATE_
VALUE)
•Process Variable
(AI3 Temp)
•PV
•SIMULATION
(Dynamic
Variables)
•Status
•Value**
(PV)
•SIMULATE_SWITCH
•TRANSDUCER_VALUE
•SIMULATE_VALUE
(SIMULATION)
•Status
•Value
(TRANSDUCER_
VALUE)
•Status
•Value
(SIMULATE_
VALUE)
Online Menu (continued)
**:
When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
<8. Setting Parameters>
8-10
IM 01C27F01-01EN
8.3.3 Parameters for Wireless
Communication
(1) Network Information
Concentrator object block : Configuration
Allows confirming the network information.
(2) Update Time
CO block : Data publication period
Sets the update time value to 1 to 3,600
seconds. The setting affects the battery life.
(3) Measurement Mode
TRANSDUCER block : MEASURE_ MODE
The setting affects the battery life; it becomes
shorter in the continuous display mode.
When the update period is set to 1 second in
intermittent mode, the mode is automatically
switched to continuous mode. When the update
period is 1 second, the mode is continuous
mode, regardless of the measurement mode.
(4) Measurement Rate
TRANSDUCER block: MEASUREMENT_
RATE
Reads the measurement rate value from 1 to
3600 seconds. The shorter the measurement
period, the shorter the battery life.
(5) Remaining battery life
UAPMO block: ENERGY_LEFT
The number of days of remaining battery life
is indicated assuming ambient temperature
condition as 23 degrees Celsius. While within
24 hours after power on, the number of days of
1461 (4 years) is indicated.
UAPMO block: RESET_ENERGY_LEFT
The number of days of battery life is reset.
When changing battery, initialization of the
remaining battery life is performed by RESET_
ENERGY_LEFT parameter. After initialization
of the remaining battery life, confirm the number
of days of battery life by ENERGY_LEFT
parameter.
6)
LCD display mode
TRANSDUCER block : LCD_MODE
0) LCD off
[Bar graph not displayed]
1) LCD intermittent display
[Bar graph not displayed]
2) LCD continuous display
[Bar graph not displayed]
5) LCD intermittent display
[Bar graph not displayed]
6) LCD continuous display
[Bar graph not displayed]
9) LCD intermittent display
[Bar graph displayed]
10) LCD continuous display
[Bar graph displayed]
When the continuous display mode is set to
ON, the LCD is on continuously. When the
continuous display mode is set to OFF, the LCD
turns on intermittently or turns off.
The interval times of display are shown as
follows.
• LCD continuous display
The LCD displays while 5 minutes then turns
off.
• LCD intermitted display
The LCD displays while 3 seconds then turns
off.
• LCD continuous display + LCD intermitted
display
The LCD displays while 5 minutes then turns
intermittently.
When measurement mode is set as continuous
mode, the LCD displays continuously
regardless of display mode.
<8. Setting Parameters>
8-11
IM 01C27F01-01EN
8.3.4 Tag and Device Information
If these are specified when ordering, the designated
Tag No. and device information are set and
shipped. Tag No. and device information can be
checked as follows.
• Procedure to call up the tag No. and device
information
- Device Tag ( Software Tag )
- Software Tag (only if needed)
This is specified when writing characters (up
to 16 characters) of amplifiers TAG that differ
from characters specified in Tag No.
- TAG_DESC
This is a universal parameter to store the
comment that describes the content of the
tag located in the TRANSDUCER and AI
blocks.
The AI1 and AI3 blocks of the AI blocks
correspond to the pressure and temperature,
respectively.
• When changing the device information, input
the information based on the following limitation
on the number of characters.
- Message function (up to 32 characters)
TRANSDUCER block : TAG_DESC
AI1, AI3 block : TAG_DESC
8.3.5 Unit
The unit parameter is set at the factory before
shipment if specified at the time of order. Follow the
procedure below to change the unit parameter.
• Procedure to call up the Unit display (Units
Index)
Al1, Al3 block : SCALE: Units Index
To change the Unit display, choose desired unit
among the list of displayed unit selecting AI1
block as for the pressure, and AI3 block as for
temperature in the AI blocks.
8.3.6 Range Change
The range values are factory-set as specified by
the customer. To change the range, follow the steps
below.
Keypad input — LRV and URV
The measurement span is determined by the upper
and lower range values. In this method, the upper
and lower range values can be set independently,
and the span changes according to the range limit
values sent to the transmitter.
• Procedure to call up the PV_RANGE display.
AI1 block : PV_RANGE
Select the AI1 block for the pressure, then
select “EU at 0%” and “EU at 100%” displayed
in the PV_RANGE parameters. And input the
lower range and upper range values for the
range.
8.3.7 Output Signal Low Cut Mode Setup
Low cut mode can be used to stabilize the output
signal near the zero point.
(There is 10% of hysteresis at only point of
transition from low to high)
[Setup Low Cut Value]
• Procedure to call up the LOW_CUTOFF display
AI1 block: LOW_CUTOFF
Select the AI1 block for the pressure, and then
input a value in the output range from 0 to 20%
for the LOW_CUTOFF parameter.
Example: setup LOW_CUT of output to 15%
LOW_CUTOFF
= (“Eu at 100%” – “Eu at 0%”) * 0.15 + “Eu at 0%”
[Setup Low Cut Mode]
• Procedure to call up the LOWCUT_MODE
display
AI1 block: LOWCUT_MODE
Select the AI1 block for the pressure, and then
select Linear or Zero for the LOWCUT_MODE
parameter.
F0804.ai
(%)
50
20
0
50 (%)
Low cut mode “Linear”
Low cut mode “Zero”
Low cut
at 20%
(%)
50
20
0
50 (%)
Low cut
at 20%
Output
Output
Input
Input
Figure 8.2
Low Cut Mode
<8. Setting Parameters>
8-12
IM 01C27F01-01EN
The low cut point has hysteresis so that the output
around the point is behaved as below figure.
Output mode: Linear
Low cut mode: Zero
Low cut: 20.00%
Output
Setting range:
0 to 20%
Input
0%
(20%)
2%
Low
cut
point
Hystrersis fixed at 10%
of the cut point
F0805.ai
8.3.8 Integral Indicator Scale Setup
The following three displays are available for the
integral indictor: pressure and temperature. The
following three variables can be displayed on the
integral indicator: % of pressure range, and % of
temperature range.
Available displays
Description
and related parameters
% of range
(PRES %)
Indicates input pressure in –10 to
110% range depending on the set
range (LRV and URV).
PRES % 45.6 %
Follow the procedure described in (a) to (b) below
to set the integral indicator.
(a) Display Selection
Display set to DISPLAY_SEL is displayed on the
integral indicator.
• Procedure to call up the DISPLAY_DEL display
TRANSDUCER block: DISPLAY_SEL
The DISPLAY_SEL parameter enables the
pressure (AI1 block), and, temperature (AI3
block) to be displayed on the LCD. Select
whether or not to enable each block to be
displayed.
(b) Cyclic Display
Information in the AI1, AI3 blocks can be displayed
cyclically according to the display On/Off setting
for the pressure (AI1 block), and temperature (AI3
block) selected in the DISPLAY_SEL parameter.
8.3.9 Unit for Displayed Temperature
When the instrument is shipped, the temperature
units are set to C (Centigrade). Follow the
procedure below to change this setting.
• Procedure to call up the Unit Index display
AI3 Block: SENSOR_RANGE: Units Index
Confirm that ºC (deg C) is selected in the Units
Index parameter for the temperature(AI3 block).
Note: When the unit is changed by units index parameter in
temperature (AI3 block), units of capsule temperature is
also changed.
8.3.10 Zero Point Adjustment and Span
Adjustment
Each EJX-B series transmitter is characterized
by factory. But there are some errors caused by
environment and installed posture.
There are Zero and Span Adjustments to fine-tune
those errors.
Zero Adjustment is adjustment for one point to
adjust the bottom value of the measurement range
as 0% of output.
The Span Adjustment defines input and output
characteristic between two points that’s one side
assumed as standard.
This is used when there is doubt of span drift or
when it is impossible to make zero at absolute
pressure with adjustment for user’s pressure
standard.
(1) Zero Point Adjustment
a.
To set 0% at current input, perform
following procedure.
This method is used only when the pressure at
bottom of measurement range is zero.
• Procedure to call up the calibration adjustment
parameter (CAL_STATUS)
AI1 block: CAL_STATUS
Confirm the value of CAL_SUCCESS that is 1
using the CAL_STATUS parameter.
b.
To match current input and output value,
follow procedure
Like the measurement that is impossible to
set process pressure to 0kPa, output value is
adjustment to actual level by other measurement
using glassgage.
<8. Setting Parameters>
8-13
IM 01C27F01-01EN
Example:
Pressure Transmitter’s span is 0 to 25.00kPa,
current level is 13.50kPa, current output is
13.83kPa.
• Procedure to call up the lower limit adjustment
parameter (CAL_POINT_LO).
AI1 Block: CAL_CMD: CAL_POINT_LO
Set the actual level value of 13.50 kPa to the
CAL_POINT_LO parameter for the pressure
(AI1 block). Apply an actual input and confirm
the value specified in CAL_POINT_LO as the
output value.
• Procedure to call up the calibration adjustment
parameter (CAL_CMD).
AI1 block: CAL_CMD: CAL_LOW
The present output is changed from 13.83kPa
to 13.50 kPa in CAL_LOW of the pressure (AI1
block) CAL_CMD parameter.
• Procedure to call up the calibration status
parameter (CAL_STATUS).
AI1 block: CAL_STATUS
Confirm the value of CAL_SUCCESS that is 1
using the CAL_STATUS parameter.
c.
Using External Zero adjustment Screw
External Zero-adjustment parameter (EXTERNAL_
ZERO_TRIM) can set permission or prohibition to
adjustment by External Zero-adjustment Screw.
Set “Trim on” to use the External Zero-adjustment
Screw. (“Trim on” at shipment)
Use a slotted screwdriver to turn the
zeroadjustment screw. Equalize the transmitter,
then turn the screw clockwise to increase the
output or counterclockwise to decrease the output.
The zero point adjustment can be made with
a resolution of 0.01% of the setting range. The
degree of zero adjustments varies with the screw
turning speed; turn the screw slowly to make a fine
adjustment, quickly to make a rough adjustment.
