Yokogawa Electric Corporation

EJX510B and EJX530B Absolute and Gauge Pressure Transmitters IM 01C27F01-01EN IM 01C27F01-01EN 2nd Edition

EJX510B and EJX530B

Absolute and Gauge Pressure Transmitters IM 01C27F01-01EN 2nd Edition 2nd Edition: Aug. 2010 (YK) All Rights Reserved, Copyright © 2010, Yokogawa Electric Corporation Contents 1. Introduction................................................................................................ 1-1 1.1 Safe Use of This Product ..................................................................................1-2 1.2 Radio Wave.........................................................................................................1-3 1.3 Warranty..............................................................................................................1-3 1.4 Trademarks.........................................................................................................1-3 1.5 ATEX Documentation........................................................................................1-4 2. Handling Cautions..................................................................................... 2-1 2.1 Model and Specifications Check......................................................................2-1 2.2 Unpacking...........................................................................................................2-1 2.3 Storage................................................................................................................2-1 2.4 Selecting the Installation Location .................................................................2-2 2.5 Pressure Connection.........................................................................................2-2 2.6 Restrictions on Use of Radio Transceivers....................................................2-3 2.7 Insulation Resistance and Dielectric Strength Test.......................................2-3 2.8 Installation of an Explosion-Protected Instrument........................................2-4 2.8.1 FM Approval........................................................................................2-4 2.8.2 CSA Certification.................................................................................2-5 2.9 EMC Conformity Standards..............................................................................2-5 2.10 Pressure Equipment Directive (PED) ...................................................2-5 2.11 Low Voltage Directive........................................................................................2-6 2.12 Regulatory Compliance for Radio and Telecommunication.........................2-7 2.12.1 Radio and Telecommunications Terminal Equipment Directive (R&TTE) .....................................................................................................2-7 2.12.2 FCC compliance.................................................................................2-7 2.12.3 Industry Canada (IC) compliance.......................................................2-7 3. Component Names................................................................................... 3-1 4. Installation.................................................................................................. 4-1 4.1 Precautions ........................................................................................................4-1 4.2 Mounting.............................................................................................................4-1 4.3 Rotating Transmitter Section............................................................................4-2 4.4 Changing the Direction of Integral Indicator .................................................4-2 4.5 Changing the direction of the antenna............................................................4-3

Installing Impulse Piping.......................................................................... 5-1

5.1 Impulse Piping Installation Precautions.........................................................5-1 5.1.1 Connecting Impulse Piping to a Transmitter.......................................5-1 5.1.2 Routing the Impulse Piping.................................................................5-1 5.2 Impulse Piping Connection Examples............................................................5-2 6. Grounding.................................................................................................. 6-1 7. Operation.................................................................................................... 7-1 7.1 Preparation for Starting Operation..................................................................7-1 7.2 Zero Point Adjustment......................................................................................7-2 7.3 Starting Operation.............................................................................................7-2 7.4 Connecting to the Field Wireless Network......................................................7-3 7.5 Shutting Down the Transmitter........................................................................7-4 8. Setting Parameters.................................................................................... 8-1 8.1 Environment for parameter setting..................................................................8-1 8.2 Preparing Software for the Configuration Tool..............................................8-1 8.3 Setting Parameters............................................................................................8-2 8.3.1 Parameter Usage and Selection.........................................................8-2 8.3.2 Function Block and Menu Tree...........................................................8-3 8.3.3 Parameters for Wireless Communication.........................................8-10 8.3.4 Tag and Device Information.............................................................. 8-11 8.3.5 Unit.................................................................................................... 8-11 8.3.6 Range Change.................................................................................. 8-11 8.3.7 Output Signal Low Cut Mode Setup................................................. 8-11 8.3.8 Integral Indicator Scale Setup...........................................................8-12 8.3.9 Unit for Displayed Temperature........................................................8-12 8.3.10 Zero Point Adjustment and Span Adjustment...................................8-12 8.3.11 Software Write Protect......................................................................8-14 8.3.12 Switching to Deep Sleep Mode.........................................................8-14 8.3.13 Switching to Silence Mode................................................................8-14 8.4 Self-Diagnostics...............................................................................................8-15 8.4.1 Identify Problems by Using the Communicator................................8-15 8.4.2 Checking with Integral Indicator........................................................8-17 9. Maintenance............................................................................................... 9-1 9.1 Overview.............................................................................................................9-1 9.2 Calibration Instruments Selection...................................................................9-1 9.3 Calibration..........................................................................................................9-1 9.4 Disassembly and Reassembly.........................................................................9-3 9.4.1 Replacing the Integral Indicator..........................................................9-3 9.4.2 Replacing the RF Assembly................................................................9-4 9.4.3 Replacing the CPU Assembly.............................................................9-4 9.4.4 Cleaning and Replacing the Capsule Assembly................................9-5

Replacing the Battery Pack................................................................9-5

9.4.6 Replacing the Batteries.......................................................................9-6 9.4.7 Handling Batteries...............................................................................9-6 9.5 Troubleshooting.................................................................................................9-7 9.5.1 Basic Troubleshooting........................................................................9-7 9.5.2 Troubleshooting Flowcharts................................................................9-8 9.5.3 Alarms and Countermeasures..........................................................9-10 10. Parameter Summary............................................................................... 10-1 11. General Specifications........................................................................... 11-1 11.1 Standard Specifications.................................................................................. 11-1 11.2 Model and Suffix Codes.................................................................................. 11-3 11.3 OPTIONAL SPECIFICATIONS......................................................................... 11-3 11.4 Dimensions....................................................................................................... 11-5 Revision Information................................................................................................i

Thank you for purchasing the DPharp EJX Absolute

and Gauge Pressure transmitter. Your EJX Pressure Transmitter was precisely calibrated at the factory before shipment. To ensure both safety and efficiency, please read this manual carefully before you operate the instrument. NOTE This manual covers the EJX510B absolute pressure transmitter and EJX530B gauge pressure transmitter. Unless otherwise stated, the illustrations in this manual are of the EJX530B differential pressure transmitter. Users of the other models should bear in mind that certain features of their instrument will differ from those shown in the illustrations of the EJX530B. Model EJX510B EJX530B  Regarding This Manual • This manual should be provided to the end user. • The contents of this manual are subject to change without prior notice. • All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission. • Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose. • If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office. • The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instruments. • Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint. • Yokogawa assumes no responsibilities for this product except as stated in the warranty. • If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages. • The following safety symbols are used in this manual: WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or physical damage. It may also be used to alert against unsafe practices. IMPORTANT Indicates that operating the hardware or software in this manner may damage it or lead to system failure. NOTE Draws attention to information essential for understanding the operation and features.

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points: (a) Installation • This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition. • With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing. • Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process fluids. • When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process fluids with the skin or eyes. • When removing the instrument from a hazardous process, avoid contact with the fluid and the interior of the meter. • All installation shall comply with local installation requirements and the local electrical code. (b) Wiring • The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition. (c) Maintenance • Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa office. • Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth. (d) Explosion Protected Type Instrument • Users of explosion proof instruments should refer first to Section 2.8 (Installation of an Explosion-Protected Instrument) of this manual. • The use of this instrument is restricted to those who have received appropriate training in the device. • Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location. • Repair or modification to this instrument by customer will cause malfunction of explosion protect function and hazardous situation. If you need to repair or modification, please contact the nearest Yokogawa office. (e) Modification • Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer. WARNING - Do not loosen bolts or nuts used for connecting impulse piping to the transmitter pressure-detector section when they are pressured because loosen bolts or nuts causes spout of process liquid. - Take appropriate care to avoid contact with the body or eyes, or inhalation of vapors when venting or draining if the accumulated liquid (or gas) is toxic or harmful. - Take appropriate care to avoid contact with the body or eyes, or inhalation of vapors when the transmitter is removed from process for maintenance if process liquid is toxic or harmful. CAUTION This instrument is certified as explosion protected type instrument. Structure, installing location, maintenance and repair of this instrument are restricted. Violation of this restriction causes hazardous situation. Users of explosion proof type instruments should refer first to section 2.8 “Installation of an Explosion- Protected Instrument” of this manual.

1.2 Radio Wave

IMPORTANT - This instrument is equipped with a wireless module which is designated as a certification of construction type as a wireless facility for 2.4 GHz band low-power data communication system of the Radio Act. Refer to 2.12 “Regulatory Compliance for Radio and Telecommunication” for detail. - Due to the designated certification of construction type, users may be subject to legal punishment in case of: - Disassembling or modifying the wireless module or antenna in this instrument - Peeling off the certification label attached to the wireless module in this instrument - Preventing interference with other wireless stations The operating frequency bandwidth of this instrument may overlap the same range as industrial devices, scientific devices, medical devices, microwave ovens, licensed premises radio stations and non-licensed specified low-power radio stations for mobile object identification systems used in factory production lines. Before using this instrument, ensure that neither a premises radio station nor specified low power radio station for mobile object identification systems is in use nearby. If this instrument causes radio wave interference to a wireless station for mobile object identification systems, promptly change the frequency being used or turn off the source of radio wave emissions. Then, contact a Yokogawa office regarding countermeasures to prevent interference, such as setting up partitions. 1.3 Warranty • The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge. • If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa office. • If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful. • The party responsible for the cost of fixing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa. • The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to: - Improper and/or inadequate maintenance by the purchaser. - Malfunction or damage due to a failure to handle, use, or store the instrument in accordance with the design specifications. - Use of the product in question in a location not conforming to the standards specified by Yokogawa, or due to improper maintenance of the installation location. - Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa. - Malfunction or damage from improper relocation of the product in question after delivery. - Reason of force majeure such as fires, earthquakes, storms/floods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination. 1.4 Trademarks In this document, trademarks or registered trademarks are not marked with “™” or “®”. Product names and company names in this document are trademarks or registered trademarks of the respective companies.

1.5 ATEX Documentation

This is only applicable to the countries in European Union. GB DK I E NL SF P F D S LT LV PL EST SLO H BG RO M CZ SK GR

<2. Handling Cautions>

2-1 IM 01C27F01-01EN 2. Handling Cautions This chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter. EJX Series transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment. Also check that all transmitter mounting hardware and a bar magnet shown in figure 2.1 is included. If the transmitter is ordered without the mounting bracket and the process connector, the transmitter mounting hardware will not be included. After checking the transmitter, carefully repack it in its box and keep it there until you are ready to install it. U-bolt Nut (L type) Mounting bracket U-bolt (L type) U-bolt (S type) U-bolt Nut (S type) F0201.ai Figure 2.1 Transmitter Mounting Hardware 2.1 Model and Specifications Check The model name and specifications are written on the name plate attached to the case. : Refer to USER'S MANUAL. Made in Japan TOKYO 180-8750 JAPAN MODEL SUFFIX SUPPLY OUTPUT MWP mA DC V DC STYLE CAL RNG NO. F0202.ai Figure 2.2 Name Plate 2.2 Unpacking Keep the transmitter in its original packaging to prevent it from being damaged during shipment. Do not unpack the transmitter until it reaches the installation site. 2.3 Storage The following precautions must be observed when storing the instrument, especially for a long period. (a) Select a storage area which meets the following conditions: • It is not exposed to rain or subject to water seepage/leaks. • Vibration and shock are kept to a minimum. • It has an ambient temperature and relative humidity within the following ranges. • For maximum battery life, storage temperature should not exceed 30°C. Ambient temperature: –40 to 85°C without integral indicator –30 to 80°C with integral indicator Relative humidity: 0% to 100% R.H. Preferred temperature and humidity: approx. 25°C and 65% R.H. (b) When storing the transmitter, repack it carefully in the packaging that it was originally shipped with. (c) If the transmitter has been used, thoroughly clean the chambers inside the cover flanges, so that there is no process fluid remaining inside. Before placing it in storage, also make sure that the pressure-detector is securely connected to the transmitter section. NOTE When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”.

<2. Handling Cautions>

2-2 IM 01C27F01-01EN 2.4 Selecting the Installation Location The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location. (a) Wireless Communication The installation location of this transmitter must meet the following conditions: - Adjust the direction of the antenna to be in the upright position regardless of the orientation of this transmitter. See section 4 for adjusting the antenna. - Install the transmitter at least 1.5m above the ground or floor. F0203.ai 1.5m or over - Ensure that there are no obstacles such as walls or pipes within a 30-cm radius of each antenna. - Confirm that each field wireless equipment compliant with ISA100.11a can see the antenna of other devices which locate within its own communication range. In the star topology network, the visibility to the antenna of gateway is a mandatory clause. (b) Ambient Temperature Avoid locations subject to wide temperature variations or a significant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate thermal insulation and/or ventilation. (c) Ambient Atmosphere Do not install the transmitter in a corrosive atmosphere. If this cannot be avoided, there must be adequate ventilation. (d) Shock and Vibration Although the transmitter is designed to be relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum. (e) Installation of Explosion-protected Transmitters An explosion-protected transmitters is certified for installation in a hazardous area containing specific gas types. See subsection 2.8 “Installation of an Explosion-Protected Transmitters.” 2.5 Pressure Connection WARNING • Never loosen the process connector bolts when an instrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled release of process fluid. • When draining toxic process fluids that have condensed inside the pressure detector, take appropriate steps to prevent the contact of such fluids with the skin or eyes and the inhalation of vapors from these fluids. The following precautions must be observed in order to safely operate the transmitter under pressure. (a) Make sure that all the process connector bolts are tightened firmly. (b) Make sure that there are no leaks in the impulse piping. (c) Never apply a pressure higher than the specified maximum working pressure.

<2. Handling Cautions>

2-3 IM 01C27F01-01EN 2.6 Restrictions on Use of Radio Transceivers IMPORTANT Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the transmitter with the transceiver while observing the measurement loop for noise effects. Thereafter use the transceiver outside the range where the noise effects were first observed. 2.7 Insulation Resistance and Dielectric Strength Test Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following: (a) Do not perform such tests more frequently than is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins. (b) Never apply a voltage exceeding 500 V DC (100 V DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test. (c) The procedure for conducting these tests is as follows: • Insulation Resistance Test 1) Remove the battery pack. See subsection 9.4.5 for details on how to remove it. 2) Short-circuit the battery connection terminals in the terminal box. 3) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted battery connection terminals and the minus (–) leadwire to the grounding terminal. 4) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied as briefly as possible to verify that the insulation resistance is at least 20 MΩ. 5) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 kΩ resistor between the grounding terminal and the short- circuiting battery connection terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging. NOTE When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”. • Dielectric Strength Test 1) Remove the battery pack. See subsection 9.4.5 for details on how to remove it. 2) Short-circuit the battery connection terminals in the terminal box. 3) Turn OFF the dielectric strength tester. Then connect the tester between the shorted battery connection terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal. 4) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specified voltage. 5) When the specified voltage is reached, hold it for one minute. 6) After completing this test, slowly decrease the voltage to avoid any voltage surges. NOTE When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”.

<2. Handling Cautions>

2-4 IM 01C27F01-01EN 2.8 Installation of an Explosion- Protected Instrument If a customer makes a repair or modification to an intrinsically safe instrument and the instrument is not restored to its original condition, its intrinsically safe construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modification to an instrument. CAUTION This instrument has been tested and certified as being intrinsically safe. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate. 2.8.1 FM Approval Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM037-A20”) Note 1. Model EJX Series Differential, gauge and absolute pressure transmitters with optional code /FS17 are applicable for use in hazardous locations. • Applicable Standard: FM3600, FM3610, FM3611, FM3810 • Intrinsically Safe for Class I, Division 1, Groups A, B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1, Class I, Zone 0 in Hazardous Locations, AEx ia IIC • Nonincendive for Class I, Division 2, Groups A, B, C & D. Class II, Division 2, Groups F & G and Class III, Division 1, Class I, Zone 2, Groups IIC, in Hazardous Locations. • Enclosure: NEMA 4X (Indoors and outdoors) • Temperature Class: T4 • Ambient temperature: -50 to 70°C Note 2. Installation • Installation should be in accordance with ANSI/ISA RP12.6 “Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations” and the National Electric Code (ANSI/NFPA 70). • Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments. • Note a warning label worded “SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” and “INSTALL IN ACCORDANCE WITH DOC. No. IFM037-A20”. Note 3. Maintenance and Repair • The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Intrinsically safe and Nonincendive Approval. Transmitter Hazardous Location [Intrinsically Safe] Class I, II, III, Division 1, Groups A,B,C,D,E,F,G Class I, Zone 0 in Hazardous (Classified) Locations AEx ia IIC [Nonincendive] Class I, II, Division 2, Groups A, B, C, D, F, G Class III, Division 1. Class I, Zone 2, Group IIC, in Hazardous (Classified) Locations F0204.ai Note 4. Battery Pack USE ONLY YOKOGAWA BATTERY PACK F9915MA or F9915NS. Note 5. Special Conditions for safe use POTENTIAL ELECTROSTATIC CHARGING HAZARD-SECURE DISTANCE OF 100MM FROM ANTENNA. DO NOT OPEN WHEN CL II, III, DIV 1,2 ATMOSPHERE IS PRESENT.

