Ei Electronics Ei2110 Contains vital information on unit operation and installation. Read and retain carefully.
If you are just installing this unit this leaflet MUST be given to the householder.
Model: Ei2110
INSTALLER INSTRUCTIONS
MULTI-SENSOR FIRE ALARM
with Rechargeable Lithium Cell Back-up
230V~
B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 3:46 PM Page 1
Ei Electronics Ei2110 1. QUICK GUIDE
1.1 INSTALLATION GUIDE
1.2 ALARM REMOVAL
2. MULTI-SENSOR FIRE ALARM FEATURES
3. HOW MANY ALARMS TO INSTALL
3.1 CATEGORIES OF SYSTEM
3.2 SELECTING ALARM TYPE
3.3 GRADE D, E & F SYSTEMS
4. POSITIONING ALARMS
4.1 LOCATIONS TO AVOID
5. INSTALLATION
5.1 MOUNTING & WIRING ALARMS
5.2 INTERCONNECTING ALARMS
6. ACCESSORIES
CONTENTS
B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 3:46 PM Page 2
Ei Electronics Ei2110 INSTALL IN THE CENTRE OF CEILING AT LEAST 300mm FROM
LIGHT FITTINGS & WALLS
ENSURE MAINS POWER IS CORRECTLY CONNECTED TO L & N
TERMINALS ON ALL INTERCONNECTED ALARMS - OTHERWISE
UNITS WILL BE DAMAGED
DO NOT FIT ACTUAL ALARMS UNTIL ALL BUILDING WORK IS
COMPLETED TO AVOID CONTAMINATION. AFTER CHECKING
OPERATION, COVER ALARMS WITH DUST COVER UNTIL
REQUIRED FOR USE
DISCONNECT THE ALARMS BEFORE APPLYING HIGH VOLTAGE
TO WIRING (FOR INSULATION TESTS)
DO NOT ATT
1.1 Installation Guide
GREEN MAINS
LIGHT
AS THE TAMPER-PROOF CATCH ENGAGES. SWITCH ON MAINS
PRESS AND HOLD THE TEST BUTTON ON THE ALARM. CHECK
THE ALARM AND ANY INTERCONNECTED UNITS SOUND.
DECIDE ON CORRECT POSITION
B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 3:46 PM Page 4
1.2 Alarm Removal
LOCATE REMOVAL SLOT
LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM.
THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW.
INSERT SCREWDRIVER
INSERT A FLAT-BLADED SCREWDRIVER HORIZONTALLY
ABOUT 10mm INTO THE CENTRE OF THE REMOVAL SLOT
SLIDE ALARM OFF BASE
WITH THE SCREWDRIVER STILL INSERTED, PUSH THE LOWER
HALF OF THE ALARM AWAY FROM THE SCREWDRIVER, IN THE
DIRECTION OF THE ARROW ON THE COVER
HOLD THE LOWER HALF OF THE ALARM AND REMOVE FROM
THE
Ei Electronics Ei2110 2. MULTI-SENSOR FIRE ALARM FEATURES
The state of the art EI2110 Multi-Sensor Fire Alarm, with its Heat enhanced Optical
Smoke Sensor, has a significantly improved performance as described below.
1. Faster Response to a wider range of fires.
The combination of the ultra fast temperature sensing thermistor and the high
performance optical sensor within the unit, enhances the fire sensing performance
such that the unit detects all the 7 different Test Fires (
4. Replace Alarm Indicator.
If the optical sensor chamber becomes very heavily contaminated, the amber fault
light will flash once every 40 seconds to inform the user. Action can then be taken to
replace the unit, long before the contamination causes nuisance alarms.
5. Alarm Memory.
After a the unit has gone into alarm, the red alarm light will flash twice (1 second apart)
every 40 seconds to indicate that the unit has alarmed in the previous 24 hours.
The Multi-Sensor Alarm can be installed for superior performance anywhere the
regulations specify an Optical Smoke Alarm or an Ionisation Smoke Alarm.