IMPORTANT
When zeroing with the zero-adjustment screw,
turn the screw firmly until ▲ or ▼ mark is
displayed on the integral indicator since there
exists mechanical dead-band of the screw.
(2) Span Adjustment
Span Adjustment is function to change the input and
output characteristic that assumed the bottom value
(zero point) of measurement range a standard.
Therefore, perform span adjustment (adjustment
of the upper limit value) after zero adjustment
(adjustment of bottom limit value).
After adding the pressure at point of adjustment and
setting pressure value as parameter, the transmitter
calculates quantity of adjustment and performs
adjustment automatically.
• Procedure to call up the lower limit value
parameter (CAL_POINT_LO)
AI1 block: CAL_CMD: CAL_POINT_LO
Set the lower limit adjustment value on
the pressure (AI1 block) CAL_POINT_LO
parameter screen. Apply a reference pressure
corresponding to the lower limit of the
measurement range to the pressure transmitter
and confirm the pressure when it stabilized.
• Procedure to call up the calibration adjustment
parameter (CAL_CMD)
AI1 block: CAL_CMD: CAL_LOW
Confirm the lower limit of the measurement
range in CAL_LOW of the pressure (AI1 block)
CAL_CMD parameter.
• Procedure to call up the calibration status
parameter (CAL_STATUS)
AI1 block: CAL_STATUS
Confirm the value of CAL_SUCCESS that is 1
using the CAL_STATUS parameter.
• Procedure to call up the upper limit adjustment
parameter (CAL_POINT_HI).
AI1 block: CAL_CMD: CAL_POINT_HI
Set the upper limit adjustment value for
the pressure (AI1 block) CAL_POINT_HI
parameter. Apply a reference pressure
corresponding to the upper limit of the
measurement range to the pressure transmitter
and confirm the when it has stabilized.
• Procedure to call up the calibration adjustment
parameter (CAL_CMD).
AI1 block: CAL_CMD: CAL_HIGH
Confirm the upper limit of the measurement
range in CAL_HIGH of the pressure (AI1 block)
CAL_CMD parameter.
<8. Setting Parameters>
8-14
IM 01C27F01-01EN
• Procedure to call up the calibration status
parameter (CAL_STATUS)
AI1 block: CAL_STATUS
Confirm the value of CAL_SUCCESS that is 1
using the CAL_STATUS parameter.
(3) Reset Adjustments to Factory Setting
A reset to the factory setting can be performed
using CAL_CLEAR of the pressure (AI1 block)
CAL_CMD parameter for the input pressure. After
calibration, confirm status by using the pressure
(AI1 block) CAL_STATUS.
The amount of adjustment made by the external
zero-adjustment screw can be reset to the initial
setting as well.
• Procedure to call up the calibration adjustment
parameter (CAL_CMD).
AI1 block: CAL_CMD: CAL_CLEAR
8.3.11 Software Write Protect
Hardware write protection and software write
protection functions are available for this transmitter
• Procedure to call up the protection setting
parameter (UAP_OPTION)
UAPMO block: UAP_OPTION
The following settings can be configured in the
UPA_OPTION parameter.
- Setting to enable or disable changing the
setting to the DIAG_SWITCH and DIAG_
CONFIG parameters.
- Setting to enable or disable the hardware
write protection switch.
- Setting to enable or disable software write
protection.
• Procedure to call up the protection setting
display parameter (HW_WRITE_PROTECT)
UAPMO block: HW_WRITE_PROTECT
The HW_WRITE_PROTECT parameter
enables the switch status of hardware write
protection to be displayed.
For the relationship between hardware write
protection and software write protection, refer
section 10. “Parameter Summary”.
8.3.12 Switching to Deep Sleep Mode
When the instrument will not be used for a long
time, switch the instrument to deep sleep mode to
conserve battery power.
To switch to deep sleep mode, follow the procedure
below.
• Procedure to call up the switch-to-deep-sleep
parameter
TRANSDUCER block: SPECIAL_CMD
Set Deep Sleep mode (0002) to the SPECIAL_
CMD parameter for the TRANSDUCER
block. To start from deep sleep mode, either
remove and insert the battery pack, or use the
configuration tool.
NOTE
• This procedure to switch to deep sleep mode
can only be use for wireless communication.
• Transmitter becomes the stop state after
setting deep sleep mode and cannot reply
any request from Communication Tool.
• For this reason, there is the case that an
error is display on Communication Tool.
• To wake up from deep sleep mode, please
pull battery pack, and wait more than 30
seconds before attaching battery back.
8.3.13 Switching to Silence Mode
This is a function to pause the instrument when
it cannot join the field wireless network after a
specified time has elapsed. This function is effective
in conserving battery power when, for example, the
installation of the field wireless integrated gateway
is delayed compared to that of field wireless
devices. The default value is 28800 seconds
(about 8 hours). Thereafter, a cycle of a one-hour
pause and six-minute search is repeated until the
instrument can join the field wireless network.
• Procedure to call up the switch-to-silence
parameter (RADIO_SILENCE)
UAPMO block: RADIO_SILENCE
Set 0 to 231 seconds for the RADIO_SILENCE
parameter of the UAPMO block. If 0 is set, the
RADIO_SILENCE parameter is invalid. To start
from silence mode, either remove and insert the
battery pack, or use the configuration tool.
<8. Setting Parameters>
8-15
IM 01C27F01-01EN
8.4 Self-Diagnostics
8.4.1 Identify Problems by Using the
Communicator
First, check DIAG_STATUS of the self-diagnostic
result.
UAPMO block: DIAG_STATUS
Any of the four categories (Check function,
Maintenance required, Failure, and Off
specification) according to NAMUR NE107* is
supplied to DIAG_STATUS of each diagnostic
result.
Table 8.3
DIAG_STATUS
Bits
Contents
Example
NAMUR NE107
Categorization
Bit31 (MSB)
F: Failure status
---
Bit30
C: Function check status
---
Bit29
O: Out of specification status
---
Bit28
M: Maintenance required status
---
Bit27
Faults in electronics
F
Bit26
Faults in sensor or actuator element
F
Bit25
Installation, calibration problem
C
Bit24
Out of service
C
Bit23
Outside sensor limits
O
Bit22
Environmental conditions out of device specification
O
Bit21
Fault prediction: Maintenance required
M
Bit20
Power is critical low: maintenance need short-term
M
Bit19
Power is low: maintenance need mid-term
M
Bit18
Software update incomplete
C
Bit17
Simulation is active
C
Bit16-Bit08
reserved by WCI
---
Bit07-Bit01
vendor specific area
---
Bit00
Detail information available
1: available
0: no available
---
2) When changing the Diag Switch parameter:
a) UAPMO block : UAP_OPTION, select
enable.
b) UAPMO block : DIAG_SWITCH, turn ON
Check function for Out of Service.
c) UAPMO block : UAP_OPTION, select
disable.
Note: Be careful when changing the alert category and turning
detection on and off as described above. Be sure to set
UAP OPTION to disable again to prevent setting errors.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field
Devices”
Checking the DIAG_STATUS category allows
taking the proper action. The DIAG_STATUS
contents are common for all ISA devices, and
the setting for the DIAG_STATUS category can
be changed. For further details, refer to DIAG_
STATUS_Detail.
In DIAG_STATUS Contents that can be diagnosed
by the EJX, the alert category set in Out of Service
can be changed to Check function. To do so, follow
one of the two procedures below.
1) When using the DIAG_CONFIG parameter:
a) UAPMO block : UAP_OPTION, select
enable.
b) UAPMO block : DIAG_CONFIG, change Out
of Service from Failure to Check function.
c) UAPMO block : UAP_OPTION, select
disable.
<8. Setting Parameters>
8-16
IM 01C27F01-01EN
Table 8.4
Diagnostic Results Summary
DIAG_STATUS Contents
NAMUR
NE107
Category
DIAG_STATUS_DETAIL
Description
Faults in electronics
F
AMP_T_SENSOR_FAIL
Amplifier temperature sensor failure
AMP_EEPROM_FAIL
Amplifier EEPROM failure
AMP_EEP_IRREGULAR
AMP EEPROM version not correct
AMP_F1_ERROR
F1 error
G_A_COMM_FAIL
G/A failure
FC_DELTA_T_FAIL
C-side delta T circuit failure
FR_DELTA_T_FAIL
R-side delta T circuit failure
WL_AD_FAIL
Battery voltage not detected (AMP
failure)
Faults in sensor or actuator
element
F
FC_SENSOR_FAIL
C sensor frequency failure
FR_SENSOR_FAIL
R sensor frequency failure
CAP_T_SENSOR_FAIL
Capsule temperature sensor failure
CAP_EEPROM_FAIL
Capsule EEPROM failure
CAP_EEP_IRREGULAR
CAP EEPROM version not correct
FC_UNOSC_FAIL
C sensor oscillation stop failure
FR_UNOSC_FAIL
R sensor oscillation stop failure
Installation, calibration problem
C
DP_TRIM_SPAN_OUTSIDE
Pressure span adjustment variable
outside of range
DP_TRIM_ZERO_OUTSIDE
Pressure zero adjustment variable
outside of range
SP_TRIM_SPAN_OUTSIDE
Static pressure span adjustment
variable outside of range
SP_TRIM_ZERO_OUTSIDE
Static pressure zero adjustment
variable outside of range
LCD_OUTSIDE_LIMIT
LCD display outside of limits
Out of service
O
AI1_OUT_OF_SERVICE
AI1 O/S mode
AI2_OUT_OF_SERVICE
AI2 O/S mode
AI3_OUT_OF_SERVICE
AI3 O/S mode
Outside sensor limits
C
DP_OUTSIDE_LIMIT
Pressure outside of range
SP_OUTSIDE_LIMIT
Static pressure outside of range
CAPT_OUTSIDE_LIMIT
Capsule temperature outside of range
AMPT_OUTSIDE_LIMIT
Amplifier temperature outside of range
Environmental conditions out
of device specification.
O
DP_OUTSIDE_RANGE
Pressure setting outside of range
SP_OUTSIDE_RANGE
Static pressure setting outside of
range
Power is critical low:
maintenance need short-term.