<2. Handling Cautions>

2-5 IM 01C27F01-01EN 2.8.2 CSA Certification Caution for CSA Intrinsically safe type. (Following contents refer to “DOC No. ICS030”) Note 1. Model EJX Series differential, gauge, and absolute pressure transmitters with optional code /CS17 are applicable for use in hazardous locations Certificate: 2325443 [For CSA C22.2] • Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1 • Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1 • Nonincendive for Class I, Division2, Groups A, B, C&D, Class II, Division2, Groups F&G, Class III, Division1 • Enclosure: Type 4X, • Temp. Code: T4 • Amb. Temp.:-50 to 70°C • Process Temperature: 120°C max. [For CSA E60079] • Applicable Standard: CAN/CSA E60079-0, CAN/CSA E60079-11, IEC 60529:2001-02 • Ex ia IIC T4 • Ambient Temperature: -50 to 70°C • Max. Process Temp.: 120°C • Enclosure: IP66 and 67 Note 2. Installation • Installation should be in accordance with Canadian Electrical Code Part I and Local Electrical Code. • Do not alter drawing without authorization from CSA. • The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation of America is prohibited and will void Canadian Standards Intrinsically safe and nonincendive Certification. Transmitter Hazardous Location [Intrinsically Safe] Group IIC, Zone 0 Class I, II, III, Division 1, Groups A,B,C,D,E,F,G [Nonincendive] Class I, II, Division 2, Groups A,B,C,D,F,G Class III, Division 1 F0205.ai Note 3. Battery Pack • Use only YOKOGAWA battery pack F9915MA or F9915NS. Note 4. Special Conditions for safe use • Potential electrostatic charging hazard - secure distance of 100mm from antenna. 2.9 EMC Conformity Standards EN61326-1 Class A, Table 2 (For use in industrial locations), EN61326-2-3 CAUTION This instrument is a Class A product, and it is designed for use in the industrial environment. Please use this instrument in the industrial environment only. 2.10 Pressure Equipment Directive (PED) (1) General • EJX Series pressure transmitters are categorized as pressure accessories under the vessel section of directive 97/23/EC, which corresponds to Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP). • EJX110B-MS, EJX110B-HS, EJX110B-VS, EJX510B-D, and EJX530B-D can be used above 200 bar and therefore considered as a part of a pressure retaining vessel where category III, Module H applies. These models with option code /PE3 conform to that category.

<2. Handling Cautions>

2-6 IM 01C27F01-01EN (2) Technical Data • Models without /PE3 Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP). • Models with /PE3 Module: H Type of Equipment: Pressure Accessory-Vessel Type of fluid: Liquid and Gas Group of fluid: 1 and 2 Model Capsule code PS (bar)*1 V(L) PS·V (bar·L) Category*2 EJX110B L 160 0.01 1.6 Article 3, Paragraph 3 (SEP) M, H, V 250 0.01 2.5 EJX110B with code /PE3 M, H, V 250 0.01 2.5 III EJX310B L, M, A, B 160 0.01 1.6 Article 3, Paragraph 3 (SEP) EJX430B H, A, B 160 0.01 1.6 Article 3, Paragraph 3 (SEP) EJX510B A, B, C 100 0.1 10 Article 3, Paragraph 3 (SEP) D 700 0.1 70 EJX510B with code /PE3 D 700 0.1 70 III EJX530B A, B, C 100 0.1 10 Article 3, Paragraph 3 (SEP) D 700 0.1 70 EJX530B with code /PE3 D 700 0.1 70 III *1: PS is maximum allowable pressure for vessel itself. *2: Referred to Table 1 covered by ANNEX II of EC Directive on Pressure Equipment Directive 97/23/EC (3) Operation CAUTION • The temperature and pressure of fluid should be maintained at levels that are consistent with normal operating conditions. • The ambient temperature should be maintained at a level that is consistent with normal operating conditions. • Please take care to prevent water hammer and the like from inducing excessive pressures in pipes and valves. If phenomena are likely, install a safety valve or take some other appropriate measure to prevent pressure from exceeding PS. • Take appropriate measures at the device or system level to protect transmitters if they are to be operated near an external heat source. 2.11 Low Voltage Directive Applicable standard: EN61010-1 (1) Pollution Degree 2 "Pollution degree" describes the degree to which a solid, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. " 2 " applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by condensation must be expected. (2) Installation Category I "Overvoltage category (Installation category)" describes a number which defines a transient overvoltage condition. It implies the regulation for impulse withstand voltage. " I " applies to electrical equipment which is supplied from the circuit when appropriate transient overvoltage control means (interfaces) are provided.

<2. Handling Cautions>

2-7 IM 01C27F01-01EN 2.12 Regulatory Compliance for Radio and Telecommunication Please confirm that a installation region fulfills a standards, require additional regulatory information and approvals, contact to Yokogawa Electric Corporation. 2.12.1 Radio and Telecommunications Terminal Equipment Directive (R&TTE) We, Yokogawa Electric Corporation hereby declare that this equipment, model EJX-L series is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. The CE declaration of conformity for R&TTE for this product can be found at http://www.yokogawa.com/ fld/ NOTE France restricts outdoor use to 10mW (10dBm) EIRP in the frequency range of 2,454 - 2,483.5MHz. Installation in France must configure the network with configuration tool not to use channel 10 to 14. To configure the network, refer to IM 01W01F01-01EN. 2.12.2 FCC compliance This device complies with Part 15 of FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of this device. Co-located: This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter. FCC WARNING: Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of he FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. 2.12.3 Industry Canada (IC) compliance This Class A digital apparatus complies with Canadian ICES-003. French: Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.

<3. Component Names>

3-1 IM 01C27F01-01EN 3. Component Names WR E D F0301.ai H L E D H L E D YES (Note 2) (Write disabled) NO (Write enabled) Zero-adjustment screw Ground terminal RF assembly CPU assembly Not in use Write protection switch Transmitter section Amplifier Cover Mounting screw Integral indicator Slide switch Hardware write protection switch (WR) Write Protection Write Protection Switch Position (Note 1) Pressure-detector section Note 1: Set the switch as shown in the figure above to set the write protection. The hardware write protection switch is set to E side. Set to H side for the switch of not-in-use. Note 2: When the switch is D side (write protection setting), provisioning is acceptable. For details of provisioning, refer to section 7.4 “ Connecting to the Field Wireless Network “. Figure 3.1 Component Names Table 3.1 Display Symbol Display Symbol Meaning of Display Symbol ▲ The output signal being zero-adjusted is increasing. ▼ The output signal being zero-adjusted is decreasing. Write protect function is enabled.

Before installing the transmitter, read the cautionary

notes in section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to section11.1 “Standard Specifications.” NOTE To connect this transmitter to the Field Wireless Network, information for connecting to the field wireless devices needs to be set beforehand. Refer to 7.4 “Connecting to the Field Wireless Network.” IMPORTANT • When welding piping during construction, take care not to allow welding currents to flow through the transmitter. • Do not step on this instrument after installation. • For the EJX530B whose capsule code is A, B or C, the pipe of the atmospheric opening is located on the pressure detecting section. The opening must not face upward. See subsection 5.1.1. • D capsule of EJX530B is of sealed gauge reference and the change in atmospheric pressure may affect the measurement. 4.2 Mounting ■ The impulse piping connection port of the transmitter is covered with a plastic cap to protect against dust. This cap must be removed before connecting the piping. (Be careful not to damage the threads when removing these caps. Do not insert a screw driver or other tool between the cap and the port threads to remove the cap.) ■ The transmitter can be mounted on a nominal 50 mm (2-inch) pipe using the mounting bracket supplied, as shown in Figure 4.1. ■ The user should prepare the mating gasket for the transmitters with Process connection code 8 and 9. See Figure 4.2. Horizontal pipe mounting F0401.ai Vertical pipe mounting 50 mm (2-inch) pipe U-bolt (L) U-bolt (S) Mounting bracket U-bolt nut (S) U-bolt nut (L) U-bolt nut (L) Mounting bracket 50 mm (2-inch) pipe U-bolt (L) U-bolt (S) U-bolt nut (S) Figure 4.1 Transmitter Mounting Gasket F0402.ai Figure 4.2 Gasketing

Tighten the hexagonal nut part of the capsule

assembly. See Figure 4.3. F0403.ai Capsule assembly Figure 4.3 Tightening Transmitter 4.3 Rotating Transmitter Section WARNING Intrinsic safe type transmitters must be, as a rule, do not rotate transmitter section if it is powered. In case you need to rotate when the transmitter is powered, using gas detector and confirm no existence of explosive gas before rotating. The transmitter section can be rotated approximately 360° (180° to either direction or 360° to one direction from the original position at shipment, depending on the configuration of the instrument.) It can be fixed at any angle within above range. 1) Remove the five setscrews that fasten the transmitter section and capsule assembly, using the Allen wrench. 2) Rotate the transmitter section slowly and stop it at designated position. For the EJX530B whose capsule code is A, B or C, the pipe of the atmospheric opening may interfere with the stopper and disturb further rotation. In that case, screw off the pipe first, rotate the housing, and then screw in the pipe by hand again. 3) Tighten the five setscrews to a torque of 1.5 N·m. IMPORTANT Do not rotate the transmitter section more than the above limit. Stopper Setscrew Transmitter section Pressure-detector section F0404.ai Figure 4.4 Rotating Transmitter Section 4.4 Changing the Direction of Integral Indicator WARNING Intrinsic safe type transmitters must be, as a rule, remove a battery pack in non-hazardous area before open/close the Amplifier Cover or disassembling and reassembling the Integral Indicator. An integral indicator can be installed in the following three directions. Follow the instructions in section 9.4.1 for removing and attaching the integral indicator.

4.5 Changing the direction of

the antenna Adjust the direction of the antenna to be in the upright position. Figure 4.5 show factory setup antenna position. If the transmitter is installed to horizontal impulse piping, follow the procedure below and change the antenna position. 1) Loosen the two mounting screws at the bottom of the antenna by using a 2.5mm Allen wrench (see Figure 4.5). 2) Press forward and down 90 degrees by rotating the axis at the bottom of the antenna. 3) Tighten the two screws to a torque of 1.5 N-m by using a torque wrench. When doing this, be careful not leave a gap between the antenna and housing. F0405.ai Figure 4.5 Mounting Screw Position F0406.ai Figure 4.6 Adjusting Antenna Position

<5. Installing Impulse Piping>

5-1 IM 01C27F01-01EN 5. Installing Impulse Piping 5.1 Impulse Piping Installation Precautions The impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects in a liquidfilled impulse line, or the drain for a gas-filled impulse line becomes plugged, it will not convey the pressure accurately. Since this will cause errors in the measurement output, select the proper piping method for the process fluid (gas, liquid, or steam). Pay careful attention to the following points when routing the impulse piping and connecting the impulse piping to a transmitter. 5.1.1 Connecting Impulse Piping to a Transmitter IMPORTANT The transmitter can be installed in horizontal impulse piping configuration, tilting the transmitter's position up to 90°. When tilting, observe that the pipe (for Model EJX530A with measurement span code A, B, and C) is positioned horizontal downwards, or any place between them, as shown in Figure 5.1 The zero-adjustment screw must be positioned downwards for all the models. F0501.ai Zero-adjustment screw  Pipe (backside of the instrument) The pipe (open to atmosphere) is positioned horizontal. If the zero-adjustment screw is positioned other than downwards after installation, rotate the housing until it is positioned downwards. Figure 5.1 Horizontal Impulse Piping Connection 5.1.2 Routing the Impulse Piping (1) Process Pressure Tap Angles If condensate, gas, sediment or other extraneous material in the process piping gets into the impulse piping, pressure measurement errors may result. To prevent such problems, the process pressure taps must be angled as shown in figure 5.2 according to the kind of fluid being measured. NOTE • If the process fluid is a gas, the taps must be vertical or within 45° either side of vertical. • If the process fluid is a liquid, the taps must be horizontal or below horizontal, but not more than 45° below horizontal. • If the process fluid is steam or other condensing vapor, the taps must be horizontal or above horizontal, but not more than 45° above horizontal. [Gas] Pressure taps Process piping [Steam] [Liquid] 45° 45° 45° 45° 45° 45° F0502.ai Figure 5.2 Process Pressure Tap Angle (For Horizontal Piping) (2) Position of Process Pressure Taps and Transmitter If condensate (or gas) accumulates in the impulse piping, it should be removed periodically by opening the drain (or vent) plugs. However, this will generate a transient disturbance in the pressure measurement, and therefore it is necessary to position the taps and route the impulse piping so that any extraneous liquid or gas generated in the leadlines returns naturally to the process piping. • If the process fluid is a gas, then as a rule the transmitter must be located higher than the process pressure taps. • If the process fluid is a liquid or steam, then as a rule the transmitter must be located lower than the process pressure taps.

<5. Installing Impulse Piping>

5-2 IM 01C27F01-01EN (3) Impulse Piping Slope The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes. (4) Preventing Freezing If there is any risk that the process fluid in the impulse piping or transmitter could freeze, use a steam jacket or heater to maintain the temperature of the fluid. NOTE After completing the connections, close the valves on the process pressure taps (main valves), the valves at the transmitter (stop valves), and the impulse piping drain valves, so that condensate, sediment, dust and other extraneous material cannot enter the impulse piping. 5.2 Impulse Piping Connection Examples Figure 5.3 shows examples of typical impulse piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, and the characteristics of the process fluid (corrosiveness, toxicity, flammability, etc.), in order to make appropriate changes and additions to the connection configurations. Note the following points when referring to these piping examples. • If the impulse line is long, bracing or supports should be provided to prevent vibration. • The impulse piping material used must be compatible with the process pressure, temperature, and other conditions. • A variety of process pressure tap valves (main valves) are available according to the type of connection (flanged, screwed, welded), construction (globe, gate, or ball valve), temperature and pressure. Select the type of valve most appropriate for the application. F0503.ai Tee Stop valve Stop valve Drain valve Drain plug Union or flange Union or flange Tap valve Figure 5.3 Impulse Piping Connection Examples

Always ground the transmitter case in accordance

with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance. F0601.ai Ground terminal Figure 6.1 Ground Terminal CAUTION Grounding is recommended for safe operation.

7.1 Preparation for Starting

Operation This section describes the operation procedure for the EJX530B as shown in figure 7.1. NOTE It is required to set security and network information to enable the transmitter to be connected to the Field Wireless Network. For more details, refer to section 7.4 “Connecting to the Field Wireless Network”. NOTE Check that the process pressure tap valves, drain valves, and stop valves are closed. (a) Follow the procedures below to introduce process pressure into the impulse piping and transmitter. 1) Open the tap valve (main valve) to fill the impulse piping with process fluid. 2) Gradually open the stop valve to introduce process fluid into the transmitter pressure- detector section. 3) Confirm that there is no pressure leak in the impulse piping, transmitter, or other components. (b) Turn on the power and connect the Field Wireless Devices to the field wireless network. (c) Using the configuration tool, confirm that the transmitter is operating properly. Check parameter values or change the setpoints as necessary. Integral Indicator’s indication can be used to confirm that the transmitter is operating properly. For details on how to confirm refer to subsection 8.4 “Self-Diagnostics”. ISA100 devices display self-diagnostic information in an easy-to-understand manner using four categories (Check function, Maintenance required, Failure, and Off specification) according to NAMUR NE107* * NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices” F0701.ai Union or flange Vent plug (Fill plug) Tap valve Stop valve Tee Drain valve Drain plug Union or flange Figure 7.1 Liquid Pressure Measurement (Gauge Pressure Transmitters) ■ Confirm that transmitter is operating properly by Integral Indicator If the transmitter is faulty, an error code is displayed. F0702.ai Self-diagnostic error on the integral indicator (Faulty transmitter) Figure 7.2 Integral Indicator with Error Code NOTE If any of the above errors are indicated on the display of the integral indicator or the configuration tool, refer to subsection 9.5.3 for the corrective action.