(The Ei2110 Multi-Sensor Fire Alarm can also be used and interconnected with an
Ei166RC Optical Smoke Alarm or an Ei161RC Ionisation Smoke Alarm if necessary).
The advice here follows the guidance in British Standard BS 5839-Part 6:2004 in
general (for further information see the BS standard itself).
The mai
It is therefore recommended that a Fire Risk Assessment is undertaken. The Risk
Assessment would be based on a combination of probabilities:
- fire occurring
- injury or death to occupant
- system operating correctly with a fire
- early detection and warning to occupants in the event of a fire.
The greater the risks, the more comprehensive and reliable systems are needed.
3.1 Categories of System
There are three Categories of LD systems for Life protection
for existing dwellings
MINIMUM PROTECTION
LD3
Minimum Protection LD3: Alarms in all hallways,
stairways and circulation areas that form part of the
escape routes from the dwelling.
Multi Storey Dwelling LD3
Living
Room
Bedroom
Bathroom
Kitchen
Bedroom
Shower
Garage
Multi-Sensor Fire Alarms located:
on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
(apart from toilets & bathrooms )
Bedroom
Bedroom
Bedroom
Kitche
Ei Electronics Ei2110 Additional Protection LD2: As LD3, but in addition
alarms in all rooms or areas that present a high fire
risk to occupants.
Heat Alarms located in:
(Heat Alarms must be within 5.3m of potential fire
sources)
each Kitchen
Multi-Sensor Fire Alarms or Heat Alarms located in:
each Living room (i.e. most frequently used
daytime room)
Multi-Sensor Fire Alarms located:
on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
(ap
for dwellings where occupants may be at high risk (e.g. elderly)
OPTIMUM PROTECTION
LD1
Optimum Protection LD1: As LD2, but in addition
alarms should be located in all rooms and other areas
of the dwelling. (apart from toilets or bathrooms)
Multi Storey Dwelling LD1
Living
Room
Bedroom
Bathroom
Kitchen
Bedroom
Shower
Garage
Bedroom
Bedroom
Bedroom
Kitchen / Dining Room
Living Room
Bathroom
Single Storey Dwelling LD1
Heat Alarm
do not fit alarm
Multi-Se
Ei Electronics Smoke Alarm Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated |
|---|---|---|---|---|---|---|
Ei 3100RF |
PDF User Manual (@M9DU43), Ei Electronics Ei 3100RF Smoke Alarm (22-07-2026) |
24 | 0.48 Mb | 1293 | 233 | 22-07-2026 |
Ei 225E |
Smoke Alarm #RD2744 |
6 | 0.14 Mb | 274 | 47 | 15-04-2026 |
Ei 261D |
User Guide: Ei Electronics Ei 261D (12R6M2, Upd.11-10-2026) |
3 | 0.45 Mb | 134 | 26 | 11-10-2026 |
Ei204 |
Ei204 (Smoke Alarm ePDF Guide, #K41C8F) |
6 | 0.12 Mb | 723 | 145 | 17-09-2026 |
Ei181 |
Smoke Alarm #N5V829 |
2 | 0.11 Mb | 1013 | 152 | 07-09-2026 |
Ei2110 |
Ei Electronics Smoke Alarm Installer's instructions (File: PDF, 28-09-2026) |
28 | 0.48 Mb | 802 | 145 | 28-09-2026 |
Ei 405 |
#UB64PO: Ei 405 Smoke Alarm Technical specifications |
2 | 0.11 Mb | 175 | 27 | 28-05-2026 |
Ei 100R |
PDF User Manual (@8UBT5Y), Ei Electronics Ei 100R Smoke Alarm (18-04-2026) |
2 | 0.11 Mb | 1217 | 256 | 18-04-2026 |
Ei141EK |
Ei141EK (Smoke Alarm ePDF Guide, #HUH89W) |
4 | 1088 | 196 | 26-09-2026 | |
RadioLINK Ei 407 |
RadioLINK Ei 407 (Smoke Alarm ePDF User Guide, #V42BTS) |
2 | 0.06 Mb | 411 | 74 | 27-05-2026 |