M
WL_DEEPSLP_ALM
Deep sleep due to low battery
Power is low:
maintenance need mid-term
M
WL_LOWBAT_ALM
Low battery
Simulation is active
C
AI1_SIMULATION_ACTIVE
AI1 Simulation mode
AI2_SIMULATION_ACTIVE
AI2 Simulation mode
AI3_SIMULATION_ACTIVE
AI3 Simulation mode
<8. Setting Parameters>
8-17
IM 01C27F01-01EN
8.4.2 Checking with Integral Indicator
NOTE
If an error is detected by running self-diagnostics,
an error number is displayed on the integral
indicator. If there is more than one error, the error
number changes at three-second intervals. See
table 9.3 regarding the alarm codes.
F0806.ai
Figure 8.6
Integral Indicator
9.1 Overview
WARNING
Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate care
to avoid contact with the body or inhalation of
vapors when draining condensate or venting gas
from the transmitter pressure-detector section
and even after dismounting the instrument from
the process line for maintenance.
Maintenance of the transmitter is easy due to its
modular construction. This chapter describes the
procedures for calibration, adjustment, and the
disassembly and reassembly procedures required
for component replacement.
Transmitters are precision instruments. Please
carefully and thoroughly read the following sections
for information on how to properly handle them
while performing maintenance.
IMPORTANT
• As a rule, maintenance of this transmitter
should be done in a maintenance room that
has all the necessary tools.
• The CPU assembly, RF assembly and
integral indicator contain sensitive parts that
can be damaged by static electricity.
Take precautions such as using a grounded
wrist strap when handling electronic parts
or touching the board circuit patterns.
Also be sure to place the removed the
CPU assembly, RF assembly and integral
indicator into a bag with an antistatic coating.
9.2 Calibration Instruments
Selection
Table 9.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
instrument, consider the required accuracy level.
Exercise care when handling these instruments to
ensure they maintain the specified accuracy.
9.3 Calibration
Use the procedure below to check instrument
operation and accuracy during periodic
maintenance or troubleshooting.
1) Insert the battery pack and then perform
provisioning to have the transmitter join the
Field Wireless Network for calibration.
2) Set the update period to 1 second using the
configuration tool to set continuous for the
transmitter.
3) Connect the devices as shown in Figure 9.1
and allow the transmitter to warm up for at least
5 minutes.
IMPORTANT
If the measurement range 0% point is 0 kPa
or shifted in the positive direction (suppressed
zero), the reference pressure should be applied
as shown in the figure.
If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
reference pressure should be applied using a
vacuum pump.
4) Apply reference pressures of 0%, 50%,
and 100% of the measurement range to the
transmitter. Calculate the errors (differences
between digital voltmeter readings and
reference pressures) as the pressure is
increased from 0% to 100% and is decreased
from 100% to 0%, and confirm that the errors
are within the required accuracy.
(Note) If output mode is “SQUARE MODE”, measurement range
of 0, 6.25, 56.25, 100% instrument adds corresponding
reference pressure.
5) When the test is finished, reset the update time
to the initial value using the configuration tool.
Instruments Required for Calibration
Name
Yokogawa-recommended Instrument
Remarks
Provisioning
device
• FieldMate (R2.02.01 or later)
DeviceFile (R3.01.01 or later)
• Infrared Adapter certified by Yokogawa
Supplier: ACTiSYS
Product name: IrDA InfraRed USB Adaptor
Product number: IR224UN
Configuration
tool
• Field Wireless Integrated Gateway attached Software
Field Wireless Configurator
Field Wireless Management Tool
• Field Wireless System related Product
Plant Resource Manager (PRM) (R3.05 or later)
Digital
manometer
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy:
±(0.015% of rdg + 0.015% of F.S.)
for 0 to 10 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Select a manometer having
a pressure range close to
that of the transmitter.
Pressure
generator
Model MC100 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25
kPa {2500 mmH2O}
Accuracy: ±0.05% of F.S.
Requires air pressure
supply.
Dead weight gauge tester 25 kPa {2500 mmH2O}
Accuracy: ±0.03% of setting
Select the one having a
pressure range close to that
of the transmitter.
Pressure
source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump
for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa
representatives from which the instrument was purchased or the nearest Yokogawa office.
P
Reference pressure
Pressure generator
Supply pressure
P
Reference pressure
Precision digital manometer
Pressure source
Using pressure
generator
Using pressure source
with manometer
F0901.ai
Figure 9.1
Instrument Connections
9.4.1 Replacing the Integral Indicator
This subsection describes the procedure for
replacing an integral indicator. (See figure 9.2)
■
Removing the Integral Indicator
1) Remove the cover.
2) While supporting the integral indicator with one
hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the RF
assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
the connector pins between it and the RF
assembly.
■
Attaching the Integral Indicator
1) Align both the LCD board assembly and RF
assembly connectors and engage them.
2) Insert and tighten the two mounting screws.
3) Replace the cover.
Zero-
adjustment
screw
RF assembly
CPU assembly
Amplifier Cover
Mounting screw
Integral
indicator
Boss
Stud
F0902.ai
Press
forward
Output terminal
cable
Zero-adjustment
screw pin
Figure 9.2
Removing and Attaching LCD Board
Assembly and CPU Assembly
9.4 Disassembly and
Reassembly
CAUTION
Precautions for the intrinsic safety explosion
prevention type instrument
Intrinsic safe type transmitters must be, as
a rule, removed to a non-hazardous area
for maintenance and be disassembled and
reassembled to the original state. Check and
confirm the insulation when it is reassembled to
the original state.
Check and confirm the insulation when it is
reassembled to the original state.
Refer to section 2.7 “Insulation Resistance and
Dielectric Strength Test” for details of Resistance
Test.
This section describes procedures for disassembly
and reassembly for maintenance and component
replacement.
CAUTION
Always remove Battery pack and shut off
pressures before disassembly and assembly.
Use proper tools for all operations.
Table 9.2 shows the tools required.
Table 9.2
Tools for Disassembly and Reassembly
Tool
Quantity
Remarks
Phillips
screwdriver
1
JIS B4633, No. 2
Slotted
screwdriver
1
Allen wrenches
3
JIS B4648
One each, nominal 3,
4 and 2.5 mm Allen
wrenches
Wrench
1
Width across flats, 17 mm
Torque wrench
1
Adjustable
wrench
1
Socket wrench
1
Width across flats, 16 mm
Socket driver
1
Width across flats, 5.5 mm
Tweezers
1
9.4.2 Replacing the RF Assembly
This subsection describes how to replace the RF
assembly (see Figure 9.2).
■
Removing the RF assembly
1) Remove the cover.
2) Remove the integral indicator (refer to
subsection 9.4.1).
3) Remove the two stud bolts by using a socket
driver (width across flats: 5.5 mm).
4) Disconnect the RF assembly from the CPU
assembly. When doing this, carefully pull the RF
assembly straight forward so as not to damage
the connector pins between it and the CPU
assembly.
5) Disconnect the antenna cable that connects the
RF assembly and the antenna.
NOTE
Be careful not to apply excessive force to the
RF assembly and the connector of the antenna
cable when removing it.
■
Mounting the RF assembly
1) Connect the antenna cable between the RF
assembly and the antenna.
2) Align both the RF assembly and CPU assembly
connectors and engage them.
3) Tighten the two stud bolts.
4) Mount the integral indicator (refer to subsection
9.4.1).
5) Replace the cover.
9.4.3 Replacing the CPU Assembly
This subsection describes how to replace the CPU
assembly (see Figure 9.2).
■
Removing the CPU assembly
1) Remove the cover.
Remove the integral indicator and the RF
assembly (refer to subsections 9.4.1 and 9.4.2).
2) Turn the zero-adjustment screw to the position
as shown in Figure 9.2.
3) Disconnect the power cable and the output
terminal cable (cable with brown connector at
the end).
When doing this, lightly press the side of the
CPU assembly connector and pull the cable
connector to disengage (see the upper left of
Figure 9.2).
4) Use a socket driver (width across flats, 5.5 mm)
to loosen the two bosses.
5) Carefully pull the CPU assembly straight
forward to remove it.
6) Disconnect the flat cable (cable with white
connector at the end) that connects the CPU
assembly and the capsule.
NOTE
Be careful not to apply excessive force to the
CPU assembly when removing it.
■
Mounting the CPU assembly
1) Connect the flat cable (with white connector)
between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown
connector) and the power cable to the CPU
assembly.
NOTE
Make certain that the cables do not get pinched
between the case and the edge of the CPU
assembly.
3) Align and engage the zero-adjustment screw
pin with the groove on the bracket on the CPU
assembly. Then insert the CPU assembly
straight onto the post in the amplifier case.
4) Tighten the two bosses. Mount the RF
assembly, and the integral indicator (refer to
subsections 9.4.1 and 9.4.2).
IMPORTANT
Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
to tightening the two bosses. If it is not, the zero-
adjustment mechanism will be damaged.
5) Replace the cover.
9.4.4 Cleaning and Replacing the Capsule
Assembly
CAUTION
Precautions for the intrinsic safety explosion
prevention type instrument
Modification is not permitted by the user for
intrinsic safety explosion prevention type
transmitter. Consult our company when you want
to exchange capsule assembly.
Execute it only at time when the following points
were confirmed for exchange capsule assembly
in the same range of measurement.
• Exchanged capsule assembly uses the one
of the same specification.
• Tighten Setscrew to fix the transmitter
section and the pressure detector section
surely after ending maintenance.
This subsection describes the procedures for
cleaning and replacing the capsule assembly. (See
figure 9.3.)
■
Removing the Capsule Assembly
IMPORTANT
Exercise care as follows when cleaning the
capsule assembly.
• Handle the capsule assembly with care, and
be especially careful not to damage or distort
the diaphragms that contact the process
fluid.
• Do not use a chlorinated or acidic solution for
cleaning.
• Rinse with clean water after cleaning, please
dry until completely dry.
1) Remove the CPU assembly as shown in
subsection 9.4.3.
2) Remove the five setscrews, the stopper bolt,
and the stopper that connect the transmitter
section and pressure-detector section.
3) Remove the hexagon-head screw and the
stopper.
4) Separate the transmitter section and pressure-
detector section.