 Verify and Change Transmitter

Parameter Setting and Values The parameters related to the following items are minimum required to be set for operation, and set at factory as specified in order. Confirm or change the parameters if needed. • Measurement range (measurement lower/ upper limit, unit) 7.2 Zero Point Adjustment After completing preparations for operating the transmitter, adjust the zero point. There are two zero point adjusting ways. IMPORTANT Do not turn off the power to the transmitter immediately after performing a zero point adjustment. Powering off within 30 seconds of performing this procedure will return the zero point to its previous setting. (1) When you can obtain the Low Range Value from the actual measured value of 0% (0kPa, atmospheric pressure);  Using the transmitter’s zero-adjustment screw Before adjusting zero point, make sure followings. • That the External zero trim parameter (EXTERNAL_ZERO_TRIM) is “Trim on”. For details, refer to section 8 “Setting Parameters”. • Use a slotted screwdriver to turn the zero- adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. The degree of zero adjustments varies with the screw turning speed turn the screw slowly to make a fine adjustment, quickly to make a rough adjustment. IMPORTANT When zeroing with the zero-adjustment screw, turn the screw firmly until ▲ or ▼ mark is displayed on the integral indicator since there exists mechanical dead-band of the screw.  Using the Configuration Tool Refer to subsection 8.3.10 “Zero Point Adjustment and Span Adjustment”. (2) When you cannot obtain the Low Range Value from the actual measured value of 0%; Adjust the transmitter output value matches to the actual measured value obtained by precise pressure measurement equipment. [Example] The measuring range of 50 to 250 kPa : the actual measured value of 130kPa. 130–50 250–50 Actual measured value= x100=40.0%  Using the transmitter’s zero-adjustment screw Turn the zero adjustment screw to adjust the transmitter.  Using the Configuration Tool Refer to subsection 8.3.10 “Zero Point Adjustment and Span Adjustment”. 7.3 Starting Operation After the zero point adjustment is completed, the transmitter is already the operating status. Follow the procedure below. 1) Confirm the operating status. If the output signal exhibits wide fluctuations (hunting) due to periodic variation in the process pressure, use the communicator to dampen the transmitter output value. Confirm the hunting using a receiving instrument or the integral indicator, set the suitable damping time constant. 2) After confirming the operating status, perform the following. IMPORTANT • Close the terminal box cover and the amplifier cover. Screw each cover in tightly until it will not turn further. • Tighten the zero-adjustment cover mounting screw to secure the cover.

7.4 Connecting to the Field

Wireless Network ■ Preparation work prior to connecting to a Field Wireless Network This transmitter does not need to be connected with a physical wire. Instead of physical wiring, it is necessary to set the field wireless devices to communicate with before installing the transmitter. This transmitter supports provisioning via infrared communication using a provisioning device and can be securely connected to a network. If the provisioning information is not set, the transmitter cannot be connected to the field wireless network. Provisioning: Provisioning is work to set the security and network information to enable the transmitter to be connected to the field wireless network. This transmitter supports a provisioning method: the OOB (out-of-band) method using infrared communication. For details on provisioning using a provisioning device, and procedure for connecting the transmitter to the Field Wireless Network, refer to the User’s Manual, YFGW710 Field Wireless Integrated Gateway (IM 01W01F01-01EN). F0703.ai within 30cm Figure 7.3 Provisioning Example ■ Provisioning work This subsection describes provisioning work using FieldMate as the provisioning device. Provisioning work performs provisioning for each field wireless device using FieldMate and an infrared adapter. If Yokogawa-recommended infrared device is used for provisioning, distance between the transmitter glass window and the infrared device should be within 30cm. For details of Yokogawa-recommended infrared device, refer to subsection 9.2 “Calibration Instruments Selection”. Perform the following provisioning tasks. • Setting provisioning information • Creating a provisioning information file 1) Setting provisioning information Set the device tag and network ID using a FieldMate provisioning function. The device tag, network ID, and join key are set in the Field Wireless Device. It is not necessary to input a join key because FieldMate automatically generates it. Setting device tag The device tag is used for the user to recognize the Field Wireless Device. Setting network ID This is the network ID for the field wireless network to which the field wireless device is connected. Set a value from 2 to 65535. The field wireless device is connected to the field wireless network corresponding to the network ID set by provisioning work. 2) Creating a provisioning information file The following provisioned information is stored in the provisioning information file. • Network ID • Device tag • EUI64 • Join key • Provisioner (name of the user who performed provisioning work by FieldMate) • Date (Time and date when provisioning was performed by FieldMate) This provisioning information file is required to load from the Field Wireless Configurator to the Field Wireless Integrated Gateway. Store the file carefully.

Connecting to a field wireless network

The action after installing the battery pack varies depending on the silence setting. In case of factory setting, mounting the battery pack automatically starts a search for the field wireless network. When the Field Wireless Integrated Gateway is found, the instrument enters the join status. When the Field Wireless Integrated Gateway is not found and a specified time has elapsed, a cycle of a one-hour pause and six-minutes search is repeated until the instrument can join the field wireless network. For details on the procedure to switch to silence mode, refer to subsection 8.3.13 “Switching to Silence Mode.” Boot Ready and pause Deep Sleep Ready Confirm connecting status Join (Disconnect) (Connect) (Search failure) (Search start) (Search start) Silence mode OFF Silence mode ON Configuration Tool Configuration Tool (Search failure) F0704.ai Mounting battery pack Figure 7.4 Wireless Connection Process NOTE If the transmitter searches the Field Wireless Network for long time at low ambient temperature condition, sometimes error “AL.70 LOW.BAT” is displayed on the Integral Indicator. Even though using new batteries, it can occur. It occurs because of battery characteristics. After joining to the Field Wireless Network, this error will be cleared within one hour if battery has no failure. 7.5 Shutting Down the Transmitter Shut down the transmitter as follows. 1) Remove the battery pack or set the transmitter to deep sleep mode by the Configuration Tool. 2) Close the low pressure stop valve. 3) Open the equalizing valve. 4) Close the high pressure stop valve. 5) Close the high pressure and low pressure tap valves. NOTE • Whenever shutting down the transmitter for a long period, remove the process line that is in the transmitter. • The equalizing valve must be left OPEN. • Refer to subsection 9.4.5 “Replacing the Battery Pack” for the battery pack removing. • When storing the instrument with a battery pack inserted, it is recommended to put the instrument into deep sleep mode to conserve battery power. For details on how to switch to deep sleep mode, refer to subsection 8.3.12 “Switching to the Deep Sleep Mode.”

<8. Setting Parameters>

8-1 IM 01C27F01-01EN 8. Setting Parameters This transmitter can remotely handle range changes, Tag No. setup, monitoring of self- diagnostic results, and Zero-Point Adjustment, etc. according to communication with a configuration tool. 8.1 Environment for parameter setting After installing the battery pack, perform provisioning and have the transmitter join the field wireless network. This transmitter supports the OOB(out-of-band) method using the infrared communication as a provisioning method. Refer to Subsection 7.4 “Connecting to the Field Wireless Network” for details of the provisioning. F0801.ai Infrared port Figure 8.1 Infrared port of the transmitter 8.2 Preparing Software for the Configuration Tool Before using the configuration tool, confirm that CF/ DD and DeviceDTM for your transmitter (wireless EJX) are installed in the configuration tool. CF/DD and DeviceDTM are provided by CD-ROM attached to YFGW710 Field Wireless Integrated Gateway. Refer to YFGW710 Field Wireless Integrated Gateway (GS 01W01F01-01EN) for details. CF (Capabilities File)/DD (Device Description) A CF file contains information, such as the vendor of the field device, its model and revision, available types of process data (flow rate, temperature, pressure, etc.), and number of data items. A DD file contains the information on parameters, such as data structures and attributes. DeviceDTM DeviceDTM (Device Type Manager) is driver software for field devices provided based on the FDT (Field Device Tool) technology. The configuration tool allows confirming the device information. For details on how to confirm the device information using the configuration tool, refer to the General Specifications, YFGW710 Field Wireless Integrated Gateway (GS 01W01F01- 01EN). Refer to subsection 9.2 “calibration Instruments Section” for a configuration tool of our recommendation.

<8. Setting Parameters>

8-2 IM 01C27F01-01EN 8.3 Setting Parameters 8.3.1 Parameter Usage and Selection Before setting a parameter, please see the following table for a summary of how and when each parameter is used. IMPORTANT After setting and sending data with the configuration tool, wait 30 seconds before turning off the transmitter. If it is turned off too soon, the settings will not be stored in the transmitter. Table 8.1 Parameter Usage and Selection Item Description Tag No Sets the tag No. as Device Tag (Software Tag). Sixteen characters (alphanumeric characters, including - and •) can be set. Output The process variable and the diagnostic result can be output. Either or all of differential pressure (AI1:PV), static pressure (AI2:PV), temperature(AI3:PV) of capsule or amplifier and self-diagnostic information (UAPMO:DIAG_STATUS) can be set to the output Range Adjust the range corresponding for 0% to 100%. The unit of the range, input value at 0% (LRV) and input value at 100% (URV) is set. Note: LRV and URV can be set within the range of -32000 to 32000. Damping time constant Adjust the output response speed for 0% to 100%. It can be set within the range of 0.00 to 100.00 seconds. The setting becomes invalid in the intermittent mode. Output signal low cut mode Used mainly to stabilize output near 0 if output signal is the square root mode. Two modes are available: forcing output to 0% for input below a specific value, or changing to proportional output for input below a specific value. Integral indicator range of scale and unit Sets one of pressure value, or temperature value for the integral indicator scale. Note: LRV and URV can be set within the range of -32000 to 32000. Unit for displayed temperature Sets a temperature unit to be displayed. Range with actual input applied Range corresponding for 0% to 100% signal is set with actual input applied. The output setting can be done just 100% to user’s reference pressure output. However, when shipping it, the calibration is done in high accuracy as for DPharp. Please do the span setting by a usual range setting. Zero Point Adjustment and Span Adjustment Handle Zero Point Adjustment and Span Adjustment. There are two methods of Zero Point Adjustment, using external zero- adjustment screw and using configuration tool. Reset adjustment Reset all setting of zero and span adjustment, etc. Software write protect Prohibit writing the setting data. Operational mode Set the operational mode of the sensor and integral indicator, etc.

<8. Setting Parameters>

8-3 IM 01C27F01-01EN 8.3.2 Function Block and Menu Tree (1) Function Block The function of this transmitter is shown below. A specific function might not be able to be used according to the configuration tool used. When a configuration tool of our recommendation is used, the software attached to the Field Wireless Integrated Gateway is necessary for setting the dotted line part. Refer to Subsection 9.2 “Calibration Instruments Selection” for a configuration tool of our recommendation. The setting of differential pressure(Al2 block) is invalid in this instrument. The output value of Al2 object and the output status are “0.0”(zero), “Uncertain” respectively. •Configuration •Diagnostics/Alerts •Power Status •Identification (UAPMO) •APP Download (UDO) •Configuration •Others (CO) •Block Info •Configuration (TRANSDUCER) •UAPMO •UDO •CO •TRANSDUCER •AI1(DP) •AI2(SP) •AI3(ET) Online Menu •UAP_OPTION •HW_WRITE_PROTECT •ST_REV •RESET_ENERGY_LEFT •RADIO_SILENCE (Configuration) •DIAG_STATUS •DIAG_STATUS_DETAIL[0] •DIAG_SWITCH •DIAG_CONFIG (Diagnostics/Alerts) •VERSION_REVISION •CTS_VERSION •ITS_VERSION •IDENT_NUMBER (Identification) •DESCRIPTION •STATE •MAX_BLOCK_SIZE •LAST_BLOCK_DOWNLOADED •ERROR_CODE (APP Download) •COMM_ENDPOINT •COMM_CONTRACT •PUB_ITEM_MAX •PUB_ITEM_NUM •PUB_ITEM (Configuration) •REVISION (Others) •Network address of remote endpoint •Transport layer port at remote endpoint •Object ID at remote endpoint •Stale data limit •Data publication period •Ideal publication phase •PublishAutoRetransmit •Configuration status (COMM_ENDPOINT) •ContractID •Contract_Status •Actual_Phase (COMM_CONTRACT) •ObjectID •AttributeID •AttributeIndex •Size (PUB_ITEM) •TAG_DESC (Block Info) •AUTO_RECOVERY •MODEL •SENSOR_SN •MEASUREMENT_RATE •MEASURE_MODE •WIRELESS_STATUS •DISPLAY_SEL •LCD_MODE •SPECIAL_CMD •SPECIAL_ORDER_ID •UNIT_SEL1 •DISPLAY_UNIT1 (Configuration) F0802-1.ai •ENERGY_LEFT •POWER_SUPPLY_STATUS (Power Status)

<8. Setting Parameters>

8-4 IM 01C27F01-01EN •Block Info •Block Mode •Dynamic Variables •Configuration •Calibration •Others (AI1 DP) •TAG_DESC (Block Info) •Target •Actual •Permitted •Normal (Block Mode ) •PV •SIMULATION (Dynamic Variables) •SIMULATE_SWITCH •TRANSDUCER_VALUE •SIMULATE_VALUE (SIMULATION) •Status •Value ** (PV) •Status •Value (TRANSDUCER_VALUE) •Status •Value (SIMULATE_VALUE) •Block Mode •CONC_OID •SCALE * •PV_FTIME (Configuration) (Block Mode) •Target •Actual •Permitted •Normal (SCALE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * •UPPER_LIM •LOWER_LIM •PV_RANGE * •LIN_TYPE * •FLOW_CONSTANT * •LOW_CUTOFF •LOWCUT_MODE * •H/L_SWAP * •T_ZERO_CMP * •TEMP_ZERO * •TEMP_SELECT * (Others) (PV_RANGE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * F0802-2.ai •Block Mode •CAL_CMD * •CAL_STATUS •CAL_POINT_HI * •CAL_POINT_LO * •CAL_MIN_SPAN •EXTERNAL_ZERO_TRIM * (Calibration) (Block Mode) •Target •Actual •Permitted •Normal Online Menu (continued) *: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service). **: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.

<8. Setting Parameters>

8-5 IM 01C27F01-01EN •Block Info •Block Mode •Dynamic Variables •Configuration •Others (AI2 SP) •TAG_DESC (Block Info) •Target •Actual •Permitted •Normal (Block Mode ) •PV •SIMULATION (Dynamic Variables) •SIMULATE_SWITCH •TRANSDUCER_VALUE •SIMULATE_VALUE (SIMULATION) •Status •Value ** (PV) •Status •Value (TRANSDUCER_VALUE) •Status •Value (SIMULATE_VALUE) •Block Mode •CONC_OID •SCALE * •PV_FTIME (Configuration) (Block Mode) •Target •Actual •Permitted •Normal (SCALE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * •UPPER_LIM •LOWER_LIM •PV_RANGE * •LIN_TYPE * •FLOW_CONSTANT * •LOW_CUTOFF •CAL_CMD * •CAL_STATUS •CAL_POINT_HI * •CAL_POINT_LO * •CAL_MIN_SPAN •SP_VALUE_TYPE * •SP_SELECT * (Others) (PV_RANGE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * F0802-3.ai Online Menu (continued) *: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service). **: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.

<8. Setting Parameters>

8-6 IM 01C27F01-01EN •Block Info •Block Mode •Dynamic Variables •Configuration •Others (AI3 ET) •TAG_DESC (Block Info) •Target •Actual •Permitted •Normal (Block Mode ) •PV •SIMULATION (Dynamic Variables) •SIMULATE_SWITCH •TRANSDUCER_VALUE •SIMULATE_VALUE (SIMULATION) •Status •Value ** (PV) •Status •Value (TRANSDUCER_VALUE) •Status •Value (SIMULATE_VALUE) •Block Mode •CONC_OID •SCALE * •PV_FTIME (Configuration) (Block Mode) •Target •Actual •Permitted •Normal (SCALE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * •SENSOR_RANGE •TERTIARY_VALUE_SEL * (Others) (SENSOR_RANGE) •EU at 100% •EU at 0% •Units Index ** •Decimal ** F0802-4.ai Online Menu (continued) *: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service). **: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.

