Siemens FC72x Quick Reference Manual
Read Online
Read the Siemens FC72x Quick Reference Manual online using the built-in PDF viewer.
Text of the manual
FC72x / FT724
Fire control panel / fire terminal
Quick Reference Guide
IP6
A6V10211094_f_en_--
Building Technologies
2015-12-15
Control Products and Systems
2 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Legal notice
Technical specifications and availability subject to change without notice.
Transmittal, reproduction, dissemination and/or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights created by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2015-12-15
Document ID: A6V10211094_f_en_--
© Siemens Switzerland Ltd, 2009
3 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Table of contents
1
About this document ............................................................................. 5
1.1
Applicable documents ................................................................................. 6
1.2
Download center ......................................................................................... 7
1.3
Technical terms and abbreviations .............................................................. 7
1.4
Revision history .......................................................................................... 7
2
Safety instructions ................................................................................ 8
2.1
Safety regulations for the method of operation ............................................ 9
2.2
Standards and directives complied with......................................................11
2.3
Responsibility of the operator .....................................................................11
3
System overview ................................................................................ 12
3.1
Station overview ........................................................................................14
4
Mounting ........................................................................................... 15
4.1
Mounting instructions .................................................................................16
5
Installation ......................................................................................... 17
5.1
Position of printed circuit boards / components...........................................18
5.2
Power supply - mains voltage connection ...................................................19
5.2.1
Emergency power supply ............................................................21
5.3
Hardware components ...............................................................................22
5.3.1
Periphery board ..........................................................................22
5.3.2
Relay for fault and alarm (RT activation) ......................................24
5.3.3
Monitored outputs for alarm and fault (FT activation) ...................25
5.3.4
Connection of monitored acoustic signal transmitters ..................27
5.3.5
Configurable inputs/outputs and supply voltage Vsys ..................28
5.4
C-NET detector line ...................................................................................31
5.5
Connectable C-NET devices ......................................................................32
5.6
C-NET topology and connection ................................................................36
5.7
Wiring principle behind C-NET devices ......................................................39
5.8
C-WEB network .........................................................................................40
6
Indication and operating elements ........................................................ 43
6.1
Extra indication and operating devices .......................................................45
7
Commissioning .................................................................................. 46
7.1
Activating access level ...............................................................................47
7.1.1
Log in / Change access level.......................................................47
7.2
Auto-configuration of control panels ...........................................................48
7.2.1
Auto-configure line ......................................................................49
7.3
Displaying C-NET devices .........................................................................52
7.4
Entering/Changing customer text ...............................................................54
7.5
Setting the system time ..............................................................................54
7.5.1
Setting time and date ..................................................................54
7.6
Changing access authorization PIN ...........................................................55
7.6.1
PIN administration .......................................................................55
7.7
Restart the station......................................................................................57
4 | 62
8
Testing the installation .........................................................................59
8.1
Checking functions .................................................................................... 59
Glossary .....................................................................................................60
Index .........................................................................................................61
About this document
Applicable documents
1
5 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
1 About this document
Goal and purpose
These brief instructions aim to provide experienced and qualified installation and
operating staff with a guide on how to mount, install, commission and repair the
system.
Scope
These brief instructions are supplements to the documents provided for the
Cerberus PRO FS720 fire detection system and apply for the following products:
●
Fire control panel FC722, FC724
●
FT724 fire terminal
These brief instructions only apply to use with C-NET detector line cable and when
commissioning with auto-configuration. They do not include other applications
and/or components of extended networking.
The information contained in this document is valid for introduction package IP6.
Target groups
The information in this document is intended for the following target groups:
Target group
Activity
Qualification
Installation personnel
●
Assembles and installs the
product components at the place
of installation.
●
Carries out a function check
following installation.
●
Has received specialist training in the
area of building installation technology
or electrical installations.
Operating personnel
●
Carries out procedures to
correctly operate the product.
●
No particular basic training is needed.
●
Has been instructed by the
commissioning personnel.
Source language and reference document
●
The source/original language of this document is German (de).
●
The reference version of this document is the international version in English.
The international version is not localized.
Document identification
The document ID is structured as follows:
ID code
Examples
ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international
A6V10215123_a_de_DE
A6V10215123_a_en_--
A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
About this document
Applicable documents
1
6 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Conventions for text marking
Markups
Special markups are shown in this document as follows:
⊳
Requirement for a behavior instruction
1.