5) Clean the capsule assembly or replace with a
new one.
■
Reassembling the Capsule Assembly
1) Reattach the transmitter section to the
pressure-detector section.
Reattach the stopper with the hexagon-head
screw.
2) Tighten the two setscrews.(Tighten the screws
to a torque of 1.5 N·m)
3) Install the CPU assembly according to
subsection 9.4.3.
4) After completing reassembly, adjust the zero
point and recheck the parameters.
Stopper
Stopper bolt
Transmitter section
Setscrew
Pressure-detector
section
Pipe
F0903.ai
Figure 9.3
Removing and Mounting the Pressure-
detector Section
9.4.5 Replacing the Battery Pack
■
Removing
1) Remove the terminal box cover.
2) Loosen the two battery pack mounting screws
(see Figure 9.5).
3) Pull out the Battery pack.
F0904.ai
The battery pack mounting
screws cannot be separated
from the battery pack so as
to prevent drop-off.
Figure 9.4
Removing the Battery Pack
1) Insert the new battery pack lightly.
2) Push the center of the battery pack and insert it
securely.
3) Tighten the two battery pack mounting screws
to a torque of approximately 0.7 N·m.
4) Replace the terminal box cover.
5) Initialize the remaining battery life.
How to initialize the remaining of battery life,
refer to subsection 8.3.3 “Parameters for
Wireless Communication”.
9.4.6 Replacing the Batteries
The batteries in the battery pack can be replaced.
WARNING
Be sure to replace the batteries or disassemble
and assemble the battery pack in a safe location.
Doing so in an explosive area could cause an
explosion.
CAUTION
When replacing the batteries, be sure to replace
the two batteries at the same time and do not
use an old and a new battery together.
■
Disassembling
1) Loosen the two battery case mounting screws
(Figure 9.5).
2) Separate the battery case into two parts.
3) Remove the old batteries.
■
Assembling
1) Insert new batteries into the battery case. Be
careful of the orientation of the batteries.
2) Attach the two parts of the battery case to each
other.
3) Tighten the two battery case mounting screws
to a torque of approximately 0.7 N·m.
F0905.ai
The battery pack mounting screws
cannot be separated from battery
pack so as to prevent drop-off.
Figure 9.5
Removing the Battery Pack
9.4.7 Handling Batteries
This battery pack contains two “D” size primary
lithium/thionyl chloride batteries. Each battery
contains approximately 5 grams of lithium, for
a total of 10 grams in each pack. Under normal
conditions, the battery materials are self-contained
and are not reactive as long as the batteries and
the pack integrity are maintained. Care should be
taken to prevent thermal, electrical or mechanical
damage. Protect the electrode of the battery pack
to avoid rapid electrical discharge. Discharged a
battery may lead to fluid leakage and excessive
heat. Batteries should be stored in a clean and
dry area. For maximum battery life, storage
temperature should not exceed 30°C.
WARNING
Handling the battery pack
The following precautions must be observed
in order to safely and effectively use a battery
pack. Improper use may lead to fluid leakage,
excessive heat, ignition, or explosion.
• Never charge it.
• Do not short-circuit it.
• Do not disassemble, transform, or modify it.
• Do not heat it or throw it into a fire.
• Do not soak it in fresh water or seawater.
CAUTION
Observe the following precautions for the safe
disposal of batteries.
• Do not incinerate the battery, and do not
expose it to a high temperature of 100°C
or more. This may lead to fluid leakage or
explosion.
• Dispose of the battery according to laws and
regulations.
Use the following dedicated parts for the battery
pack and batteries.
■ Battery Pack
Part number: F9915MA
■ Batteries
Part number: A1133EB
Alternatively, Tadiran TL-5930/S batteries may
be purchased and used.
■ Battery Case
Part number: F9915NS
Transportation of products containing
lithium batteries :
The battery pack contains lithium batteries. When
transporting this transmitter with the battery pack
inserted, keep it in deep sleep mode in order to
conserve battery power. For details on how to
switch to deep sleep mode, refer to subsection
8.3.12 “Switching to Deep Sleep Mode.” Primary
lithium batteries are regulated in transportation by
the U.S. Department of Transportation, and are
also covered by the International Air Transport
Association (IATA), the International Civil Aviation
Organization (ICAO), and the European Ground
Transportation of Dangerous Goods (ARD). It is the
responsibility of the shipper to ensure compliance
with these or any other local requirements. Consult
current regulations and requirements before
shipping.
■
Procedure to replace and dispose of the
batteries of the product
The following describes the EU Directive 006/66/EC
(EU’s New Battery Directive), which applies only EU
countries.
This product uses batteries. When removing the
batteries from this product and disposing of them,
follow the national regulations on disposal.
A battery collection system is available in EU
countries. Batteries should be disposed of properly
according to the system.
Battery type : Primary lithium-thionyl chloride
battery
Crossed-out dustbin symbol
CAUTION
The above symbol means that the batteries
with this symbol on them must be collected
separately in accordance with AnnexII of EU’s
New Battery Directive.
■
Procedure to remove the batteries safely:
Refer to subsection 9.4.5 “Replacing the Battery
Pack” and subsection 9.4.6 “Replacing the
Batteries.”
9.5 Troubleshooting
If any abnormality appears in the measured values,
use the troubleshooting flow chart below to isolate
and remedy the problem. Since some problems
have complex causes, these flow charts may
not identify all. If you have difficulty isolating or
correcting a problem, contact Yokogawa service
personnel.
9.5.1 Basic Troubleshooting
First determine whether the process variable
is actually abnormal or a problem exists in the
measurement system.
If the problem is in the measurement system,
isolate the problem and decide what corrective
action to take.
This transmitter is equipped with a self-diagnostic
function which will be useful in troubleshooting,
and the transmitter equipped with an integral
indicator will show an alarm code as a result of self-
diagnosis.
See subsection 9.5.3 for the list of alarms.
See also each communication manual.
Abnormalities appear in measurement.
: Areas where self-diagnostic offers support
Is process variable
itself abnormal?
Inspect the
process system.
Isolate problem in
measurement system.
Does problem exist in
receiving instrument?
Check/correct
environmental conditions.
Inspect receiver.
Check transmitter.
Check/correct operating
conditions.
Measurement system problem
F0906.ai
YES
NO
NO
YES
Environmental conditions
Operating conditions
Transmitter itself
Figure 9.6
Basic Flow and Self-Diagnostics
9.5.2 Troubleshooting Flowcharts
Check display of the error code.
Check self-diagnostics by configuration tools.
Does the self-diagnostic
indicate problem location?
Contact Yokogawa service personnel.
F0907.ai
The following sorts of symptoms indicate that transmitter
may not be operating properly.
Example : • There is no output signal.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.
Fix pressure leaks, paying particular
attention to connections for impulse
piping,pressure-detector section, etc.
Fully open valve.
Are valves opened or
closed correctly?
Is there any pressure leak?
YES
NO
YES
NO
NO
YES
Refer to Alarm Message Summary in
Subsection 9.5.3.
Is the
Field Wireless Network
setting correct?
NO
YES
Reconnect to the Field Wireless
Network.
Connect an configuration tool and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
Contact Yokogawa service personnel.
F0908.ai
Are valves opened or
closed correctly?
Refer to Alarm Message Summary in
Subsection 9.5.3.
YES
NO
Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.
Fully open valve.
NO
YES
YES
NO
Adjust the zero point.
NO
YES
Is there any pressure leak?
Is zero point
adjusted correctly?
Output travels beyond 0% or 100%.
Connect an configuration tool and check self-diagnostics.
Contact Yokogawa service personnel.
F0909.ai
Are valves opened or
closed correctly?
Is impulse piping
connected correctly?
Refer to Alarm Message Summary in
each communication manual to take
actions.
Provide lagging and/or cooling, or allow
adequate ventilation.
Refer to subsection 9.2 "Calibration
Instruments Selection".
Fully open valve.
Refer to individual model user manuals
and connect piping as appropriate for
the measurement purpose.
Adjust the output.
Is transmitter
installed where there is
marked variation in
temperature?
Is output adjusted correctly?
Large output error.
Does the self-
diagnostic indicate problem
location?
Were appropriate
instruments used for
calibration?
YES
NO
YES
NO
NO
YES
NO
YES
NO
YES
NO
YES
9.5.3 Alarms and Countermeasures
Various diagnostics of the Al2 object and the static pressure is not supported in this instrument.
Table 9.3
Alarms Message Summary (Causes and Actions)
Integral
indicator
Factory
NAMUR
category
Bit
DIAG_STATUS
DIAG_STATUS_DETAIL
Cause
Release/
recovery
conditions
(except
restart)
Action
AL. 01
CAP. ERR
F
Bit 26
Faults
in sensor or
actuator
element
FC_SENSOR_FAIL
Pressure sensor
failure
Recovers only
when AUTO
RECOVER is
ON and within
the range
Replace the
capsule.
FR_SENSOR_FAIL
FC_UNOSC_FAIL
Recovers only
when AUTO
RECOVER
is ON and
oscillation does
not stop
FR_UNOSC_FAIL
CAP_T_SENSOR_FAIL
Capsule
temperature
sensor failure
None
CAP_EEPROM_FAIL
Capsule
EEPROM
memory failure
Recovers when
A or B returns
to normal.
CAP_EEP_IRREGULAR
None
AL. 02
AMP. ERR
F
Bit 27
Faults in
electronics
AMP_T_SENSOR_FAIL
Amplifier
temperature
sensor failure
None
Replace the
amplifier.
AMP_EEPROM_FAIL
AMP_EEP_IRREGULAR
Amplifier
EEPROM failure
None
FC_DELTA_T_FAIL
FR_DELTA_T_FAIL
AMP_F1_ERROR
G_A_COMM_FAIL
WL_AD_FAIL
Amplifier failure
None
AL. 10
PRESS
C
Bit 23
Outside sensor
limits
DP_OUTSIDE_LIMIT
Pressure
outside of
specified range
Recovers when
input pressure
returns within
the range.
Check
the input
pressure.
AL. 11
ST. PRSS
SP_OUTSIDE_LIMIT
Static pressure
outside of
specified range
Recovers when
static pressure
returns within
the range.
Check
the input
pressure.