<8. Setting Parameters>

8-7 IM 01C27F01-01EN (2) Menu Tree The menu tree of a configuration tool of our recommendation is shown below. Refer to Subsection 9.2 “Calibration Instruments Selection” for a configuration tool of our recommendation. •UAPMO •TRANSDUCER •AI1 DP •AI2 SP •AI3 Temp •Device Configuration •Diagnostic •Process Variable (Device Configuration) Online Menu F0803-1.ai •Configure/Setup (UAPMO) •Configure/Setup (TRANSDUCER) •UAP_OPTION •HW_WRITE_PROTECT •ST_REV •RESET_ENERGY_LEFT •RADIO_SILENCE (Configuration) •VERSION_REVISION •CTS_VERSION •ITS_VERSION •IDENT_NUMBER (Identification) •AUTO_RECOVERY •MODEL •SENSOR_SN •MEASUREMENT_RATE •MEASURE_MODE •WIRELESS_STATUS •DISPLAY_SEL •LCD_MODE •SPECIAL_CMD •SPECIAL_ORDER_ID •UNIT_SEL1 •DISPLAY_UNIT1 (Configuration/Calibration) •TAG_DESC (Block Info) •Configure/Setup (AI1 DP) •Target •Actual •Permitted •Normal (Block Mode) •Block Mode •CONC_OID •SCALE * •PV_FTIME (Configuration) •Target •Actual •Permitted •Normal (Block Mode) •Block Mode •CAL_CMD * •CAL_STATUS •CAL_POINT_HI * •CAL_POINT_LO * •CAL_MIN_SPAN •EXTERNAL_ZERO_TRIM * (Calibration) •Target •Actual •Permitted •Normal (Block Mode) •UPPER_LIM •LOWER_LIM •PV_RANGE * •LIN_TYPE * •FLOW_CONSTANT * •LOW_CUTOFF •LOWCUT_MODE * •H/L_SWAP * •T_ZERO_CMP * •TEMP_ZERO * •TEMP_SELECT * (Others) •EU at 100% * •EU at 0% * •Units Index * •Decimal * (PV_RANGE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * (SCALE) •TAG_DESC (Block Info) *: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).

<8. Setting Parameters>

8-8 IM 01C27F01-01EN •Configure/Setup (AI2 SP) F0803-2.ai •TAG_DESC (Block Info) •UPPER_LIM •LOWER_LIM •PV_RANGE * •LIN_TYPE * •FLOW_CONSTANT * •LOW_CUTOFF •CAL_CMD* •CAL_STATUS •CAL_POINT_HI * •CAL_POINT_LO * •CAL_MIN_SPAN •SP_VALUE_TYPE * •SP_SELECT * (Others) •Target •Actual •Permitted •Normal (Block Mode) •EU at 100% •EU at 0% •Units Index * •Decimal * (PV_RANGE) (Block Mode) •Target •Actual •Permitted •Normal (AI3 Temp) (Block Info) •TAG_DESC •SENSOR_RANGE •TERTIARY_VALUE_SEL * (Others) •Block Mode •CONC_OID •SCALE * •PV_FTIME (Configuration) •Target •Actual •Permitted •Normal (Block Mode) •EU at 100% * •EU at 0% * •Units Index * •Decimal * (SCALE) •EU at 100% * •EU at 0% * •Units Index * •Decimal * (PV_REMGE) •Configure/Setup •Block Mode •CONC_OID •SCALE * •PV_FTIME (Configuration) •Target •Actual •Permitted •Normal (Block Mode) •EU at 100% * •EU at 0% * •Units Index * •Decimal * (SCALE) Device Configuration (continued) Online Menu (continued) *: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).

<8. Setting Parameters>

8-9 IM 01C27F01-01EN •UAPMO (Diagnostic) F0803-3.ai •Device Diagnostics (UAPMO) •DIAG_STATUS •DIAG_STATUS_DETAIL[0] •DIAG_SWITCH •DIAG_CONFIG (Diagnostics/Alerts) •ENERGY_LEFT •POWER_SUPPLY_STATUS (Power Status) •AI1 DP •AI2 SP •AI3 Temp (Process Variable) •Process Variable (AI1 DP) •PV •SIMULATION (Dynamic Variables) •Status •Value** (PV) •SIMULATE_SWITCH •TRANSDUCER_VALUE •SIMULATE_VALUE (SIMULATION) •Status •Value (TRANSDUCER_ VALUE) •Status •Value (SIMULATE_ VALUE) •Process Variable (AI2 SP) •PV •SIMULATION (Dynamic Variables) •Status •Value** (PV) •SIMULATE_SWITCH •TRANSDUCER_VALUE •SIMULATE_VALUE (SIMULATION) •Status •Value (TRANSDUCER_ VALUE) •Status •Value (SIMULATE_ VALUE) •Process Variable (AI3 Temp) •PV •SIMULATION (Dynamic Variables) •Status •Value** (PV) •SIMULATE_SWITCH •TRANSDUCER_VALUE •SIMULATE_VALUE (SIMULATION) •Status •Value (TRANSDUCER_ VALUE) •Status •Value (SIMULATE_ VALUE) Online Menu (continued) **: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.

<8. Setting Parameters>

8-10 IM 01C27F01-01EN 8.3.3 Parameters for Wireless Communication (1) Network Information Concentrator object block : Configuration Allows confirming the network information. (2) Update Time CO block : Data publication period Sets the update time value to 1 to 3,600 seconds. The setting affects the battery life. (3) Measurement Mode TRANSDUCER block : MEASURE_ MODE The setting affects the battery life; it becomes shorter in the continuous display mode. When the update period is set to 1 second in intermittent mode, the mode is automatically switched to continuous mode. When the update period is 1 second, the mode is continuous mode, regardless of the measurement mode. (4) Measurement Rate TRANSDUCER block: MEASUREMENT_ RATE Reads the measurement rate value from 1 to 3600 seconds. The shorter the measurement period, the shorter the battery life. (5) Remaining battery life UAPMO block: ENERGY_LEFT The number of days of remaining battery life is indicated assuming ambient temperature condition as 23 degrees Celsius. While within 24 hours after power on, the number of days of 1461 (4 years) is indicated. UAPMO block: RESET_ENERGY_LEFT The number of days of battery life is reset. When changing battery, initialization of the remaining battery life is performed by RESET_ ENERGY_LEFT parameter. After initialization of the remaining battery life, confirm the number of days of battery life by ENERGY_LEFT parameter. 6) LCD display mode TRANSDUCER block : LCD_MODE 0) LCD off [Bar graph not displayed] 1) LCD intermittent display [Bar graph not displayed] 2) LCD continuous display [Bar graph not displayed] 5) LCD intermittent display [Bar graph not displayed] 6) LCD continuous display [Bar graph not displayed] 9) LCD intermittent display [Bar graph displayed] 10) LCD continuous display [Bar graph displayed] When the continuous display mode is set to ON, the LCD is on continuously. When the continuous display mode is set to OFF, the LCD turns on intermittently or turns off. The interval times of display are shown as follows. • LCD continuous display The LCD displays while 5 minutes then turns off. • LCD intermitted display The LCD displays while 3 seconds then turns off. • LCD continuous display + LCD intermitted display The LCD displays while 5 minutes then turns intermittently. When measurement mode is set as continuous mode, the LCD displays continuously regardless of display mode.

<8. Setting Parameters>

8-11 IM 01C27F01-01EN 8.3.4 Tag and Device Information If these are specified when ordering, the designated Tag No. and device information are set and shipped. Tag No. and device information can be checked as follows. • Procedure to call up the tag No. and device information - Device Tag ( Software Tag ) - Software Tag (only if needed) This is specified when writing characters (up to 16 characters) of amplifiers TAG that differ from characters specified in Tag No. - TAG_DESC This is a universal parameter to store the comment that describes the content of the tag located in the TRANSDUCER and AI blocks. The AI1 and AI3 blocks of the AI blocks correspond to the pressure and temperature, respectively. • When changing the device information, input the information based on the following limitation on the number of characters. - Message function (up to 32 characters) TRANSDUCER block : TAG_DESC AI1, AI3 block : TAG_DESC 8.3.5 Unit The unit parameter is set at the factory before shipment if specified at the time of order. Follow the procedure below to change the unit parameter. • Procedure to call up the Unit display (Units Index) Al1, Al3 block : SCALE: Units Index To change the Unit display, choose desired unit among the list of displayed unit selecting AI1 block as for the pressure, and AI3 block as for temperature in the AI blocks. 8.3.6 Range Change The range values are factory-set as specified by the customer. To change the range, follow the steps below. Keypad input — LRV and URV The measurement span is determined by the upper and lower range values. In this method, the upper and lower range values can be set independently, and the span changes according to the range limit values sent to the transmitter. • Procedure to call up the PV_RANGE display. AI1 block : PV_RANGE Select the AI1 block for the pressure, then select “EU at 0%” and “EU at 100%” displayed in the PV_RANGE parameters. And input the lower range and upper range values for the range. 8.3.7 Output Signal Low Cut Mode Setup Low cut mode can be used to stabilize the output signal near the zero point. (There is 10% of hysteresis at only point of transition from low to high) [Setup Low Cut Value] • Procedure to call up the LOW_CUTOFF display AI1 block: LOW_CUTOFF Select the AI1 block for the pressure, and then input a value in the output range from 0 to 20% for the LOW_CUTOFF parameter. Example: setup LOW_CUT of output to 15% LOW_CUTOFF = (“Eu at 100%” – “Eu at 0%”) * 0.15 + “Eu at 0%” [Setup Low Cut Mode] • Procedure to call up the LOWCUT_MODE display AI1 block: LOWCUT_MODE Select the AI1 block for the pressure, and then select Linear or Zero for the LOWCUT_MODE parameter. F0804.ai (%) 50 20 0 50 (%) Low cut mode “Linear” Low cut mode “Zero” Low cut at 20% (%) 50 20 0 50 (%) Low cut at 20% Output Output Input Input Figure 8.2 Low Cut Mode

<8. Setting Parameters>

8-12 IM 01C27F01-01EN The low cut point has hysteresis so that the output around the point is behaved as below figure. Output mode: Linear Low cut mode: Zero Low cut: 20.00% Output Setting range: 0 to 20% Input 0% (20%) 2% Low cut point Hystrersis fixed at 10% of the cut point F0805.ai 8.3.8 Integral Indicator Scale Setup The following three displays are available for the integral indictor: pressure and temperature. The following three variables can be displayed on the integral indicator: % of pressure range, and % of temperature range. Available displays Description and related parameters % of range (PRES %) Indicates input pressure in –10 to 110% range depending on the set range (LRV and URV). PRES % 45.6 % Follow the procedure described in (a) to (b) below to set the integral indicator. (a) Display Selection Display set to DISPLAY_SEL is displayed on the integral indicator. • Procedure to call up the DISPLAY_DEL display TRANSDUCER block: DISPLAY_SEL The DISPLAY_SEL parameter enables the pressure (AI1 block), and, temperature (AI3 block) to be displayed on the LCD. Select whether or not to enable each block to be displayed. (b) Cyclic Display Information in the AI1, AI3 blocks can be displayed cyclically according to the display On/Off setting for the pressure (AI1 block), and temperature (AI3 block) selected in the DISPLAY_SEL parameter. 8.3.9 Unit for Displayed Temperature When the instrument is shipped, the temperature units are set to C (Centigrade). Follow the procedure below to change this setting. • Procedure to call up the Unit Index display AI3 Block: SENSOR_RANGE: Units Index Confirm that ºC (deg C) is selected in the Units Index parameter for the temperature(AI3 block). Note: When the unit is changed by units index parameter in temperature (AI3 block), units of capsule temperature is also changed. 8.3.10 Zero Point Adjustment and Span Adjustment Each EJX-B series transmitter is characterized by factory. But there are some errors caused by environment and installed posture. There are Zero and Span Adjustments to fine-tune those errors. Zero Adjustment is adjustment for one point to adjust the bottom value of the measurement range as 0% of output. The Span Adjustment defines input and output characteristic between two points that’s one side assumed as standard. This is used when there is doubt of span drift or when it is impossible to make zero at absolute pressure with adjustment for user’s pressure standard. (1) Zero Point Adjustment a. To set 0% at current input, perform following procedure. This method is used only when the pressure at bottom of measurement range is zero. • Procedure to call up the calibration adjustment parameter (CAL_STATUS) AI1 block: CAL_STATUS Confirm the value of CAL_SUCCESS that is 1 using the CAL_STATUS parameter. b. To match current input and output value, follow procedure Like the measurement that is impossible to set process pressure to 0kPa, output value is adjustment to actual level by other measurement using glassgage.

<8. Setting Parameters>

8-13 IM 01C27F01-01EN Example: Pressure Transmitter’s span is 0 to 25.00kPa, current level is 13.50kPa, current output is 13.83kPa. • Procedure to call up the lower limit adjustment parameter (CAL_POINT_LO). AI1 Block: CAL_CMD: CAL_POINT_LO Set the actual level value of 13.50 kPa to the CAL_POINT_LO parameter for the pressure (AI1 block). Apply an actual input and confirm the value specified in CAL_POINT_LO as the output value. • Procedure to call up the calibration adjustment parameter (CAL_CMD). AI1 block: CAL_CMD: CAL_LOW The present output is changed from 13.83kPa to 13.50 kPa in CAL_LOW of the pressure (AI1 block) CAL_CMD parameter. • Procedure to call up the calibration status parameter (CAL_STATUS). AI1 block: CAL_STATUS Confirm the value of CAL_SUCCESS that is 1 using the CAL_STATUS parameter. c. Using External Zero adjustment Screw External Zero-adjustment parameter (EXTERNAL_ ZERO_TRIM) can set permission or prohibition to adjustment by External Zero-adjustment Screw. Set “Trim on” to use the External Zero-adjustment Screw. (“Trim on” at shipment) Use a slotted screwdriver to turn the zeroadjustment screw. Equalize the transmitter, then turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. The degree of zero adjustments varies with the screw turning speed; turn the screw slowly to make a fine adjustment, quickly to make a rough adjustment. IMPORTANT When zeroing with the zero-adjustment screw, turn the screw firmly until ▲ or ▼ mark is displayed on the integral indicator since there exists mechanical dead-band of the screw. (2) Span Adjustment Span Adjustment is function to change the input and output characteristic that assumed the bottom value (zero point) of measurement range a standard. Therefore, perform span adjustment (adjustment of the upper limit value) after zero adjustment (adjustment of bottom limit value). After adding the pressure at point of adjustment and setting pressure value as parameter, the transmitter calculates quantity of adjustment and performs adjustment automatically. • Procedure to call up the lower limit value parameter (CAL_POINT_LO) AI1 block: CAL_CMD: CAL_POINT_LO Set the lower limit adjustment value on the pressure (AI1 block) CAL_POINT_LO parameter screen. Apply a reference pressure corresponding to the lower limit of the measurement range to the pressure transmitter and confirm the pressure when it stabilized. • Procedure to call up the calibration adjustment parameter (CAL_CMD) AI1 block: CAL_CMD: CAL_LOW Confirm the lower limit of the measurement range in CAL_LOW of the pressure (AI1 block) CAL_CMD parameter. • Procedure to call up the calibration status parameter (CAL_STATUS) AI1 block: CAL_STATUS Confirm the value of CAL_SUCCESS that is 1 using the CAL_STATUS parameter. • Procedure to call up the upper limit adjustment parameter (CAL_POINT_HI). AI1 block: CAL_CMD: CAL_POINT_HI Set the upper limit adjustment value for the pressure (AI1 block) CAL_POINT_HI parameter. Apply a reference pressure corresponding to the upper limit of the measurement range to the pressure transmitter and confirm the when it has stabilized. • Procedure to call up the calibration adjustment parameter (CAL_CMD). AI1 block: CAL_CMD: CAL_HIGH Confirm the upper limit of the measurement range in CAL_HIGH of the pressure (AI1 block) CAL_CMD parameter.

