Pilot Communications EV Plus+ Quick Installation Manual
Text of Pilot Communications EV Plus+ Quick Installation Manual
17/01/2020 / DC1 / Version2
Tools required
#
Name
Remark
1
Philips screwdriver
Electric with bit preferred
2
Hex (M5) screwdriver
Electric with bit preferred
3
Level
–
4
Stainless steel anchors
Size M10
5
Stainless steel bolts
M10 to fit the anchors
6
Drill
When the anchors are not pre-inserted
7
63A Type C Circuit Breaker
–
8
5 core 6mm2 cable
Length as required
2
+44 (0) 1606 59 66 22
17/01/2020 / DC1 / Version2 This type of installation requires an electrical background.
When unpacking contents of the kit, it is crucial to perform a visual check to
confirm that none of the parts are damaged or broken.
Prior to installation, make sure to disconnect the main circuit breaker (CB).
Locate the serial number (S/N) of the device on the stand and confirm that the same
serial number is configured in the Chargepoint management system with Pilot
17/01/2020 / DC1 / Version2 Make sure to always follow your current IET Wiring regulations.
The Pilot EV Plus+ installation should only be carried out by a certified installer.
The below instructions are a guideline and provided for reference only. You are solely
responsible for following all applicable electrical safety procedures, codes, methods,
and materials provided as per the instructions below.
Verify external power cables that are visible from bene
17/01/2020 / DC1 / Version2 Using the Hex screwdriver,
unfasten the 10 screws to
dismantle the access panel.
Dismantle the access panel
1
www.thepilotgroup.co.uk
17/01/2020 / DC1 / Version2 Place the stand on a flat concrete surface with pre-inserted stainless-
steel anchors. Using the 4 bolts, tighten the stand.
Assemble the stand
2
Ensure that the stand is aligned straight.
6
+44 (0) 1606 59 66 22
17/01/2020 / DC1 / Version2 Connect the cables according to the diagram:
L1 = Brown
L2 = Black
L3 = Grey
N = Blue
PE Earth \ PE \ Ground = Yellow Green
Make sure to perform the appropriate PE connection test based on
the current edition of the IET Wiring regulations.
Verify that all the circuit breakers (CB) are turned ON (Switch I).
Connect the cables
3
!
www.thepilotgroup.co.uk
17/01/2020 / DC1 / Version2 Using the Hex screwdriver, fasten the 10 screws to assemble the
access panel.
Assemble the access panel
4
8
+44 (0) 1606 59 66 22
17/01/2020 / DC1 / Version2 Using the Phillips screwdriver
fasten the 4 screws and secure
the base (two parts).
Secure the base cover
5
Make sure that the main circuit breaker (CB) meets with the safety
requirements.
!
www.thepilotgroup.co.uk
17/01/2020 / DC1 / Version2 Switch on the main CB - Circuit Breaker (Switch I).
Make sure that both the Pilot EV Plus+ screen and VPOS Touch device
are turned on and functional in the idle mode.
Power up the device
6
10
+44 (0) 1606 59 66 22
www.thepilotgroup.co.uk +44 (0) 1606 59 66 22
Pilot Group Limited, 15 Carnarvon Street
Manchester M3 1HJ
As a privately-owned business that has traded internationally since 1992 from our base in Manchester, we believe in working
closely with our customers to form long lasting and mutually beneficial partnerships.
At Pilot Group we believe in using technology to make the places we live and work SMART, SAFE and SUSTAINABLE.
At Pilot Group we supply