AL. 12
CAP. TMP
CAPT_OUTSIDE_LMIT
Capsule
temperature
outside of range
(-50 to 130°C)
Recovers when
temperature
returns within
the range.
Retain heat
or insulate
so that
temperature
returns within
the specified
range.
AL. 13
AMP. TMP
AMPT_OUTSIDE_LIMIT
Amplifier
temperature
outside of range
(-50 to 95°C)
Recovers when
temperature
returns within
the range.
Retain heat
or insulate
so that
temperature
returns within
the specified
range.
Power is critical
low:
maintenance
need short -
term
WL_DEEPSLP_ALM
Low remaining
battery power
results in
switching to
deep sleep.
None
Replace the
batteries.
AL. 70
LOW. BAT
M
Bit 19
Power is
low:
maintenance
need mid - term
WL_LOWBAT_ALM
Low remaining
battery power
None
Replace the
batteries.
AL. 60
AI OOS
C
Bit 24
O/S
AI1_OUT_OF_SERVICE
AI1 block is O/S
mode.
Returns when
the mode target
of AI1 block is
other than O/S.
Set the mode
target to
AUTO.
AL. 61
AI OOS
AI2_OUT_OF_SERVICE
AI2 block is O/S
mode.
Returns when
the mode target
of AI2 block is
other than O/S.
Set the mode
target to
AUTO.
AL. 62
AI OOS
AI3_OUT_OF_SERVICE
AI3 block is O/S
mode.
Returns when
the mode target
of AI3 block is
other than O/S.
Set the mode
target to
AUTO.
AI1 block is
simulate mode.
Returns when
the simulate
mode of AI1
block is set
to disable. 1
(Disable)
Check the
simulate
mode of AI1
block.
AL. 64
AI SIM
SimulationActive
(AI2)
AI2 block is
simulate mode.
Returns when
the simulate
mode of AI2
block is set
to disable. 1
(Disable)
Check the
simulate
mode of AI2
block.
AL. 65
AI SIM
C
Bit 17
Simulation is
active
SimulationActive
(AI3)
AI3 block is
simulate mode.
Returns when
the simulate
mode of AI3
block is set
to disable. 1
(Disable)
Check the
simulate
mode of AI3
block.
“Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
Alarm Message Summary (Output Actions)
Integral
Indicator
Factory
NAMUR
category
Bit
DIAG_STATUS
DIAG_STATUS_DETAIL
Output actions
Pressure
Static
Pressure
Capsule
Temp
Value
Amp
Temp
Value
AL. 01
CAP. ERR F
Bit 26
Faults
in sensor or
actuator
element
FC_SENSOR_FAIL
Output value
(hold value)
Output status
(BAD: Sensor
Failure)
Output value
(hold value)
Output status
(BAD: Sensor
Failure)
Normal action
Normal action
FR_SENSOR_FAIL
FC_UNOSC_FAIL
FR_UNOSC_FAIL
CAP_T_SENSOR_FAIL
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Subnormal)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Subnormal)
Output value
(calculated in
a normal way)
Output status
(BAD: Sensor
Failure)
CAP_EEPROM_FAIL
Output value
(hold value)
Output status
(BAD: Device
Failure)
Output value
(hold value)
Output status
(BAD: Device
Failure)
Output value
(calculated in
a normal way)
Output status
(BAD: Device
Failure)
Output value
(calculated in
a normal way)
Output status
(BAD: Device
Failure)
CAP_EEP_IRREGULAR
AL. 02
AMP.ERR F
Bit 27 Faults in
electronics
AMP_T_SENSOR_FAIL
Normal action Normal action Normal action
Output value
(calculated in
a normal way)
Output status
(BAD: Sensor
Failure)
AMP_EEPROM_FAIL
Output value
(hold value)
Output status
(BAD: Device
Failure)
Output value
(hold value)
Output status
(BAD: Device
Failure)
Output value
(calculated in
a normal way)
Output status
(BAD: Device
Failure)
Output value
(hold value)
Output status
(BAD: Device
Failure)
AMP_EEP_IRREGULAR
FC_DELTA_T_FAIL
Output value
(hold value)
output status
(BAD: Device
Failure)
Output value
(hold value)
Output status
(BAD: Device
Failure)
Normal action
Output value
(hold value)
output status
(BAD: Device
Failure)
FR_DELTA_T_FAIL
AMP_F1_ERROR
Output value
(calculated in
a normal way)
Output status
(BAD: Device
Failure)
Output value
(calculated in
a normal way)
Output status
(BAD: Device
Failure)
G_A_COMM_FAIL
WL_AD_FAIL
Bit 23 Outside sensor
limits
DP_OUTSIDE_LIMIT
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Subnormal)
Normal action Normal action
AL. 11
ST. PRSS
SP_OUTSIDE_LIMIT
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Subnormal)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
Normal action Normal action
AL. 12
CAP. TMP
CAPT_OUTSIDE_LIMIT
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Subnormal)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Subnormal)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
Normal action
AL. 13
AMP. TMP
AMPT_OUTSIDE_LIMIT
Normal action Normal action Normal action
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
AL. 53
P. SDEV
C
Bit 25
Installation,
calibration
problem
DP_TRIM_SPAN_
OUTSIDE
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Engineering
Unit Range
Violation)
Normal action Normal action Normal action
AL. 53
P. ZDEV
DP_TRIM_ZERO_
OUTSIDE
Normal action Normal action Normal action Normal action
AL. 55
SP. SDEN
SP_TRIM_SPAN_
OUTSIDE
Normal action Normal action Normal action Normal action
AL. 55
SP.ZDEN
SP_TRIM_ZERO_
OUTSIDE
Normal action Normal action Normal action Normal action
AL. 79
OV. DISP
LCD_OUTSIDE_LIMIT
Normal action Normal action Normal action Normal action
AL. 30
RANGE
O
Bit 22
Environmental
conditions out
of device
specification
DP_OUTSIDE_RANGE
Normal action Normal action Normal action Normal action
AL. 31
SP. RNG
SP_OUTSIDE_RANGE
Normal action Normal action Normal action Normal action
AL. 70
LOW.BAT M
Bit 20
Power is
critical
low:
maintenance
need
short - term
WL_DEEPSLP_ALM
Normal action Normal action Normal action Normal action
LOW. BAT M
Bit 19
Power is
low:
maintenance
need
mid - term
WL_LOWBAT_ALM
Normal action Normal action Normal action Normal action
AL. 60
AI OOS
C
Bit 24 O/S
AI1_OUT_OF_SERVICE
Normal action Normal action Normal action Normal action
AL. 61
AI OOS
AI2_OUT_OF_SERVICE
Normal action Normal action Normal action Normal action
AL. 62
AI OOS
AI3_OUT_OF_SERVICE
Normal action Normal action Normal action Normal action
AL. 63
AI SIM
C
Bit 17 Simulation is
active
SimulationActive
(AI1)
Normal action Normal action Normal action Normal action
AL. 64
AI SIM
SimulationActive
(AI2)
Normal action Normal action Normal action Normal action
AL. 65
AI SIM
SimulationActive
(AI3)
Normal action Normal action Normal action Normal action
“Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
<10. Parameter Summary>
10-1
IM 01C27F01-01EN
10. Parameter Summary
The setting of differential pressure (Al2 block) is invalid in this instrument. The output value of Al2 object and
the output status are “0.0”(zero) and “Uncertain” respectively.
Various diagnostics of the Al2 object and the static pressure is not supported in this instrument.
Table 10.1
Parameter
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
1.
UAPMO
block
1
VERSION_
REVISION
Indicates the application revision of EJX This revision
when the application software is downloaded.
---
R
10
ST_REV
Indicates the revision level of the fixed parameters of
UAP Used, for example, to check whether parameters
have been change.
0
R
64
IDENT_NUMBER
Indicates the vender ID, model ID, and revision of the
device.
---
R
65
CTS_VERSION
Indicates the version of the communication stack test
system (CTS).
0
R
66
ITS_VERSION
Indicates the version of the inter operability test system
(ITS).
0
R
67
DIAG_STATUS
Indicates the diagnostic results of the device based on
the NAMUR NE0107* model.
Setting DIAG_STATUS to ON allows turning OFF
and ON the display of the diagnostic results for each
summary, and changing Categorize For Categorize at
the time of shipment, refer to tables 8.3 and 10.2.
0
R
68
UAP_OPTION
Allows setting the DIAG_STATUS and write protection
of UAP.
DIAG_STATUS configuration
1: Enable, 0: Disable (default)
Hardware Write Protect
1: Enable, 0: Disable (default)
Software Write Protect
1: On, 0: Off
The following table shows the relationship between the
hardware write protection and software write protection.
Hardware
write
protect
Hardware
switch
condition
Software
write
protect
Write
protect
Disable
Off or On
Off
No
Disable
Off or On
On
Protected
Enable
Off
Off or On
No
Enable
On
Off or On
Protected
0
W
69
DIAG_SWITCH
Allows setting On/Off for each summary of DIAG_
STATUS when UAP_OPTION is set to Enable and
DIAG_STATUS is set to Enable.
0
W
70
DIAG_CONFIG
Allows Categorize for each summary of DIAG_STATUS
when UAP_OPTION is set to Enable and DIAG_
STATUS is set to Enable.
Refer to Table
10.2.
W
102
DIAG_STATUS_
DETAIL[2]
Detailed information on DIAG_STATUS. For Categorize
at the time of shipment, refer to Table 10.2.
Refer to Table
10.2.
R
103
ENERGY_LEFT
Indicates the number of days of remaining battery life
assuming ambient temperature condition as 23 degrees
Celsius.
The unit is day.
---
R
104
RESET_ENERGY_
LEFT
Initialize the remaining battery life (ENERGY_LEFT) and
reset it as new batteries.
Perform the battery replacement.
0 = Continue
1 = Reset
0 (reading value
is always 0)
W
<10. Parameter Summary>
10-2
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
1.UAPMO
block
(continued)
105
POWER_
SUPPLY_STATUS
Indicates the battery level and the power supply
method.
0 = external power supply
1 = battery level 75% or more
2 = battery level 25% ~ 75%
3 = battery level 25% or less
R
110
HW_WRITE_
PROTECT
Allows recognizing the status of the hardware write
protection switch.