<8. Setting Parameters>

8-14 IM 01C27F01-01EN • Procedure to call up the calibration status parameter (CAL_STATUS) AI1 block: CAL_STATUS Confirm the value of CAL_SUCCESS that is 1 using the CAL_STATUS parameter. (3) Reset Adjustments to Factory Setting A reset to the factory setting can be performed using CAL_CLEAR of the pressure (AI1 block) CAL_CMD parameter for the input pressure. After calibration, confirm status by using the pressure (AI1 block) CAL_STATUS. The amount of adjustment made by the external zero-adjustment screw can be reset to the initial setting as well. • Procedure to call up the calibration adjustment parameter (CAL_CMD). AI1 block: CAL_CMD: CAL_CLEAR 8.3.11 Software Write Protect Hardware write protection and software write protection functions are available for this transmitter • Procedure to call up the protection setting parameter (UAP_OPTION) UAPMO block: UAP_OPTION The following settings can be configured in the UPA_OPTION parameter. - Setting to enable or disable changing the setting to the DIAG_SWITCH and DIAG_ CONFIG parameters. - Setting to enable or disable the hardware write protection switch. - Setting to enable or disable software write protection. • Procedure to call up the protection setting display parameter (HW_WRITE_PROTECT) UAPMO block: HW_WRITE_PROTECT The HW_WRITE_PROTECT parameter enables the switch status of hardware write protection to be displayed. For the relationship between hardware write protection and software write protection, refer section 10. “Parameter Summary”. 8.3.12 Switching to Deep Sleep Mode When the instrument will not be used for a long time, switch the instrument to deep sleep mode to conserve battery power. To switch to deep sleep mode, follow the procedure below. • Procedure to call up the switch-to-deep-sleep parameter TRANSDUCER block: SPECIAL_CMD Set Deep Sleep mode (0002) to the SPECIAL_ CMD parameter for the TRANSDUCER block. To start from deep sleep mode, either remove and insert the battery pack, or use the configuration tool. NOTE • This procedure to switch to deep sleep mode can only be use for wireless communication. • Transmitter becomes the stop state after setting deep sleep mode and cannot reply any request from Communication Tool. • For this reason, there is the case that an error is display on Communication Tool. • To wake up from deep sleep mode, please pull battery pack, and wait more than 30 seconds before attaching battery back. 8.3.13 Switching to Silence Mode This is a function to pause the instrument when it cannot join the field wireless network after a specified time has elapsed. This function is effective in conserving battery power when, for example, the installation of the field wireless integrated gateway is delayed compared to that of field wireless devices. The default value is 28800 seconds (about 8 hours). Thereafter, a cycle of a one-hour pause and six-minute search is repeated until the instrument can join the field wireless network. • Procedure to call up the switch-to-silence parameter (RADIO_SILENCE) UAPMO block: RADIO_SILENCE Set 0 to 231 seconds for the RADIO_SILENCE parameter of the UAPMO block. If 0 is set, the RADIO_SILENCE parameter is invalid. To start from silence mode, either remove and insert the battery pack, or use the configuration tool.

<8. Setting Parameters>

8-15 IM 01C27F01-01EN 8.4 Self-Diagnostics 8.4.1 Identify Problems by Using the Communicator First, check DIAG_STATUS of the self-diagnostic result. UAPMO block: DIAG_STATUS Any of the four categories (Check function, Maintenance required, Failure, and Off specification) according to NAMUR NE107* is supplied to DIAG_STATUS of each diagnostic result. Table 8.3 DIAG_STATUS Bits Contents Example NAMUR NE107 Categorization Bit31 (MSB) F: Failure status --- Bit30 C: Function check status --- Bit29 O: Out of specification status --- Bit28 M: Maintenance required status --- Bit27 Faults in electronics F Bit26 Faults in sensor or actuator element F Bit25 Installation, calibration problem C Bit24 Out of service C Bit23 Outside sensor limits O Bit22 Environmental conditions out of device specification O Bit21 Fault prediction: Maintenance required M Bit20 Power is critical low: maintenance need short-term M Bit19 Power is low: maintenance need mid-term M Bit18 Software update incomplete C Bit17 Simulation is active C Bit16-Bit08 reserved by WCI --- Bit07-Bit01 vendor specific area --- Bit00 Detail information available 1: available 0: no available --- 2) When changing the Diag Switch parameter: a) UAPMO block : UAP_OPTION, select enable. b) UAPMO block : DIAG_SWITCH, turn ON Check function for Out of Service. c) UAPMO block : UAP_OPTION, select disable. Note: Be careful when changing the alert category and turning detection on and off as described above. Be sure to set UAP OPTION to disable again to prevent setting errors. * NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices” Checking the DIAG_STATUS category allows taking the proper action. The DIAG_STATUS contents are common for all ISA devices, and the setting for the DIAG_STATUS category can be changed. For further details, refer to DIAG_ STATUS_Detail. In DIAG_STATUS Contents that can be diagnosed by the EJX, the alert category set in Out of Service can be changed to Check function. To do so, follow one of the two procedures below. 1) When using the DIAG_CONFIG parameter: a) UAPMO block : UAP_OPTION, select enable. b) UAPMO block : DIAG_CONFIG, change Out of Service from Failure to Check function. c) UAPMO block : UAP_OPTION, select disable.

<8. Setting Parameters>

8-16 IM 01C27F01-01EN Table 8.4 Diagnostic Results Summary DIAG_STATUS Contents NAMUR NE107 Category DIAG_STATUS_DETAIL Description Faults in electronics F AMP_T_SENSOR_FAIL Amplifier temperature sensor failure AMP_EEPROM_FAIL Amplifier EEPROM failure AMP_EEP_IRREGULAR AMP EEPROM version not correct AMP_F1_ERROR F1 error G_A_COMM_FAIL G/A failure FC_DELTA_T_FAIL C-side delta T circuit failure FR_DELTA_T_FAIL R-side delta T circuit failure WL_AD_FAIL Battery voltage not detected (AMP failure) Faults in sensor or actuator element F FC_SENSOR_FAIL C sensor frequency failure FR_SENSOR_FAIL R sensor frequency failure CAP_T_SENSOR_FAIL Capsule temperature sensor failure CAP_EEPROM_FAIL Capsule EEPROM failure CAP_EEP_IRREGULAR CAP EEPROM version not correct FC_UNOSC_FAIL C sensor oscillation stop failure FR_UNOSC_FAIL R sensor oscillation stop failure Installation, calibration problem C DP_TRIM_SPAN_OUTSIDE Pressure span adjustment variable outside of range DP_TRIM_ZERO_OUTSIDE Pressure zero adjustment variable outside of range SP_TRIM_SPAN_OUTSIDE Static pressure span adjustment variable outside of range SP_TRIM_ZERO_OUTSIDE Static pressure zero adjustment variable outside of range LCD_OUTSIDE_LIMIT LCD display outside of limits Out of service O AI1_OUT_OF_SERVICE AI1 O/S mode AI2_OUT_OF_SERVICE AI2 O/S mode AI3_OUT_OF_SERVICE AI3 O/S mode Outside sensor limits C DP_OUTSIDE_LIMIT Pressure outside of range SP_OUTSIDE_LIMIT Static pressure outside of range CAPT_OUTSIDE_LIMIT Capsule temperature outside of range AMPT_OUTSIDE_LIMIT Amplifier temperature outside of range Environmental conditions out of device specification. O DP_OUTSIDE_RANGE Pressure setting outside of range SP_OUTSIDE_RANGE Static pressure setting outside of range Power is critical low: maintenance need short-term. M WL_DEEPSLP_ALM Deep sleep due to low battery Power is low: maintenance need mid-term M WL_LOWBAT_ALM Low battery Simulation is active C AI1_SIMULATION_ACTIVE AI1 Simulation mode AI2_SIMULATION_ACTIVE AI2 Simulation mode AI3_SIMULATION_ACTIVE AI3 Simulation mode

<8. Setting Parameters>

8-17 IM 01C27F01-01EN 8.4.2 Checking with Integral Indicator NOTE If an error is detected by running self-diagnostics, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at three-second intervals. See table 9.3 regarding the alarm codes. F0806.ai Figure 8.6 Integral Indicator

9.1 Overview

WARNING Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body or inhalation of vapors when draining condensate or venting gas from the transmitter pressure-detector section and even after dismounting the instrument from the process line for maintenance. Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disassembly and reassembly procedures required for component replacement. Transmitters are precision instruments. Please carefully and thoroughly read the following sections for information on how to properly handle them while performing maintenance. IMPORTANT • As a rule, maintenance of this transmitter should be done in a maintenance room that has all the necessary tools. • The CPU assembly, RF assembly and integral indicator contain sensitive parts that can be damaged by static electricity. Take precautions such as using a grounded wrist strap when handling electronic parts or touching the board circuit patterns. Also be sure to place the removed the CPU assembly, RF assembly and integral indicator into a bag with an antistatic coating. 9.2 Calibration Instruments Selection Table 9.1 lists the instruments that can be used to calibrate a transmitter. When selecting an instrument, consider the required accuracy level. Exercise care when handling these instruments to ensure they maintain the specified accuracy. 9.3 Calibration Use the procedure below to check instrument operation and accuracy during periodic maintenance or troubleshooting. 1) Insert the battery pack and then perform provisioning to have the transmitter join the Field Wireless Network for calibration. 2) Set the update period to 1 second using the configuration tool to set continuous for the transmitter. 3) Connect the devices as shown in Figure 9.1 and allow the transmitter to warm up for at least 5 minutes. IMPORTANT If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure should be applied as shown in the figure. If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied using a vacuum pump. 4) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter. Calculate the errors (differences between digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from 100% to 0%, and confirm that the errors are within the required accuracy. (Note) If output mode is “SQUARE MODE”, measurement range of 0, 6.25, 56.25, 100% instrument adds corresponding reference pressure. 5) When the test is finished, reset the update time to the initial value using the configuration tool.

Instruments Required for Calibration

Name Yokogawa-recommended Instrument Remarks Provisioning device • FieldMate (R2.02.01 or later) DeviceFile (R3.01.01 or later) • Infrared Adapter certified by Yokogawa Supplier: ACTiSYS Product name: IrDA InfraRed USB Adaptor Product number: IR224UN Configuration tool • Field Wireless Integrated Gateway attached Software Field Wireless Configurator Field Wireless Management Tool • Field Wireless System related Product Plant Resource Manager (PRM) (R3.05 or later) Digital manometer Model MT220 precision digital manometer 1) For 10 kPa class Accuracy: ±(0.015% of rdg + 0.015% of F.S.) for 0 to 10 kPa ±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa 2) For 130 kPa class Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa ±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa 3) For 700 kPa class Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa ±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa ±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa 4) For 3000 kPa class Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa ±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa 5) For 130 kPa abs class Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs Select a manometer having a pressure range close to that of the transmitter. Pressure generator Model MC100 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa {2500 mmH2O} Accuracy: ±0.05% of F.S. Requires air pressure supply. Dead weight gauge tester 25 kPa {2500 mmH2O} Accuracy: ±0.03% of setting Select the one having a pressure range close to that of the transmitter. Pressure source Model 6919 pressure regulator (pressure pump) Pressure range: 0 to 133 kPa {1000 mmHg} Prepare the vacuum pump for negative pressure ranges. Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives from which the instrument was purchased or the nearest Yokogawa office. P Reference pressure Pressure generator Supply pressure P Reference pressure Precision digital manometer Pressure source Using pressure generator Using pressure source with manometer F0901.ai Figure 9.1 Instrument Connections

9.4.1 Replacing the Integral Indicator

This subsection describes the procedure for replacing an integral indicator. (See figure 9.2) ■ Removing the Integral Indicator 1) Remove the cover. 2) While supporting the integral indicator with one hand, loosen its two mounting screws. 3) Dismount the LCD board assembly from the RF assembly. When doing this, carefully pull the LCD board assembly straight forward so as not to damage the connector pins between it and the RF assembly. ■ Attaching the Integral Indicator 1) Align both the LCD board assembly and RF assembly connectors and engage them. 2) Insert and tighten the two mounting screws. 3) Replace the cover. Zero- adjustment screw RF assembly CPU assembly Amplifier Cover Mounting screw Integral indicator Boss Stud F0902.ai Press forward Output terminal cable Zero-adjustment screw pin Figure 9.2 Removing and Attaching LCD Board Assembly and CPU Assembly 9.4 Disassembly and Reassembly CAUTION Precautions for the intrinsic safety explosion prevention type instrument Intrinsic safe type transmitters must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state. Check and confirm the insulation when it is reassembled to the original state. Check and confirm the insulation when it is reassembled to the original state. Refer to section 2.7 “Insulation Resistance and Dielectric Strength Test” for details of Resistance Test. This section describes procedures for disassembly and reassembly for maintenance and component replacement. CAUTION Always remove Battery pack and shut off pressures before disassembly and assembly. Use proper tools for all operations. Table 9.2 shows the tools required. Table 9.2 Tools for Disassembly and Reassembly Tool Quantity Remarks Phillips screwdriver 1 JIS B4633, No. 2 Slotted screwdriver 1 Allen wrenches 3 JIS B4648 One each, nominal 3, 4 and 2.5 mm Allen wrenches Wrench 1 Width across flats, 17 mm Torque wrench 1 Adjustable wrench 1 Socket wrench 1 Width across flats, 16 mm Socket driver 1 Width across flats, 5.5 mm Tweezers 1

9.4.2 Replacing the RF Assembly

This subsection describes how to replace the RF assembly (see Figure 9.2). ■ Removing the RF assembly 1) Remove the cover. 2) Remove the integral indicator (refer to subsection 9.4.1). 3) Remove the two stud bolts by using a socket driver (width across flats: 5.5 mm). 4) Disconnect the RF assembly from the CPU assembly. When doing this, carefully pull the RF assembly straight forward so as not to damage the connector pins between it and the CPU assembly. 5) Disconnect the antenna cable that connects the RF assembly and the antenna. NOTE Be careful not to apply excessive force to the RF assembly and the connector of the antenna cable when removing it. ■ Mounting the RF assembly 1) Connect the antenna cable between the RF assembly and the antenna. 2) Align both the RF assembly and CPU assembly connectors and engage them. 3) Tighten the two stud bolts. 4) Mount the integral indicator (refer to subsection 9.4.1). 5) Replace the cover. 9.4.3 Replacing the CPU Assembly This subsection describes how to replace the CPU assembly (see Figure 9.2). ■ Removing the CPU assembly 1) Remove the cover. Remove the integral indicator and the RF assembly (refer to subsections 9.4.1 and 9.4.2). 2) Turn the zero-adjustment screw to the position as shown in Figure 9.2. 3) Disconnect the power cable and the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage (see the upper left of Figure 9.2). 4) Use a socket driver (width across flats, 5.5 mm) to loosen the two bosses. 5) Carefully pull the CPU assembly straight forward to remove it. 6) Disconnect the flat cable (cable with white connector at the end) that connects the CPU assembly and the capsule. NOTE Be careful not to apply excessive force to the CPU assembly when removing it. ■ Mounting the CPU assembly 1) Connect the flat cable (with white connector) between the CPU assembly and the capsule. 2) Connect the output terminal cable (with brown connector) and the power cable to the CPU assembly. NOTE Make certain that the cables do not get pinched between the case and the edge of the CPU assembly. 3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU assembly straight onto the post in the amplifier case. 4) Tighten the two bosses. Mount the RF assembly, and the integral indicator (refer to subsections 9.4.1 and 9.4.2). IMPORTANT Confirm that the zero-adjustment screw pin is placed properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero- adjustment mechanism will be damaged. 5) Replace the cover.

9.4.4 Cleaning and Replacing the Capsule

Assembly CAUTION Precautions for the intrinsic safety explosion prevention type instrument Modification is not permitted by the user for intrinsic safety explosion prevention type transmitter. Consult our company when you want to exchange capsule assembly. Execute it only at time when the following points were confirmed for exchange capsule assembly in the same range of measurement. • Exchanged capsule assembly uses the one of the same specification. • Tighten Setscrew to fix the transmitter section and the pressure detector section surely after ending maintenance. This subsection describes the procedures for cleaning and replacing the capsule assembly. (See figure 9.3.) ■ Removing the Capsule Assembly IMPORTANT Exercise care as follows when cleaning the capsule assembly. • Handle the capsule assembly with care, and be especially careful not to damage or distort the diaphragms that contact the process fluid. • Do not use a chlorinated or acidic solution for cleaning. • Rinse with clean water after cleaning, please dry until completely dry. 1) Remove the CPU assembly as shown in subsection 9.4.3. 2) Remove the five setscrews, the stopper bolt, and the stopper that connect the transmitter section and pressure-detector section. 3) Remove the hexagon-head screw and the stopper. 4) Separate the transmitter section and pressure- detector section. 5) Clean the capsule assembly or replace with a new one. ■ Reassembling the Capsule Assembly 1) Reattach the transmitter section to the pressure-detector section. Reattach the stopper with the hexagon-head screw. 2) Tighten the two setscrews.(Tighten the screws to a torque of 1.5 N·m) 3) Install the CPU assembly according to subsection 9.4.3. 4) After completing reassembly, adjust the zero point and recheck the parameters. Stopper Stopper bolt Transmitter section Setscrew Pressure-detector section Pipe F0903.ai Figure 9.3 Removing and Mounting the Pressure- detector Section 9.4.5 Replacing the Battery Pack ■ Removing 1) Remove the terminal box cover. 2) Loosen the two battery pack mounting screws (see Figure 9.5). 3) Pull out the Battery pack. F0904.ai The battery pack mounting screws cannot be separated from the battery pack so as to prevent drop-off. Figure 9.4 Removing the Battery Pack

1) Insert the new battery pack lightly.