(Switch Off, Switch On)
R
111
RADIO_SILENCE
Repeats a cycle of a 1-hour pause and 6-minute
search if the instrument cannot join the network after a
time specified in RADIO_SILENCE has elapsed.
28800
W
2.
UDO
block
2
DESCRIPTION
Indicates the version and model information of the
downloaded data.
---
R
3
STATE
Indicates the present transition state.
---
R
5
MAX_BLOCK_
SIZE
Maximum block size. This value is smaller than the
maximum data size of APDU.
---
R
14
LAST_BLOCK_
DOWNLOADED
Indicates the last downloaded block number.
0 means that no block has been downloaded.
---
R
16
ERROR_CODE
Indicates the error codes for DLError.
0 = noError
1 = Timeout
2 = ClientAbort
64 = Apply failure
---
R
3.
CO
block
1
REVISION
Indicates the version level of COMM_ENDPOINT, etc.
---
R
2
COMM_
ENDPOINT
Indicates the Endpoint information. The following
shows the components.
1. Network address of remote endpoint
2. Transport layer port at remote endpoint
3. Object ID at remote endpoint
4. Stale data limit
5. Data publication period
6. Ideal publication phase
7. PublishAutoRetransmit
8. Configuration status
---
W
3
COMM_
CONTRACT
Indicates the Contract information. The following
shows the components.
1. ContractID
2. Contract_Status
3. Actual_Phase
---
R
4
PUB_ITEM_MAX
Maximum PUB_ITEM value
---
R
5
PUB_ITEM_NUM
PUB_ITEM number
---
R
6
PUB_ITEM
Indicates the PUB_ITEM information. The following
shows the components
1. ObjectID
2. AttributeID
3. AttributeIndex
4. Size
---
W
<10. Parameter Summary>
10-3
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
4.
TRANSDUCER
block
1
TAG_DESC
Memo field available to write anything.
Transducer
W
2
AUTO_
RECOVERY
Allows specifying the action when the cause of a
sensor failure is removed.
OFF (=0):
AL continues to be indicated
even after the cause of the sensor
error is removed, and the BURN
OUT state is not released.
ON (=1):
The AL indication for sensor
failure disappears and normal
action is resumed when the cause
of the sensor failure is removed.
ON
W
3
MODEL
Indicates the model name of the transmitter.
---
R
4
SENSOR_SN
Indicates the device number of the transmitter.
---
R
5
MEASUREMENT
_RATE
Indicates the measurement period of process values.
---
R
6
MEASURE_
MODE
Measurement mode selects continuous mode or
intermittent mode.
When the update time is set to 1 in intermittent mode,
the mode is automatically switched to continuous
mode.
When the update time is set to 1 second, the
computation process is in continuous mode,
regardless of the measurement mode.
intermittent
mode
W
7
WIRELESS_
STATUS
Indicate the communication status.
1. Indicates the initial idle status or join status.
(idle status, join status)
2. Indicates whether Contract(Pub) is established.
(not establishment, establishment)
3. Indicates whether Contract(R/W) is
established.
(not establishment, establishment)
1. idle status
2. not
estabilishment
3. not
esabilishment
R
8
DISPLAY_SEL
Select the LCD display contents.
1. Indicates display status of PV Value of AI1
(displayed, not displayed)
2. Indicates display status of PV Value of AI2
(displayed, not displayed)
3. Indicates display status of PV Value of AI3
(displayed, not displayed)
1. displayed
2. not
displayed
3. not
displayed
W
9
LCD_MODE
Select the LCD mode
1. Indicates the ON mode. (off, intermittent)
2. Indicates whether continuous or not.
(continuous off, continuous on)
3. EJX does not use.
4. Indicates the bar graph display.
(bar graph not displayed, bar graph displayed)
1. OFF
2. continuous
OFF
3. ---
4. bar graph
not displayed
W
10
SPECIAL_CMD
Special function parameter.
0 = initialize value at READ (None)
1 = EJX does not use.
2 = deep sleep status
To start from deep sleep mode, either remove and
insert the battery pack, or use the configuration tool.
0
W
11
SPECIAL_
ORDER_ID
Displays the special order number, if applicable.
---
R
12
UNIT_SEL1
Selects whether to automatically apply the unit to the
word for the parameter for which the unit display is
selected, or apply the characters that are written to
DISPLAY_UNIT. (Auto, Custom)
Auto
W
13
DISPLAY_UNIT1
When Custom is selected in UNIT_SEL1, set the
display unit using 6 characters or less.
NULL
W
<10. Parameter Summary>
10-4
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
5.
AI1 block
1
PV
AL1 is a pressure output object.
Indicates the primary analog value (or corresponding
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
1. Value = ---
2. Status = ---
W
2
MODE
A universal parameter to indicate the block’s operation
status. Each O/S, Auto, and Man can select from.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by
Target of Al object.
4. Normal : Indicate normal status mode of Al
object.
1.
Target=O/S
2.
Actual=O/S
3.
Permitted=
O/S
4.
Normal=O/S
W
3
CONC_OID
Indicates the Concentrator object value that
corresponds to the data update of the PV value.
3
R
4
SCALE
Allows specifying the upper or lower limit for the PV
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the
PV value.
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
1. EU at 100%
= 100
2. EU at 0%
= 0
3. Units Index
= %
4. Decimal = 2
W
26
TAG_DESC
A universal parameter to store the comment that
describes the tag
Al1:
Differential
Pressure
W
27
PV_FTIME
Allows adjusting the time constant for filtering the PV
value. Setting unit: Second. This is enabled for the
Continuous mode.
0 sec
W
28
SIMULATE_
SWITCH
A simulation function switch for the AI object test
(Disable, Enable)
1 (Disable)
W
29
TRANSDUCER_
VALUE
When SIMULATE_SWITCH is set to Disable, this
value is used as the input value for the AI object. Refer
to Figure 10.1.
Disable
R
30
SIMULATE_
VALUE
When SIMULATE_SWITCH is set to Enable, this value
is used as the input value for the AI object.
The input value can be changed.
---
W
51
UPPER_LIM
Indicates the upper limit (URL) for the pressure.
---
R
52
LOWER_LIM
Indicates the lower limit (LRL) for the pressure.
---
R
53
PV_RANGE
Sets the measurement range.
1. EU at 100% : Indicates input value of the upper
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the
measurement range.
4. Decimal : Indicates the digit number below the
decimal point.
EU at 100%
= 100
EU at 0%
= 0
Units Index
= kPa (1133)
Decimal
= 2
W
54
LIN_TYPE
Select either No Linearization or Square root as a
setting of the output range.
0 = No Linearization :
Provides an output value scaled according to the
PV_RANGE and SCALE range settings.
(To use Direct with FF, set the same value for
PV_RANGE and SCALE.)
10 = Square root :
Provides a square root output computed for the
value scaled according to the PV_RANGE and
SCALE range settings.
0
W
<10. Parameter Summary>
10-5
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
5.
AI1
block
(continued)
55
FLOW_
CONSTANT
Indicates the flow coefficient, which shows the
correlation between the flow rate value and square root
value of the differential pressure.
1.0
W
56
LOW_CUTOFF
Specifies the low cut value. The unit is subject to
SCALE:Units Index.
10
W
57
CAL_CMD
Specifies the calibration method.
0 = CAL_NONE : Initial state in which calibration is
not performed
1 = CAL_LOW : Applies an actual input and adjusts
the lower limit using the value specified in CAL_
POINT_LO.
2 = CAL_HIGH : Applies an actual input and adjusts
the higher limit using the value specified in CAL_
POINT_HI.
5 = CAL_CLEAR : Clears the adjustment variable.
0 (reading
value is
always 0)
W
58
CAL_STATUS
Indicates the calibration status.
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status
when the adjustment variable is outside of range.
---
R
59
CAL_POINT_HI
Specifies the higher limit adjustment variable for
adjustment between two points.
---
W
60
CAL_POINT_LO
Specifies the lower limit adjustment variable for the
adjustment between two points.
---
W
61
CAL_MIN_SPAN
Indicates the minimum span of the adjustment
variable.
---
R
104
EXTERNAL_
ZERO_TRIM
Allows performing external zero adjustment.
(Trim on, Trim off)
Trim on
W
105
LOWCUT_MODE
Specifies the low cut mode.
(Linear, Zero)
Linear
W
106
H/L_SWAP
Allows performing reverse connection of the impulse
line.
(NORMAL, REVERSE : reverse connection)
Used when the lower pressure side and higher
pressure side of the impulse line were connected
wrongly when installing the pressure transmitter.
Normal
W
107
T_ZERO_CMP
Parameter to select the temperature zero shift
compensation mode
0 = OFF : Does not perform temperature zero shift
compensation.
1 = ON : Performs temperature zero shift
compensation.
Off
w
108
TEMP_ZERO
Parameter to set the temperature gradient value for the
temperature zero shift compensation
0
w
109
TEMP_SELECT
Parameter to select the temperature (amplifier-side
/ capsule-side) used for the temperature zero shift
compensation.
0 = AMP TEMP : the value of the amplifier-side
temperature sensor is used.
1 = CAP TEMP : the value of the capsule-side
temperature sensor is used.
1
w
<10. Parameter Summary>
10-6
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
6.
AI2
block
1
PV
AI2 is a static pressure output object.
Indicates the primary analog value (or corresponding
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
---
W
2
MODE
A universal parameter to indicate the block’s operation
status. O/S, Auto, and Man can be selected.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by Target
of Al object.
4. Normal : Indicate normal status mode of Al object.
1.Target
= O/S
2.Actual
= O/S
3.Permitted
= O/S
4.Normal
= O/S
W
3
CONC_OID
Indicates the Concentrator object value that
corresponds to the data update of the PV value.
3
R
4
SCALE
Allows specifying the upper or lower limit for the PV
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the
PV value.
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
1. EU at 100%
= 100
2. EU at 0%
= 0
3. Units Index
= %
4. Decimal
= 2
W
26
TAG_DESC
A universal parameter to store the comment that
describes the tag.
AI2: Static
Pressure
W
27
PV_FTIME
Allows adjusting the time constant for filtering the PV
value. Setting unit: Second. This is enabled for the
Continuous mode.