2) Push the center of the battery pack and insert it securely. 3) Tighten the two battery pack mounting screws to a torque of approximately 0.7 N·m. 4) Replace the terminal box cover. 5) Initialize the remaining battery life. How to initialize the remaining of battery life, refer to subsection 8.3.3 “Parameters for Wireless Communication”. 9.4.6 Replacing the Batteries The batteries in the battery pack can be replaced. WARNING Be sure to replace the batteries or disassemble and assemble the battery pack in a safe location. Doing so in an explosive area could cause an explosion. CAUTION When replacing the batteries, be sure to replace the two batteries at the same time and do not use an old and a new battery together. ■ Disassembling 1) Loosen the two battery case mounting screws (Figure 9.5). 2) Separate the battery case into two parts. 3) Remove the old batteries. ■ Assembling 1) Insert new batteries into the battery case. Be careful of the orientation of the batteries. 2) Attach the two parts of the battery case to each other. 3) Tighten the two battery case mounting screws to a torque of approximately 0.7 N·m. F0905.ai The battery pack mounting screws cannot be separated from battery pack so as to prevent drop-off. Figure 9.5 Removing the Battery Pack 9.4.7 Handling Batteries This battery pack contains two “D” size primary lithium/thionyl chloride batteries. Each battery contains approximately 5 grams of lithium, for a total of 10 grams in each pack. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Protect the electrode of the battery pack to avoid rapid electrical discharge. Discharged a battery may lead to fluid leakage and excessive heat. Batteries should be stored in a clean and dry area. For maximum battery life, storage temperature should not exceed 30°C. WARNING Handling the battery pack The following precautions must be observed in order to safely and effectively use a battery pack. Improper use may lead to fluid leakage, excessive heat, ignition, or explosion. • Never charge it. • Do not short-circuit it. • Do not disassemble, transform, or modify it. • Do not heat it or throw it into a fire. • Do not soak it in fresh water or seawater. CAUTION Observe the following precautions for the safe disposal of batteries. • Do not incinerate the battery, and do not expose it to a high temperature of 100°C or more. This may lead to fluid leakage or explosion. • Dispose of the battery according to laws and regulations. Use the following dedicated parts for the battery pack and batteries. ■ Battery Pack Part number: F9915MA ■ Batteries Part number: A1133EB Alternatively, Tadiran TL-5930/S batteries may be purchased and used. ■ Battery Case Part number: F9915NS

Transportation of products containing

lithium batteries : The battery pack contains lithium batteries. When transporting this transmitter with the battery pack inserted, keep it in deep sleep mode in order to conserve battery power. For details on how to switch to deep sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode.” Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation, and are also covered by the International Air Transport Association (IATA), the International Civil Aviation Organization (ICAO), and the European Ground Transportation of Dangerous Goods (ARD). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping. ■ Procedure to replace and dispose of the batteries of the product The following describes the EU Directive 006/66/EC (EU’s New Battery Directive), which applies only EU countries. This product uses batteries. When removing the batteries from this product and disposing of them, follow the national regulations on disposal. A battery collection system is available in EU countries. Batteries should be disposed of properly according to the system. Battery type : Primary lithium-thionyl chloride battery Crossed-out dustbin symbol CAUTION The above symbol means that the batteries with this symbol on them must be collected separately in accordance with AnnexII of EU’s New Battery Directive. ■ Procedure to remove the batteries safely: Refer to subsection 9.4.5 “Replacing the Battery Pack” and subsection 9.4.6 “Replacing the Batteries.” 9.5 Troubleshooting If any abnormality appears in the measured values, use the troubleshooting flow chart below to isolate and remedy the problem. Since some problems have complex causes, these flow charts may not identify all. If you have difficulty isolating or correcting a problem, contact Yokogawa service personnel. 9.5.1 Basic Troubleshooting First determine whether the process variable is actually abnormal or a problem exists in the measurement system. If the problem is in the measurement system, isolate the problem and decide what corrective action to take. This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting, and the transmitter equipped with an integral indicator will show an alarm code as a result of self- diagnosis. See subsection 9.5.3 for the list of alarms. See also each communication manual.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support Is process variable itself abnormal? Inspect the process system. Isolate problem in measurement system. Does problem exist in receiving instrument? Check/correct environmental conditions. Inspect receiver. Check transmitter. Check/correct operating conditions. Measurement system problem F0906.ai YES NO NO YES Environmental conditions Operating conditions Transmitter itself Figure 9.6 Basic Flow and Self-Diagnostics 9.5.2 Troubleshooting Flowcharts Check display of the error code. Check self-diagnostics by configuration tools. Does the self-diagnostic indicate problem location? Contact Yokogawa service personnel. F0907.ai The following sorts of symptoms indicate that transmitter may not be operating properly. Example : • There is no output signal. • Output signal does not change even though process variable is known to be varying. • Output value is inconsistent with value inferred for process variable. Fix pressure leaks, paying particular attention to connections for impulse piping,pressure-detector section, etc. Fully open valve. Are valves opened or closed correctly? Is there any pressure leak? YES NO YES NO NO YES Refer to Alarm Message Summary in Subsection 9.5.3. Is the Field Wireless Network setting correct? NO YES Reconnect to the Field Wireless Network.

Connect an configuration tool and check self-diagnostics.

Does the self- diagnostic indicate problem location? Contact Yokogawa service personnel. F0908.ai Are valves opened or closed correctly? Refer to Alarm Message Summary in Subsection 9.5.3. YES NO Fix pressure leaks, paying particular attention to connections for impulse piping, pressure-detector section, etc. Fully open valve. NO YES YES NO Adjust the zero point. NO YES Is there any pressure leak? Is zero point adjusted correctly? Output travels beyond 0% or 100%. Connect an configuration tool and check self-diagnostics. Contact Yokogawa service personnel. F0909.ai Are valves opened or closed correctly? Is impulse piping connected correctly? Refer to Alarm Message Summary in each communication manual to take actions. Provide lagging and/or cooling, or allow adequate ventilation. Refer to subsection 9.2 "Calibration Instruments Selection". Fully open valve. Refer to individual model user manuals and connect piping as appropriate for the measurement purpose. Adjust the output. Is transmitter installed where there is marked variation in temperature? Is output adjusted correctly? Large output error. Does the self- diagnostic indicate problem location? Were appropriate instruments used for calibration? YES NO YES NO NO YES NO YES NO YES NO YES

9.5.3 Alarms and Countermeasures

Various diagnostics of the Al2 object and the static pressure is not supported in this instrument. Table 9.3 Alarms Message Summary (Causes and Actions) Integral indicator Factory NAMUR category Bit DIAG_STATUS DIAG_STATUS_DETAIL Cause Release/ recovery conditions (except restart) Action AL. 01 CAP. ERR F Bit 26 Faults in sensor or actuator element FC_SENSOR_FAIL Pressure sensor failure Recovers only when AUTO RECOVER is ON and within the range Replace the capsule. FR_SENSOR_FAIL FC_UNOSC_FAIL Recovers only when AUTO RECOVER is ON and oscillation does not stop FR_UNOSC_FAIL CAP_T_SENSOR_FAIL Capsule temperature sensor failure None CAP_EEPROM_FAIL Capsule EEPROM memory failure Recovers when A or B returns to normal. CAP_EEP_IRREGULAR None AL. 02 AMP. ERR F Bit 27 Faults in electronics AMP_T_SENSOR_FAIL Amplifier temperature sensor failure None Replace the amplifier. AMP_EEPROM_FAIL AMP_EEP_IRREGULAR Amplifier EEPROM failure None FC_DELTA_T_FAIL FR_DELTA_T_FAIL AMP_F1_ERROR G_A_COMM_FAIL WL_AD_FAIL Amplifier failure None AL. 10 PRESS C Bit 23 Outside sensor limits DP_OUTSIDE_LIMIT Pressure outside of specified range Recovers when input pressure returns within the range. Check the input pressure. AL. 11 ST. PRSS SP_OUTSIDE_LIMIT Static pressure outside of specified range Recovers when static pressure returns within the range. Check the input pressure. AL. 12 CAP. TMP CAPT_OUTSIDE_LMIT Capsule temperature outside of range (-50 to 130°C) Recovers when temperature returns within the range. Retain heat or insulate so that temperature returns within the specified range. AL. 13 AMP. TMP AMPT_OUTSIDE_LIMIT Amplifier temperature outside of range (-50 to 95°C) Recovers when temperature returns within the range. Retain heat or insulate so that temperature returns within the specified range.

Power is critical

low: maintenance need short - term WL_DEEPSLP_ALM Low remaining battery power results in switching to deep sleep. None Replace the batteries. AL. 70 LOW. BAT M Bit 19 Power is low: maintenance need mid - term WL_LOWBAT_ALM Low remaining battery power None Replace the batteries. AL. 60 AI OOS C Bit 24 O/S AI1_OUT_OF_SERVICE AI1 block is O/S mode. Returns when the mode target of AI1 block is other than O/S. Set the mode target to AUTO. AL. 61 AI OOS AI2_OUT_OF_SERVICE AI2 block is O/S mode. Returns when the mode target of AI2 block is other than O/S. Set the mode target to AUTO. AL. 62 AI OOS AI3_OUT_OF_SERVICE AI3 block is O/S mode. Returns when the mode target of AI3 block is other than O/S. Set the mode target to AUTO.

AI1 block is

simulate mode. Returns when the simulate mode of AI1 block is set to disable. 1 (Disable) Check the simulate mode of AI1 block. AL. 64 AI SIM SimulationActive (AI2) AI2 block is simulate mode. Returns when the simulate mode of AI2 block is set to disable. 1 (Disable) Check the simulate mode of AI2 block. AL. 65 AI SIM C Bit 17 Simulation is active SimulationActive (AI3) AI3 block is simulate mode. Returns when the simulate mode of AI3 block is set to disable. 1 (Disable) Check the simulate mode of AI3 block. “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off specification) according to NAMUR NE107*. * NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”

Alarm Message Summary (Output Actions)

Integral Indicator Factory NAMUR category Bit DIAG_STATUS DIAG_STATUS_DETAIL Output actions Pressure Static Pressure Capsule Temp Value Amp Temp Value AL. 01 CAP. ERR F Bit 26 Faults in sensor or actuator element FC_SENSOR_FAIL Output value (hold value) Output status (BAD: Sensor Failure) Output value (hold value) Output status (BAD: Sensor Failure) Normal action Normal action FR_SENSOR_FAIL FC_UNOSC_FAIL FR_UNOSC_FAIL CAP_T_SENSOR_FAIL Output value (calculated in a normal way) Output status (UNCERTAIN: Subnormal) Output value (calculated in a normal way) Output status (UNCERTAIN: Subnormal) Output value (calculated in a normal way) Output status (BAD: Sensor Failure) CAP_EEPROM_FAIL Output value (hold value) Output status (BAD: Device Failure) Output value (hold value) Output status (BAD: Device Failure) Output value (calculated in a normal way) Output status (BAD: Device Failure) Output value (calculated in a normal way) Output status (BAD: Device Failure) CAP_EEP_IRREGULAR AL. 02 AMP.ERR F Bit 27 Faults in electronics AMP_T_SENSOR_FAIL Normal action Normal action Normal action Output value (calculated in a normal way) Output status (BAD: Sensor Failure) AMP_EEPROM_FAIL Output value (hold value) Output status (BAD: Device Failure) Output value (hold value) Output status (BAD: Device Failure) Output value (calculated in a normal way) Output status (BAD: Device Failure) Output value (hold value) Output status (BAD: Device Failure) AMP_EEP_IRREGULAR FC_DELTA_T_FAIL Output value (hold value) output status (BAD: Device Failure) Output value (hold value) Output status (BAD: Device Failure) Normal action Output value (hold value) output status (BAD: Device Failure) FR_DELTA_T_FAIL AMP_F1_ERROR Output value (calculated in a normal way) Output status (BAD: Device Failure) Output value (calculated in a normal way) Output status (BAD: Device Failure) G_A_COMM_FAIL WL_AD_FAIL

Bit 23 Outside sensor

limits DP_OUTSIDE_LIMIT Output value (calculated in a normal way) Output status (UNCERTAIN: Sensor Conversion not Accurate) Output value (calculated in a normal way) Output status (UNCERTAIN: Subnormal) Normal action Normal action AL. 11 ST. PRSS SP_OUTSIDE_LIMIT Output value (calculated in a normal way) Output status (UNCERTAIN: Subnormal) Output value (calculated in a normal way) Output status (UNCERTAIN: Sensor Conversion not Accurate) Normal action Normal action AL. 12 CAP. TMP CAPT_OUTSIDE_LIMIT Output value (calculated in a normal way) Output status (UNCERTAIN: Subnormal) Output value (calculated in a normal way) Output status (UNCERTAIN: Subnormal) Output value (calculated in a normal way) Output status (UNCERTAIN: Sensor Conversion not Accurate) Normal action AL. 13 AMP. TMP AMPT_OUTSIDE_LIMIT Normal action Normal action Normal action Output value (calculated in a normal way) Output status (UNCERTAIN: Sensor Conversion not Accurate) AL. 53 P. SDEV C Bit 25 Installation, calibration problem DP_TRIM_SPAN_ OUTSIDE Output value (calculated in a normal way) Output status (UNCERTAIN: Engineering Unit Range Violation) Normal action Normal action Normal action AL. 53 P. ZDEV DP_TRIM_ZERO_ OUTSIDE Normal action Normal action Normal action Normal action AL. 55 SP. SDEN SP_TRIM_SPAN_ OUTSIDE Normal action Normal action Normal action Normal action AL. 55 SP.ZDEN SP_TRIM_ZERO_ OUTSIDE Normal action Normal action Normal action Normal action AL. 79 OV. DISP LCD_OUTSIDE_LIMIT Normal action Normal action Normal action Normal action AL. 30 RANGE O Bit 22 Environmental conditions out of device specification DP_OUTSIDE_RANGE Normal action Normal action Normal action Normal action AL. 31 SP. RNG SP_OUTSIDE_RANGE Normal action Normal action Normal action Normal action AL. 70 LOW.BAT M Bit 20 Power is critical low: maintenance need short - term WL_DEEPSLP_ALM Normal action Normal action Normal action Normal action

LOW. BAT M

Bit 19 Power is low: maintenance need mid - term WL_LOWBAT_ALM Normal action Normal action Normal action Normal action AL. 60 AI OOS C Bit 24 O/S AI1_OUT_OF_SERVICE Normal action Normal action Normal action Normal action AL. 61 AI OOS AI2_OUT_OF_SERVICE Normal action Normal action Normal action Normal action AL. 62 AI OOS AI3_OUT_OF_SERVICE Normal action Normal action Normal action Normal action AL. 63 AI SIM C Bit 17 Simulation is active SimulationActive (AI1) Normal action Normal action Normal action Normal action AL. 64 AI SIM SimulationActive (AI2) Normal action Normal action Normal action Normal action AL. 65 AI SIM SimulationActive (AI3) Normal action Normal action Normal action Normal action “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off specification) according to NAMUR NE107*. * NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”