0 sec
W
28
SIMULATE_
SWITCH
A simulation function switch for the AI object test
(Disable, Enable)
Disable
W
29
TRANSDUCER_
VALUE
When SIMULATE_SWITCH is set to Disable, this
value is used as the input value for the AI object.
---
R
30
SIMULATE_
VALUE
When SIMULATE_SWITCH is set to Enable, this value
is used as the input value for the AI object.
The input value can be changed.
---
W
51
UPPER_LIM
Indicates the upper limit (URL) for the pressure.
---
R
52
LOWER_LIM
Indicates the lower limit (LRL) for the pressure.
---
R
53
PV_RANGE
Sets the measurement range.
1. EU at 100% : Indicates input value of the upper
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the
measurement range.
4. Decimal : Indicates the digit number below the
decimal point.
1. EU at
100% =
25000.000000
EU at 0%
= 0
Units Index
= kPa
Decimal
= 2
W
<10. Parameter Summary>
10-7
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
6.
AI2
block
(continued)
54
LIN_TYPE
Select either No Linearization or Square root as a
setting of the output range.
0 = No Linearization :
Provides an output value scaled according to the
PV_RANGE and SCALE range settings.
(To use Direct with FF, set the same value for
PV_RANGE and SCALE.)
10 = Square root :
Provides a square root output computed for the
value scaled according to the PV_RANGE and
SCALE range settings.
0
W
55
FLOW_
CONSTANT
Indicates the flow coefficient, which shows the
correlation between the flow rate value and square root
value of the pressure.
1.0
W
56
LOW_CUTOFF
Specifies the low cut value. The unit is subject to
SCALE : Units index.
10
W
57
CAL_CMD
Specifies the calibration method.
0 = CAL_NONE : Initial state in which calibration is
not performed
1 = CAL_LOW : Applies an actual input and adjusts
the lower limit using the value specified in CAL_
POINT_LO.
2 = CAL_HIGH : Applies an actual input and adjusts
the higher limit using the value specified in CAL_
POINT_HI.
5 = CAL_CLEAR : Clears the adjustment variable.
0 (reading
value is
always 0)
W
58
CAL_STATUS
Indicates the calibration status.
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status
when the adjustment variable is outside of range.
R
59
CAL_POINT_HI
Specifies the higher limit adjustment variable for
adjustment between two points.
---
W
60
CAL_POINT_LO
Specifies the lower limit adjustment variable for the
adjustment between two points.
---
W
61
CAL_MIN_SPAN
Indicates the minimum span of the adjustment
variable.
---
R
102
SP_VALUE_TYPE
Selects the gauge pressure or the absolute pressure.
Abs
W
103
SP_SELECT
Parameter to select the High-side pressure or the Low-
side pressure as the static pressure output.
0 = High : Displays the H-side pressure as the static
pressure
1 = Low : Displays the L-side pressure as the static
pressure
High
W
<10. Parameter Summary>
10-8
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
7.
AI3
block
1
PV
Al3 is a temperature pressure output object.
Indicates the primary analog value (or corresponding
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
1. Value = ---
2. Status = ---
W
2
MODE
A universal parameter to indicate the block’s operation
status. O/S, Auto, and Man can be selected.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by Target
of Al object.
4. Normal : Indicate normal status mode of Al object.
1. Target = O/S
2. Actual = O/S
3. Permitted
= O/S
4. Normal =
O/S
W
3
CONC_OID
Indicates the Concentrator object value that
corresponds to the data update of the PV value.
3
R
4
SCALE
Allows specifying the upper or lower limit for the PV
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the
PV value.
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
1. EU at 100%
= 100
2. EU at 0%
= 0
3. Units Index
= %
4. Decimal = 2
W
26
TAG_DESC
A universal parameter to store the comment that
describes the tag
AI3: Capsule
temperature
W
27
PV_FTIME
Allows adjusting the time constant for filtering the PV
value.
Setting unit: Second. This is enabled for the
Continuous mode.
0 sec
W
28
SIMULATE_
SWITCH
A simulation function switch for the AI object test
(Disable, Enable)
Disable
W
29
TRANSDUCER_
VALUE
When SIMULATE_SWITCH is set to Disable, this
value is used as the input value for the AI object.
---
R
30
SIMULATE_
VALUE
When SIMULATE_SWITCH is set to Enable, this value
is used as the input value for the AI object.
The input value can be changed.
---
W
53
SENSOR_RANGE
Parameter to nondimensionalize the sensor output
value.
The temperature unit can selects from K, degC, and
degF.
1. EU at 100% : Indicates input value of the upper
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the
measurement range.
4. Decimal : Indicates the digit number below the
decimal point.
1. EU at 100%
= 130
2. EU at 0%
= -50
3. Units Index
= deg C
4. Decimal = 0
W
102
TERTIARY_
VALUE_SEL
Specifies either the capsule temperature or amplifier
temperature as the output value.
(CAP, AMP)
CAP
W
(Note) Handling: R=Read only, W=Read & Write
(Note) “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
<10. Parameter Summary>
10-9
IM 01C27F01-01EN
Table 10.2
DIAG_STATUS_DETAIL[0]
No
Bit
DIAG_STATUS_DETAIL
Description
DIAG_STATUS
assignment bit
NAMUR
DiagnosticDetail_1
1
31
FC_SENSOR_FAIL
C sensor frequency error
Bit26
F
2
30
FR_SENSOR_FAIL
R sensor frequency error
Bit26
F
3
29
CAP_T_SENSOR_FAIL
Capsule temperature sensor failure
Bit26
F
4
28
CAP_EEPROM_FAIL
Capsule EEPROM failure
Bit26
F
5
27
CAP_EEP_IRREGULAR
CAP EEPROM version not correct
Bit26
F
6
26
AMP_T_SENSOR_FAIL
Amplifier temperature sensor failure
Bit27
F
7
25
AMP_EEPROM_FAIL
Amplifier EEPROM failure
Bit27
F
8
24
AMP_EEP_IRREGULAR
AMP EEPROM version not correct
Bit27
F
9
23
AMP_F1_ERROR
F1 error
Bit27
F
10
22
G_A_COMM_FAIL
G/A failure
Bit27
F
11
21
FC_UNOSC_FAIL
C sensor oscillation stop failure
Bit26
F
12
20
FC_DELTA_T_FAIL
C-side deltaT circuit failure
Bit27
F
13
19
FR_DELTA_T_FAIL
R-side deltaT circuit failure
Bit27
F
14
18
WL_AD_FAIL
Battery voltage not detected (AMP failure)
Bit27
F
15
17
FR_UNOSC_FAIL
R sensor oscillation stop failure
Bit26
F
17
15
DP_OUTSIDE_LIMIT
Pressure outside of specified range
Bit23
C
18
14
SP_OUTSIDE_LIMIT
Static pressure outside of specified range
Bit23
C
19
13
CAPT_OUTSIDE_LIMIT
Capsule temperature outside of specified
range
Bit23
C
20
12
AMPT_OUTSIDE_LIMIT
Amplifier temperature outside of specified
range
Bit23
C
22
7
DP_OUTSIDE_RANGE
Input pressure setting outside of range
Bit22
O
23
6
SP_OUTSIDE_RANGE
Static pressure setting outside of range
Bit22
O
DiagnosticDetail_2
24
31
AI1_OUT_OF_SERVICE
AI1 O/S mode
Bit24
C
25
30
AI2_OUT_OF_SERVICE
AI2 O/S mode
Bit24
C
26
29
AI3_OUT_OF_SERVICE
AI3 O/S mode
Bit24
C
27
28
AI1_SIMULATION_ACTIVE
AI1 simulation mode
Bit17
C
28
27
AI2_SIMULATION_ACTIVE
AI2 simulation mode
Bit17
C
29
26
AI3_SIMULATION_ACTIVE
AI3 simulation mode
Bit17
C
33
20
DP_TRIM_SPAN_OUTSIDE
Pressure span adjustment variable outside of
range
Bit25
C
34
19
DP_TRIM_ZERO_OUTSIDE
Pressure zero adjustment variable outside of
range
Bit25
C
38
15
SP_TRIM_SPAN_OUTSIDE
Static pressure span adjustment variable
outside of range
Bit25
C
39
14
SP_TRIM_ZERO_OUTSIDE
Static pressure zero adjustment variable
outside of range
Bit25
C
40
13
WL_LOWBAT_ALM
Low battery
Bit19
M
41
10
WL_DEEPSLP_ALM
Deep sleep due to low battery
Bit20
M
42
8
LCD_OUTSIDE_LIMIT
LCD display outside of specified range
Bit25
C
F1001.ai
AI algoritm
MODE Target
from operator
from operator
from operator
from transducer
SIMULATE
On
Off
AI
algorithm
Linearization
scaling,
filter
Alert
report
HiHi etc
PV
Auto
O/S
Man
Publish
Value
& Status
PV
PV
Value
& Status
Value
& Status
Value
& Status
Mode and
PV.Status handling
SWITCH
SIMULATE
_VALUE
Figure 10.1
Example schema of analog input object
<11. General Specifications>
11-1
IM 01C27F01-01EN
11. General Specifications
11.1 Standard Specifications
Communication protocol:
ISA100.11a protocol
Data rate:
250 kbps
Frequency:
2400 - 2483.5 MHz license free ISM band
Radio security:
AES 128 bit codified
RF Transmitter power:
Max. 11.6 dBm (fixed)
Antenna:
+2 dBi Omni directional monopole type
Span and range limits:
(For EJX510B, values are in absolute and lower
range limits are 0.)
T01E.ai
Span
Span
Range
Range
Range
Range
Span
–1 to 20
1 to 50
–1 to 100
2 to 100
0.4 to 20
145 to 7200
10 to 500
8 to 200 kPa
–0.1 to 10
–0.1 to 2
0.04 to 2
–100 to 200 kPa
–14.5 to 1450
0.2 to 10
1.16 to 29
–14.5 to 29
5.8 to 290
–14.5 to 290
29 to 1450
Span
–1 to 2
10 to 500
–1 to 500
–14.5 to 7200
–0.1 to 50
–1 to 500
2 to 100
–1 to 2
0.08 to 2
0.4 to 20
–1 to 20
–1 to 100
A
D
0.08 to 2
C
B
kgf/cm2 (/D4)
MPa
Measurement
Span/Range
psi (/D1)
bar (/D3)
Performance specifications:
Refer to GS 01C27F01-01EN.
Output:
Wireless (ISA100.11a protocol) 2.4GHz signal
Update Time:
Measurement mode
Pressure
Continuous
100 msec
Intermittent
1 to 3600 sec selectable
If the update time is set at one second, the transmitter
shifts to the continuous mode.
Zero Adjustment Limits:
Zero can be fully elevated or suppressed, within
the lower and upper range limits of the capsule.
External Zero Adjustment:
External zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator
with range-setting switch.
Integral Indicator (LCD display):
5-digit numerical display, 6-digit unit display
and bar graph. The indicator is configurable
to display one or up to two of the following
variables periodically.;
Pressure and temperature.
Burst Pressure:
A, B and C capsule: 30MPa
D capsule: 132MPa
Self Diagnostics:
Capsule failure, amplifier failure,
configuration error, battery alarm,
wireless communication alarm,
and over-range error for process variables.
Ambient Temperature Limits:
-40 to 85ºC(-40 to 185°F)
-30 to 80ºC(-22 to 176°F) LCD visible range
Process Temperature Limits:
-40 to 120ºC(-40 to 248°F)
Ambient Humidity Limits:
0 to 100% RH
<11. General Specifications>
11-2
IM 01C27F01-01EN
Working Pressure Limits (Silicone oil):
Maximum Pressure Limits
Pressure
Capsule
EJX510B
EJX530B
A
200 kPa abs
(29 psia)
200 kPa (29 psig)
Bi
2 MPa abs (290 psia)
2 MPa (290 psig)
C
10 MPa abs
(1450 psia)
10 MPa
(1450 psig)
D
50 MPa abs
(7200 psia)
50 MPa
(7200 psig)
Minimum Pressure Limit
See graph below
-40
(-40)
0
(32)
40
(104)
80
(176)
120 (248)
0.1(0.75)
0.13(1)
1(7.5)
100(750)
10(75)
2.7(20)
0.01(0.075)
0.013(0.1)
85
(185)
(mmHg abs)
Working
pressure
kPa abs
Applicable range
Process temperature °C ( °F)
F01E.ai
Atmospheric
pressure
-40
(-40)
0
(32)
40
(104)
80
(176)
120
(248)
1(0.14)
2.7(0.38)
10(1.4)
(psia)
100(14.5)
Process temperature °C ( °F)
Working
pressure
kPa abs
Applicable range
F02E.ai
Maximum Over Pressure
Pressure
Capsule
EJX510B
EJX530B
A and B
4 MPa abs (580 psia)
4 MPa (580 psig)
C
20 MPa abs
(2900 psia)
20 MPa
(2900 psig)
D
75 MPa abs
(10800 psia)
75 MPa
(10800 psig)
Connections:
Refer to “MODEL AND SUFFIX CODES.”
Wetted Parts Materials:
Diaphragm, Process Connector
Refer to “MODEL AND SUFFIX CODES.”
Non-wetted Parts Materials:
Housing
Low copper cast aluminum alloy with
polyurethane, mint-green paint (Munsell
5.6BG 3.3/2.9 or its equivalent)
Degrees of Protection
IP66/IP67, NEMA4X
Pipe
Polypropylene
Cover O-rings
Buna-N
Name plate and tag
304 SST tag plate wired onto transmitter
Fill Fluid
Silicone, fluorinated oil (optional)
Weight:
Capsule A, B and C: 3.2kg (7.1 lb) *
Capsule D: 3.4kg (7.4 lb) *
*: Without battery pack and mounting bracket.
<11. General Specifications>
11-3
IM 01C27F01-01EN
11.2 Model and Suffix Codes
T03E.ai
Model
Description
Suffix Codes
304 SST 2-inch pipe mounting
None
Absolute pressure transmitter
Gauge pressure transmitter
Wireless communication (ISA100.11a protocol)
8 to 200 kPa
(1.16 to 29 psi)
0.04 to 2 MPa
(5.8 to 290 psi)
0.2 to 10 MPa
(29 to 1450 psi)
1 to 50 MPa
(145 to 7200 psi)
/ Optional specification
Always 0
Cast aluminum alloy
No electrical connection
Process connection
Diaphragm
316L SST#
Hastelloy C-276 *1#
Hastelloy C-276 *1#
Hastelloy C-276 *1#
1/2 NPT female
1/2 NPT male
G1/2 DIN 16 288 male *2
M20×1.5 DIN 16 288 male *2
Digital indicator
Measurement
span (Capsule)
Wetted parts
material *3
EJX510B
EJX530B
Process connections
Mounting bracket
Electrical connection
Optional code
Integral indicator
Output signal
Amplifier housing
—
Always N
—
· · · · · · · · · · · · · · · · · · · · · · · ·
· · · · · · · · · · · · · · · · · · · · · · · ·
-L · · · · · · · · · · · · · · · · · · · · · ·
A · · · · · · · · · · · · · · · · · · · · ·
B · · · · · · · · · · · · · · · · · · · · ·
C · · · · · · · · · · · · · · · · · · · · ·
D · · · · · · · · · · · · · · · · · · · · ·
4 · · · · · · · · · · · · · · · · ·
7 · · · · · · · · · · · · · · · · ·
8 · · · · · · · · · · · · · · · · ·
9 · · · · · · · · · · · · · · · · ·
N · · · · · · · · · · · · · · ·
-0 · · · · · · · · · · · · ·
D · · · · · · ·
F · · · · · ·
N · · · · · ·
7 · · · · · · · · · · · ·
J · · · · · · · · ·
S · · · · · · · · · · · · · · · · · ·
H · · · · · · · · · · · · · · · · · ·
►
The “►” marks indicates the most typical selection for each specification. Example: EJX530B-LAS4N-07JNN/o.
*1:
Hastelloy C-276 or ASTM N10276.
*2:
Not applicable for combination of capsule code D and wetted parts material code H.
*3:
Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid
can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
The ‘#’ marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use
of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for
details.
11.3 OPTIONAL SPECIFICATIONS
OPTIONAL SPECIFICATIONS (For Explosion Protected type)
Approvals under pending
Item
Description
Code
Factory Mutual
(FM)
FM Intrinsically safe Approval
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia
IIC
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups F & G, and Class III, Division 1, Class I, Zone 2, Group IIC, in Hazardous Locations
FS17
CENELEC ATEX
CENELEC ATEX (KEMA) Intrinsically safe Approval
—
Canadian
Standards
Association
(CSA)
CSA Intrinsically safe Approval
[For CSA C22.2]
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups
E, F & G, Class III, Division 1,
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups F
& G, Class III, Division 1
[For CSA E60079]
Ex ia II C T4
CS17
IECEx Scheme
IECEx Intrinsically safe Approval
—
<11. General Specifications>
11-4
IM 01C27F01-01EN
OPTIONAL SPECIFICATIONS
(See Table for Span and
Range Limits.)
Nitrogen(N2) Gas or Water *8
Retention time: one minute
T04E.ai
Degrease cleansing treatment
Degrease cleansing treatment with fluorinated oilfilled capsule.
Operating temperature –20 to 80°C (–4 to 176°F)
Fluorinated oil filled in capsule
Operating temperature –20 to 80°C (–4 to 176°F)
P calibration (psi unit)
bar calibration (bar unit)
M calibration (kgf/cm2 unit)
Process Connector
Test Pressure: 200 kPa (29 psi) *4
Test Pressure: 2 MPa (290 psi) *5
Test Pressure: 10 MPa (1450 psi) *6
Test Pressure: 50 MPa (7200 psi) *7
Description
Code
K1
K2
K3
D1
D3
D4
M15
T05
T06
T07
T08
Item
Oil-prohibited use *10
Capsule fill fluid
Calibration units *2
Material certificate*3
PED 97/23/EC
Category III, Module H, Type of Equipment: Pressure Accessory-Vessel,
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
PE3
European Pressure Equipment
Directive *11
Pressure test
/Leak test certificate *9
Inside of isolating diaphragms (fill fluid side) are gold plated, effective for hydrogen
permeation.
A1
Gold-plated diaphragm *10
Painting
Color change
Coating change
Amplifier cover only
Anti-corrosion coating *1
P
X2
*1:
Not applicable with color change option.
*2:
The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*3:
Material traceability certification, per EN 10204 3.1 B.
*4:
Applicable for capsule code A.
*5:
Applicable for capsule code B.
*6:
Applicable for capsule code C.
*7:
Applicable for capsule code D.
*8:
Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2).
*9:
The unit on the certificate is always kPa/MPa regardless of selection of option code D1, D3 and D4.
*10:
Applicable for wetted parts material code S.
*11:
Applicable for measurement span code D. If compliance with category III is needed, specify this option code.
<11. General Specifications>
11-5
IM 01C27F01-01EN
11.4 Dimensions
Unit: mm (approx. inch)
72
(2.83)
282 (11.10)
162 (6.38)
202 (7.95)
322 (12.68)
140 (5.51)
82*4
(3.23)
12*3
(0.47)
94*2 (3.70)
64
(2.52)
191 (7.52)
199 (7.83)
39
(1.54)
24
(0.94)
Ø110 (4.33)
Open to
atmosphere*1
Mounting bracket
(Optional)
Integral indicator
2-inch pipe
(O. D. 60 mm)
Process connections code 7
Process connections code 4
Process connections code 8 and 9
193
(7.60)
*1: Applicable for EJX530B Measurement span code A, B, and C.
*2: 92 mm (3.62 inch) for Measurement span code D.
*3: 11 mm (0.43 inch) for Measurement span code D.
*4: 80 mm (3.15 inch) for Measurement span code D.
Zero adjustment
Ground terminal
209
(8.23)
)
9
7
.
0
(
0
2
)
0
2
.
0
(
5
ø6
(0.24)
F03E.ai
Infrared Configuration
F04E.ai
Infrared port
: EJX510B and EJX530B
Absolute and Gauge Pressure Transmitters
Manual No.
: IM 01C27F01-01EN
Edition
Date
Page
Revised Item
2nd
Aug. 2010
—
Release of ISA100.11a protocol