<10. Parameter Summary>

10-1 IM 01C27F01-01EN 10. Parameter Summary The setting of differential pressure (Al2 block) is invalid in this instrument. The output value of Al2 object and the output status are “0.0”(zero) and “Uncertain” respectively. Various diagnostics of the Al2 object and the static pressure is not supported in this instrument. Table 10.1 Parameter Object ID Attribute ID Label Description Default value Handling 1. UAPMO block 1 VERSION_ REVISION Indicates the application revision of EJX This revision when the application software is downloaded. --- R 10 ST_REV Indicates the revision level of the fixed parameters of UAP Used, for example, to check whether parameters have been change. 0 R 64 IDENT_NUMBER Indicates the vender ID, model ID, and revision of the device. --- R 65 CTS_VERSION Indicates the version of the communication stack test system (CTS). 0 R 66 ITS_VERSION Indicates the version of the inter operability test system (ITS). 0 R 67 DIAG_STATUS Indicates the diagnostic results of the device based on the NAMUR NE0107* model. Setting DIAG_STATUS to ON allows turning OFF and ON the display of the diagnostic results for each summary, and changing Categorize For Categorize at the time of shipment, refer to tables 8.3 and 10.2. 0 R 68 UAP_OPTION Allows setting the DIAG_STATUS and write protection of UAP. DIAG_STATUS configuration 1: Enable, 0: Disable (default) Hardware Write Protect 1: Enable, 0: Disable (default) Software Write Protect 1: On, 0: Off The following table shows the relationship between the hardware write protection and software write protection. Hardware write protect Hardware switch condition Software write protect Write protect Disable Off or On Off No Disable Off or On On Protected Enable Off Off or On No Enable On Off or On Protected 0 W 69 DIAG_SWITCH Allows setting On/Off for each summary of DIAG_ STATUS when UAP_OPTION is set to Enable and DIAG_STATUS is set to Enable. 0 W 70 DIAG_CONFIG Allows Categorize for each summary of DIAG_STATUS when UAP_OPTION is set to Enable and DIAG_ STATUS is set to Enable. Refer to Table 10.2. W 102 DIAG_STATUS_ DETAIL[2] Detailed information on DIAG_STATUS. For Categorize at the time of shipment, refer to Table 10.2. Refer to Table 10.2. R 103 ENERGY_LEFT Indicates the number of days of remaining battery life assuming ambient temperature condition as 23 degrees Celsius. The unit is day. --- R 104 RESET_ENERGY_ LEFT Initialize the remaining battery life (ENERGY_LEFT) and reset it as new batteries. Perform the battery replacement. 0 = Continue 1 = Reset 0 (reading value is always 0) W

<10. Parameter Summary>

10-2 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 1.UAPMO block (continued) 105 POWER_ SUPPLY_STATUS Indicates the battery level and the power supply method. 0 = external power supply 1 = battery level 75% or more 2 = battery level 25% ~ 75% 3 = battery level 25% or less R 110 HW_WRITE_ PROTECT Allows recognizing the status of the hardware write protection switch. (Switch Off, Switch On) R 111 RADIO_SILENCE Repeats a cycle of a 1-hour pause and 6-minute search if the instrument cannot join the network after a time specified in RADIO_SILENCE has elapsed. 28800 W 2. UDO block 2 DESCRIPTION Indicates the version and model information of the downloaded data. --- R 3 STATE Indicates the present transition state. --- R 5 MAX_BLOCK_ SIZE Maximum block size. This value is smaller than the maximum data size of APDU. --- R 14 LAST_BLOCK_ DOWNLOADED Indicates the last downloaded block number. 0 means that no block has been downloaded. --- R 16 ERROR_CODE Indicates the error codes for DLError. 0 = noError 1 = Timeout 2 = ClientAbort 64 = Apply failure --- R 3. CO block 1 REVISION Indicates the version level of COMM_ENDPOINT, etc. --- R 2 COMM_ ENDPOINT Indicates the Endpoint information. The following shows the components. 1. Network address of remote endpoint 2. Transport layer port at remote endpoint 3. Object ID at remote endpoint 4. Stale data limit 5. Data publication period 6. Ideal publication phase 7. PublishAutoRetransmit 8. Configuration status --- W 3 COMM_ CONTRACT Indicates the Contract information. The following shows the components. 1. ContractID 2. Contract_Status 3. Actual_Phase --- R 4 PUB_ITEM_MAX Maximum PUB_ITEM value --- R 5 PUB_ITEM_NUM PUB_ITEM number --- R 6 PUB_ITEM Indicates the PUB_ITEM information. The following shows the components 1. ObjectID 2. AttributeID 3. AttributeIndex 4. Size --- W

<10. Parameter Summary>

10-3 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 4. TRANSDUCER block 1 TAG_DESC Memo field available to write anything. Transducer W 2 AUTO_ RECOVERY Allows specifying the action when the cause of a sensor failure is removed. OFF (=0): AL continues to be indicated even after the cause of the sensor error is removed, and the BURN OUT state is not released. ON (=1): The AL indication for sensor failure disappears and normal action is resumed when the cause of the sensor failure is removed. ON W 3 MODEL Indicates the model name of the transmitter. --- R 4 SENSOR_SN Indicates the device number of the transmitter. --- R 5 MEASUREMENT _RATE Indicates the measurement period of process values. --- R 6 MEASURE_ MODE Measurement mode selects continuous mode or intermittent mode. When the update time is set to 1 in intermittent mode, the mode is automatically switched to continuous mode. When the update time is set to 1 second, the computation process is in continuous mode, regardless of the measurement mode. intermittent mode W 7 WIRELESS_ STATUS Indicate the communication status. 1. Indicates the initial idle status or join status. (idle status, join status) 2. Indicates whether Contract(Pub) is established. (not establishment, establishment) 3. Indicates whether Contract(R/W) is established. (not establishment, establishment) 1. idle status 2. not estabilishment 3. not esabilishment R 8 DISPLAY_SEL Select the LCD display contents. 1. Indicates display status of PV Value of AI1 (displayed, not displayed) 2. Indicates display status of PV Value of AI2 (displayed, not displayed) 3. Indicates display status of PV Value of AI3 (displayed, not displayed) 1. displayed 2. not displayed 3. not displayed W 9 LCD_MODE Select the LCD mode 1. Indicates the ON mode. (off, intermittent) 2. Indicates whether continuous or not. (continuous off, continuous on) 3. EJX does not use. 4. Indicates the bar graph display. (bar graph not displayed, bar graph displayed) 1. OFF 2. continuous OFF 3. --- 4. bar graph not displayed W 10 SPECIAL_CMD Special function parameter. 0 = initialize value at READ (None) 1 = EJX does not use. 2 = deep sleep status To start from deep sleep mode, either remove and insert the battery pack, or use the configuration tool. 0 W 11 SPECIAL_ ORDER_ID Displays the special order number, if applicable. --- R 12 UNIT_SEL1 Selects whether to automatically apply the unit to the word for the parameter for which the unit display is selected, or apply the characters that are written to DISPLAY_UNIT. (Auto, Custom) Auto W 13 DISPLAY_UNIT1 When Custom is selected in UNIT_SEL1, set the display unit using 6 characters or less. NULL W

<10. Parameter Summary>

10-4 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 5. AI1 block 1 PV AL1 is a pressure output object. Indicates the primary analog value (or corresponding process value) and status used to execute this function. Allows updating data by specifying this for the Concentrator object. 1. Value: output value of Al object 2. Status: Specify output status of Al object. 1. Value = --- 2. Status = --- W 2 MODE A universal parameter to indicate the block’s operation status. Each O/S, Auto, and Man can select from. 1. Target : Specify Al object mode. 2. Actual : Indicates current mode of Al object. 3. Permitted : Indicates the mode selected by Target of Al object. 4. Normal : Indicate normal status mode of Al object. 1. Target=O/S 2. Actual=O/S 3. Permitted= O/S 4. Normal=O/S W 3 CONC_OID Indicates the Concentrator object value that corresponds to the data update of the PV value. 3 R 4 SCALE Allows specifying the upper or lower limit for the PV scaling, unit code, etc. 1. EU at 100% : Indicate the upper limit of the PV value. 2. EU at 0% : Indicate the lower limit of the PV value. 3. Units Index : Indicate the setting unit used for the PV value. 4. Decimal : Indicate the digit number below the decimal point displayed in the LCD indicator. 1. EU at 100% = 100 2. EU at 0% = 0 3. Units Index = % 4. Decimal = 2 W 26 TAG_DESC A universal parameter to store the comment that describes the tag Al1: Differential Pressure W 27 PV_FTIME Allows adjusting the time constant for filtering the PV value. Setting unit: Second. This is enabled for the Continuous mode. 0 sec W 28 SIMULATE_ SWITCH A simulation function switch for the AI object test (Disable, Enable) 1 (Disable) W 29 TRANSDUCER_ VALUE When SIMULATE_SWITCH is set to Disable, this value is used as the input value for the AI object. Refer to Figure 10.1. Disable R 30 SIMULATE_ VALUE When SIMULATE_SWITCH is set to Enable, this value is used as the input value for the AI object. The input value can be changed. --- W 51 UPPER_LIM Indicates the upper limit (URL) for the pressure. --- R 52 LOWER_LIM Indicates the lower limit (LRL) for the pressure. --- R 53 PV_RANGE Sets the measurement range. 1. EU at 100% : Indicates input value of the upper limit. 2. EU at 0% : Indicates input value of the lower limit. 3. Units Index : Indicates the units of the measurement range. 4. Decimal : Indicates the digit number below the decimal point. EU at 100% = 100 EU at 0% = 0 Units Index = kPa (1133) Decimal = 2 W 54 LIN_TYPE Select either No Linearization or Square root as a setting of the output range. 0 = No Linearization : Provides an output value scaled according to the PV_RANGE and SCALE range settings. (To use Direct with FF, set the same value for PV_RANGE and SCALE.) 10 = Square root : Provides a square root output computed for the value scaled according to the PV_RANGE and SCALE range settings. 0 W

<10. Parameter Summary>

10-5 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 5. AI1 block (continued) 55 FLOW_ CONSTANT Indicates the flow coefficient, which shows the correlation between the flow rate value and square root value of the differential pressure. 1.0 W 56 LOW_CUTOFF Specifies the low cut value. The unit is subject to SCALE:Units Index. 10 W 57 CAL_CMD Specifies the calibration method. 0 = CAL_NONE : Initial state in which calibration is not performed 1 = CAL_LOW : Applies an actual input and adjusts the lower limit using the value specified in CAL_ POINT_LO. 2 = CAL_HIGH : Applies an actual input and adjusts the higher limit using the value specified in CAL_ POINT_HI. 5 = CAL_CLEAR : Clears the adjustment variable. 0 (reading value is always 0) W 58 CAL_STATUS Indicates the calibration status. 0 = CAL_NONE : Start-up and default value 1 = CAL_SUCCESS : Indicates that calibration was successful. 7 = CAL_BAD_TRIM_POINT : Indicates this status when the adjustment variable is outside of range. --- R 59 CAL_POINT_HI Specifies the higher limit adjustment variable for adjustment between two points. --- W 60 CAL_POINT_LO Specifies the lower limit adjustment variable for the adjustment between two points. --- W 61 CAL_MIN_SPAN Indicates the minimum span of the adjustment variable. --- R 104 EXTERNAL_ ZERO_TRIM Allows performing external zero adjustment. (Trim on, Trim off) Trim on W 105 LOWCUT_MODE Specifies the low cut mode. (Linear, Zero) Linear W 106 H/L_SWAP Allows performing reverse connection of the impulse line. (NORMAL, REVERSE : reverse connection) Used when the lower pressure side and higher pressure side of the impulse line were connected wrongly when installing the pressure transmitter. Normal W 107 T_ZERO_CMP Parameter to select the temperature zero shift compensation mode 0 = OFF : Does not perform temperature zero shift compensation. 1 = ON : Performs temperature zero shift compensation. Off w 108 TEMP_ZERO Parameter to set the temperature gradient value for the temperature zero shift compensation 0 w 109 TEMP_SELECT Parameter to select the temperature (amplifier-side / capsule-side) used for the temperature zero shift compensation. 0 = AMP TEMP : the value of the amplifier-side temperature sensor is used. 1 = CAP TEMP : the value of the capsule-side temperature sensor is used. 1 w

<10. Parameter Summary>

10-6 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 6. AI2 block 1 PV AI2 is a static pressure output object. Indicates the primary analog value (or corresponding process value) and status used to execute this function. Allows updating data by specifying this for the Concentrator object. 1. Value: output value of Al object 2. Status: Specify output status of Al object. --- W 2 MODE A universal parameter to indicate the block’s operation status. O/S, Auto, and Man can be selected. 1. Target : Specify Al object mode. 2. Actual : Indicates current mode of Al object. 3. Permitted : Indicates the mode selected by Target of Al object. 4. Normal : Indicate normal status mode of Al object. 1.Target = O/S 2.Actual = O/S 3.Permitted = O/S 4.Normal = O/S W 3 CONC_OID Indicates the Concentrator object value that corresponds to the data update of the PV value. 3 R 4 SCALE Allows specifying the upper or lower limit for the PV scaling, unit code, etc. 1. EU at 100% : Indicate the upper limit of the PV value. 2. EU at 0% : Indicate the lower limit of the PV value. 3. Units Index : Indicate the setting unit used for the PV value. 4. Decimal : Indicate the digit number below the decimal point displayed in the LCD indicator. 1. EU at 100% = 100 2. EU at 0% = 0 3. Units Index = % 4. Decimal = 2 W 26 TAG_DESC A universal parameter to store the comment that describes the tag. AI2: Static Pressure W 27 PV_FTIME Allows adjusting the time constant for filtering the PV value. Setting unit: Second. This is enabled for the Continuous mode. 0 sec W 28 SIMULATE_ SWITCH A simulation function switch for the AI object test (Disable, Enable) Disable W 29 TRANSDUCER_ VALUE When SIMULATE_SWITCH is set to Disable, this value is used as the input value for the AI object. --- R 30 SIMULATE_ VALUE When SIMULATE_SWITCH is set to Enable, this value is used as the input value for the AI object. The input value can be changed. --- W 51 UPPER_LIM Indicates the upper limit (URL) for the pressure. --- R 52 LOWER_LIM Indicates the lower limit (LRL) for the pressure. --- R 53 PV_RANGE Sets the measurement range. 1. EU at 100% : Indicates input value of the upper limit. 2. EU at 0% : Indicates input value of the lower limit. 3. Units Index : Indicates the units of the measurement range. 4. Decimal : Indicates the digit number below the decimal point. 1. EU at 100% = 25000.000000 EU at 0% = 0 Units Index = kPa Decimal = 2 W

<10. Parameter Summary>

10-7 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 6. AI2 block (continued) 54 LIN_TYPE Select either No Linearization or Square root as a setting of the output range. 0 = No Linearization : Provides an output value scaled according to the PV_RANGE and SCALE range settings. (To use Direct with FF, set the same value for PV_RANGE and SCALE.) 10 = Square root : Provides a square root output computed for the value scaled according to the PV_RANGE and SCALE range settings. 0 W 55 FLOW_ CONSTANT Indicates the flow coefficient, which shows the correlation between the flow rate value and square root value of the pressure. 1.0 W 56 LOW_CUTOFF Specifies the low cut value. The unit is subject to SCALE : Units index. 10 W 57 CAL_CMD Specifies the calibration method. 0 = CAL_NONE : Initial state in which calibration is not performed 1 = CAL_LOW : Applies an actual input and adjusts the lower limit using the value specified in CAL_ POINT_LO. 2 = CAL_HIGH : Applies an actual input and adjusts the higher limit using the value specified in CAL_ POINT_HI. 5 = CAL_CLEAR : Clears the adjustment variable. 0 (reading value is always 0) W 58 CAL_STATUS Indicates the calibration status. 0 = CAL_NONE : Start-up and default value 1 = CAL_SUCCESS : Indicates that calibration was successful. 7 = CAL_BAD_TRIM_POINT : Indicates this status when the adjustment variable is outside of range. R 59 CAL_POINT_HI Specifies the higher limit adjustment variable for adjustment between two points. --- W 60 CAL_POINT_LO Specifies the lower limit adjustment variable for the adjustment between two points. --- W 61 CAL_MIN_SPAN Indicates the minimum span of the adjustment variable. --- R 102 SP_VALUE_TYPE Selects the gauge pressure or the absolute pressure. Abs W 103 SP_SELECT Parameter to select the High-side pressure or the Low- side pressure as the static pressure output. 0 = High : Displays the H-side pressure as the static pressure 1 = Low : Displays the L-side pressure as the static pressure High W

<10. Parameter Summary>

10-8 IM 01C27F01-01EN Object ID Attribute ID Label Description Default value Handling 7. AI3 block 1 PV Al3 is a temperature pressure output object. Indicates the primary analog value (or corresponding process value) and status used to execute this function. Allows updating data by specifying this for the Concentrator object. 1. Value: output value of Al object 2. Status: Specify output status of Al object. 1. Value = --- 2. Status = --- W 2 MODE A universal parameter to indicate the block’s operation status. O/S, Auto, and Man can be selected. 1. Target : Specify Al object mode. 2. Actual : Indicates current mode of Al object. 3. Permitted : Indicates the mode selected by Target of Al object. 4. Normal : Indicate normal status mode of Al object. 1. Target = O/S 2. Actual = O/S 3. Permitted = O/S 4. Normal = O/S W 3 CONC_OID Indicates the Concentrator object value that corresponds to the data update of the PV value. 3 R 4 SCALE Allows specifying the upper or lower limit for the PV scaling, unit code, etc. 1. EU at 100% : Indicate the upper limit of the PV value. 2. EU at 0% : Indicate the lower limit of the PV value. 3. Units Index : Indicate the setting unit used for the PV value. 4. Decimal : Indicate the digit number below the decimal point displayed in the LCD indicator. 1. EU at 100% = 100 2. EU at 0% = 0 3. Units Index = % 4. Decimal = 2 W 26 TAG_DESC A universal parameter to store the comment that describes the tag AI3: Capsule temperature W 27 PV_FTIME Allows adjusting the time constant for filtering the PV value. Setting unit: Second. This is enabled for the Continuous mode. 0 sec W 28 SIMULATE_ SWITCH A simulation function switch for the AI object test (Disable, Enable) Disable W 29 TRANSDUCER_ VALUE When SIMULATE_SWITCH is set to Disable, this value is used as the input value for the AI object. --- R 30 SIMULATE_ VALUE When SIMULATE_SWITCH is set to Enable, this value is used as the input value for the AI object. The input value can be changed. --- W 53 SENSOR_RANGE Parameter to nondimensionalize the sensor output value. The temperature unit can selects from K, degC, and degF. 1. EU at 100% : Indicates input value of the upper limit. 2. EU at 0% : Indicates input value of the lower limit. 3. Units Index : Indicates the units of the measurement range. 4. Decimal : Indicates the digit number below the decimal point. 1. EU at 100% = 130 2. EU at 0% = -50 3. Units Index = deg C 4. Decimal = 0 W 102 TERTIARY_ VALUE_SEL Specifies either the capsule temperature or amplifier temperature as the output value. (CAP, AMP) CAP W (Note) Handling: R=Read only, W=Read & Write (Note) “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off specification) according to NAMUR NE107*. * NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”

<10. Parameter Summary>

10-9 IM 01C27F01-01EN Table 10.2 DIAG_STATUS_DETAIL[0] No Bit DIAG_STATUS_DETAIL Description DIAG_STATUS assignment bit NAMUR DiagnosticDetail_1 1 31 FC_SENSOR_FAIL C sensor frequency error Bit26 F 2 30 FR_SENSOR_FAIL R sensor frequency error Bit26 F 3 29 CAP_T_SENSOR_FAIL Capsule temperature sensor failure Bit26 F 4 28 CAP_EEPROM_FAIL Capsule EEPROM failure Bit26 F 5 27 CAP_EEP_IRREGULAR CAP EEPROM version not correct Bit26 F 6 26 AMP_T_SENSOR_FAIL Amplifier temperature sensor failure Bit27 F 7 25 AMP_EEPROM_FAIL Amplifier EEPROM failure Bit27 F 8 24 AMP_EEP_IRREGULAR AMP EEPROM version not correct Bit27 F 9 23 AMP_F1_ERROR F1 error Bit27 F 10 22 G_A_COMM_FAIL G/A failure Bit27 F 11 21 FC_UNOSC_FAIL C sensor oscillation stop failure Bit26 F 12 20 FC_DELTA_T_FAIL C-side deltaT circuit failure Bit27 F 13 19 FR_DELTA_T_FAIL R-side deltaT circuit failure Bit27 F 14 18 WL_AD_FAIL Battery voltage not detected (AMP failure) Bit27 F 15 17 FR_UNOSC_FAIL R sensor oscillation stop failure Bit26 F 17 15 DP_OUTSIDE_LIMIT Pressure outside of specified range Bit23 C 18 14 SP_OUTSIDE_LIMIT Static pressure outside of specified range Bit23 C 19 13 CAPT_OUTSIDE_LIMIT Capsule temperature outside of specified range Bit23 C 20 12 AMPT_OUTSIDE_LIMIT Amplifier temperature outside of specified range Bit23 C 22 7 DP_OUTSIDE_RANGE Input pressure setting outside of range Bit22 O 23 6 SP_OUTSIDE_RANGE Static pressure setting outside of range Bit22 O DiagnosticDetail_2 24 31 AI1_OUT_OF_SERVICE AI1 O/S mode Bit24 C 25 30 AI2_OUT_OF_SERVICE AI2 O/S mode Bit24 C 26 29 AI3_OUT_OF_SERVICE AI3 O/S mode Bit24 C 27 28 AI1_SIMULATION_ACTIVE AI1 simulation mode Bit17 C 28 27 AI2_SIMULATION_ACTIVE AI2 simulation mode Bit17 C 29 26 AI3_SIMULATION_ACTIVE AI3 simulation mode Bit17 C 33 20 DP_TRIM_SPAN_OUTSIDE Pressure span adjustment variable outside of range Bit25 C 34 19 DP_TRIM_ZERO_OUTSIDE Pressure zero adjustment variable outside of range Bit25 C 38 15 SP_TRIM_SPAN_OUTSIDE Static pressure span adjustment variable outside of range Bit25 C 39 14 SP_TRIM_ZERO_OUTSIDE Static pressure zero adjustment variable outside of range Bit25 C 40 13 WL_LOWBAT_ALM Low battery Bit19 M 41 10 WL_DEEPSLP_ALM Deep sleep due to low battery Bit20 M 42 8 LCD_OUTSIDE_LIMIT LCD display outside of specified range Bit25 C F1001.ai AI algoritm MODE Target from operator from operator from operator from transducer SIMULATE On Off AI algorithm Linearization scaling, filter Alert report HiHi etc PV Auto O/S Man Publish Value & Status PV PV Value & Status Value & Status Value & Status Mode and PV.Status handling SWITCH SIMULATE _VALUE Figure 10.1 Example schema of analog input object

<11. General Specifications>

11-1 IM 01C27F01-01EN 11. General Specifications 11.1 Standard Specifications Communication protocol: ISA100.11a protocol Data rate: 250 kbps Frequency: 2400 - 2483.5 MHz license free ISM band Radio security: AES 128 bit codified RF Transmitter power: Max. 11.6 dBm (fixed) Antenna: +2 dBi Omni directional monopole type Span and range limits: (For EJX510B, values are in absolute and lower range limits are 0.) T01E.ai Span Span Range Range Range Range Span –1 to 20 1 to 50 –1 to 100 2 to 100 0.4 to 20 145 to 7200 10 to 500 8 to 200 kPa –0.1 to 10 –0.1 to 2 0.04 to 2 –100 to 200 kPa –14.5 to 1450 0.2 to 10 1.16 to 29 –14.5 to 29 5.8 to 290 –14.5 to 290 29 to 1450 Span –1 to 2 10 to 500 –1 to 500 –14.5 to 7200 –0.1 to 50 –1 to 500 2 to 100 –1 to 2 0.08 to 2 0.4 to 20 –1 to 20 –1 to 100 A D 0.08 to 2 C B kgf/cm2 (/D4) MPa Measurement Span/Range psi (/D1) bar (/D3) Performance specifications: Refer to GS 01C27F01-01EN. Output: Wireless (ISA100.11a protocol) 2.4GHz signal Update Time: Measurement mode Pressure Continuous 100 msec Intermittent 1 to 3600 sec selectable If the update time is set at one second, the transmitter shifts to the continuous mode. Zero Adjustment Limits: Zero can be fully elevated or suppressed, within the lower and upper range limits of the capsule. External Zero Adjustment: External zero is continuously adjustable with 0.01% incremental resolution of span. Re-range can be done locally using the digital indicator with range-setting switch. Integral Indicator (LCD display): 5-digit numerical display, 6-digit unit display and bar graph. The indicator is configurable to display one or up to two of the following variables periodically.; Pressure and temperature. Burst Pressure: A, B and C capsule: 30MPa D capsule: 132MPa Self Diagnostics: Capsule failure, amplifier failure, configuration error, battery alarm, wireless communication alarm, and over-range error for process variables. Ambient Temperature Limits: -40 to 85ºC(-40 to 185°F) -30 to 80ºC(-22 to 176°F) LCD visible range Process Temperature Limits: -40 to 120ºC(-40 to 248°F) Ambient Humidity Limits: 0 to 100% RH

<11. General Specifications>

11-2 IM 01C27F01-01EN Working Pressure Limits (Silicone oil): Maximum Pressure Limits Pressure Capsule EJX510B EJX530B A 200 kPa abs (29 psia) 200 kPa (29 psig) Bi 2 MPa abs (290 psia) 2 MPa (290 psig) C 10 MPa abs (1450 psia) 10 MPa (1450 psig) D 50 MPa abs (7200 psia) 50 MPa (7200 psig) Minimum Pressure Limit See graph below -40 (-40) 0 (32) 40 (104) 80 (176) 120 (248) 0.1(0.75) 0.13(1) 1(7.5) 100(750) 10(75) 2.7(20) 0.01(0.075) 0.013(0.1) 85 (185) (mmHg abs) Working pressure kPa abs Applicable range Process temperature °C ( °F) F01E.ai Atmospheric pressure -40 (-40) 0 (32) 40 (104) 80 (176) 120 (248) 1(0.14) 2.7(0.38) 10(1.4) (psia) 100(14.5) Process temperature °C ( °F) Working pressure kPa abs Applicable range F02E.ai Maximum Over Pressure Pressure Capsule EJX510B EJX530B A and B 4 MPa abs (580 psia) 4 MPa (580 psig) C 20 MPa abs (2900 psia) 20 MPa (2900 psig) D 75 MPa abs (10800 psia) 75 MPa (10800 psig) Connections: Refer to “MODEL AND SUFFIX CODES.” Wetted Parts Materials: Diaphragm, Process Connector Refer to “MODEL AND SUFFIX CODES.” Non-wetted Parts Materials: Housing Low copper cast aluminum alloy with polyurethane, mint-green paint (Munsell 5.6BG 3.3/2.9 or its equivalent) Degrees of Protection IP66/IP67, NEMA4X Pipe Polypropylene Cover O-rings Buna-N Name plate and tag 304 SST tag plate wired onto transmitter Fill Fluid Silicone, fluorinated oil (optional) Weight: Capsule A, B and C: 3.2kg (7.1 lb) * Capsule D: 3.4kg (7.4 lb) * *: Without battery pack and mounting bracket.

<11. General Specifications>

11-3 IM 01C27F01-01EN 11.2 Model and Suffix Codes T03E.ai Model Description Suffix Codes 304 SST 2-inch pipe mounting None Absolute pressure transmitter Gauge pressure transmitter Wireless communication (ISA100.11a protocol) 8 to 200 kPa (1.16 to 29 psi) 0.04 to 2 MPa (5.8 to 290 psi) 0.2 to 10 MPa (29 to 1450 psi) 1 to 50 MPa (145 to 7200 psi) / Optional specification Always 0 Cast aluminum alloy No electrical connection Process connection Diaphragm 316L SST# Hastelloy C-276 *1# Hastelloy C-276 *1# Hastelloy C-276 *1# 1/2 NPT female 1/2 NPT male G1/2 DIN 16 288 male *2 M20×1.5 DIN 16 288 male *2 Digital indicator Measurement span (Capsule) Wetted parts material *3 EJX510B EJX530B Process connections Mounting bracket Electrical connection Optional code Integral indicator Output signal Amplifier housing — Always N — · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · -L · · · · · · · · · · · · · · · · · · · · · · A · · · · · · · · · · · · · · · · · · · · · B · · · · · · · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · · · · · · · D · · · · · · · · · · · · · · · · · · · · · 4 · · · · · · · · · · · · · · · · · 7 · · · · · · · · · · · · · · · · · 8 · · · · · · · · · · · · · · · · · 9 · · · · · · · · · · · · · · · · · N · · · · · · · · · · · · · · · -0 · · · · · · · · · · · · · D · · · · · · · F · · · · · · N · · · · · · 7 · · · · · · · · · · · · J · · · · · · · · · S · · · · · · · · · · · · · · · · · · H · · · · · · · · · · · · · · · · · · ► The “►” marks indicates the most typical selection for each specification. Example: EJX530B-LAS4N-07JNN/o. *1: Hastelloy C-276 or ASTM N10276. *2: Not applicable for combination of capsule code D and wetted parts material code H. *3: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user’s process fluids. Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material. The ‘#’ marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details. 11.3 OPTIONAL SPECIFICATIONS  OPTIONAL SPECIFICATIONS (For Explosion Protected type) Approvals under pending Item Description Code Factory Mutual (FM) FM Intrinsically safe Approval Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2, Groups F & G, and Class III, Division 1, Class I, Zone 2, Group IIC, in Hazardous Locations FS17 CENELEC ATEX CENELEC ATEX (KEMA) Intrinsically safe Approval — Canadian Standards Association (CSA) CSA Intrinsically safe Approval [For CSA C22.2] Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups F & G, Class III, Division 1 [For CSA E60079] Ex ia II C T4 CS17 IECEx Scheme IECEx Intrinsically safe Approval —

<11. General Specifications>

11-4 IM 01C27F01-01EN  OPTIONAL SPECIFICATIONS (See Table for Span and Range Limits.) Nitrogen(N2) Gas or Water *8 Retention time: one minute T04E.ai Degrease cleansing treatment Degrease cleansing treatment with fluorinated oilfilled capsule. Operating temperature –20 to 80°C (–4 to 176°F) Fluorinated oil filled in capsule Operating temperature –20 to 80°C (–4 to 176°F) P calibration (psi unit) bar calibration (bar unit) M calibration (kgf/cm2 unit) Process Connector Test Pressure: 200 kPa (29 psi) *4 Test Pressure: 2 MPa (290 psi) *5 Test Pressure: 10 MPa (1450 psi) *6 Test Pressure: 50 MPa (7200 psi) *7 Description Code K1 K2 K3 D1 D3 D4 M15 T05 T06 T07 T08 Item Oil-prohibited use *10 Capsule fill fluid Calibration units *2 Material certificate*3 PED 97/23/EC Category III, Module H, Type of Equipment: Pressure Accessory-Vessel, Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2 PE3 European Pressure Equipment Directive *11 Pressure test /Leak test certificate *9 Inside of isolating diaphragms (fill fluid side) are gold plated, effective for hydrogen permeation. A1 Gold-plated diaphragm *10 Painting Color change Coating change Amplifier cover only Anti-corrosion coating *1 P X2 *1: Not applicable with color change option. *2: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1, D3, and D4. *3: Material traceability certification, per EN 10204 3.1 B. *4: Applicable for capsule code A. *5: Applicable for capsule code B. *6: Applicable for capsule code C. *7: Applicable for capsule code D. *8: Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2). *9: The unit on the certificate is always kPa/MPa regardless of selection of option code D1, D3 and D4. *10: Applicable for wetted parts material code S. *11: Applicable for measurement span code D. If compliance with category III is needed, specify this option code.

<11. General Specifications>

11-5 IM 01C27F01-01EN 11.4 Dimensions Unit: mm (approx. inch) 72 (2.83) 282 (11.10) 162 (6.38) 202 (7.95) 322 (12.68) 140 (5.51) 82*4 (3.23) 12*3 (0.47) 94*2 (3.70) 64 (2.52) 191 (7.52) 199 (7.83) 39 (1.54) 24 (0.94) Ø110 (4.33) Open to atmosphere*1 Mounting bracket (Optional) Integral indicator 2-inch pipe (O. D. 60 mm)  Process connections code 7  Process connections code 4  Process connections code 8 and 9 193 (7.60) *1: Applicable for EJX530B Measurement span code A, B, and C. *2: 92 mm (3.62 inch) for Measurement span code D. *3: 11 mm (0.43 inch) for Measurement span code D. *4: 80 mm (3.15 inch) for Measurement span code D. Zero adjustment Ground terminal 209 (8.23) ) 9 7 . 0 ( 0 2 ) 0 2 . 0 ( 5 ø6 (0.24) F03E.ai  Infrared Configuration F04E.ai Infrared port