2.
Behavior instruction with at least two operation sequences
–
Version, option, or detailed information for a behavior instruction
⇨
Intermediate result of a behavior instruction
⇨
End result of a behavior instruction
●
Numbered lists and behavior instructions with an operation
sequence
[➙ X]
Reference to a page number
'Text'
Quotation, reproduced identically
Identification of keys
>
Relation sign and for identification between steps in a sequence,
e.g., 'Menu bar' > 'Help' > 'Help topics'
↑ Text
Identification of a glossary entry
Supplementary information and tips
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
1.1
Applicable documents
Document ID
Title
A6V10210355
System description
A6V10210362
Planning
A6V10210390
Mounting / Installation
A6V10210416
Commissioning / Maintenance / Troubleshooting
A6V10210424
Configuration
A6V10229261
List of compatibility
A6V1021 0368
Product data
A6V10211118
Quantities Tool
About this document
Download center
1
7 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
1.2
Download center
You can download various types of documents, such as data sheets, installation
instructions, and license texts via the following Internet address:
http://siemens.com/bt/download
κ
Enter the document ID in the 'Find by keyword' input box.
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
1.3
Technical terms and abbreviations
You will find details of technical terms and abbreviations in the 'Glossary' chapter.
1.4
Revision history
The reference document's modification index applies to all languages into which
the reference document is translated.
The first edition of a language version or a country variant may, for example, have
the modification index 'd' instead of 'a' if the reference document already has this
modification index.
The table below shows this document's revision history:
Version
Edition date
Brief description
f
2015-12-15
Edition: Introduction Package IP6
●
Referenced documents updated
●
'Station overview' chapter: Ethernet switch (modular) integrated
●
'C-WEB network' chapter: Data rate changed to 315 kbit/s
●
C-NET detector line updated
e
2014-02-10
Information on voltage ranges revised in the chapter 'Configurable inputs/outputs
and supply voltage Vsys'
d
2013-11-14
Edition: Introduction Package IP5
●
Change to date format according to ISO 8601
●
C-NET devices added: FDCI723, FDM223-Ex, OOH740-A9-Ex, FDCL221-Ex,
FDA221, FDA241, FDM273, FDM243H
●
License key (Sx) replaces license key (Lx)
CPR replaces CPD: The Construction Products Regulation (CPR 305/2011)
replaces the previous Construction Products Directive (CPD 89/106).
New:
●
LED module FTO2008-A1 with 24 red/green and yellow LEDs each
c
2012-06
Edition: Introduction Package IP4
●
C-NET devices updated
b
2010-07
●
Adaptation to MP3.0 XS
●
Adaptation of naming
●
Various minor corrections
a
2009-05
First edition MP1XS
8 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
2 Safety instructions
The safety notices must be observed in order to protect people and property.
The safety notices in this document contain the following elements:
●
Symbol for danger
●
Signal word
●
Nature and origin of the danger
●
Consequences if the danger occurs
●
Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury.
Follow all measures identified by this symbol to avoid injury or death.
Additional danger symbols
These symbols indicate general dangers, the type of danger or possible
consequences, measures and prohibitions, examples of which are shown in the
following table:
General danger
Explosive atmosphere
Voltage/electric shock
Laser light
Battery
Heat
Signal word
The signal word classifies the danger as defined in the following table:
Signal word
Danger level
DANGER
DANGER identifies a dangerous situation, which will result directly in death or
serious injury if you do not avoid this situation.
WARNING
WARNING identifies a dangerous situation, which may result in death or serious
injury if you do not avoid this situation.
CAUTION
CAUTION identifies a dangerous situation, which could result in slight to
moderately serious injury if you do not avoid this situation.
NOTICE
NOTICE identifies possible damage to property that may result from non-
observance.
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Nature and origin of the danger
Consequences if the danger occurs
●
Measures / prohibitions for danger avoidance
Safety regulations for the method of operation
2
9 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
●
Measures / prohibitions for danger avoidance
2.1
Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant
European and international safety standards. Should additional national or local
safety standards or legislation concerning the planning, mounting, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
●
Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
●
Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
●
Lock volt-free areas to prevent them being switched back on again by mistake.
●
Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
●
Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
●
Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
●
Produce earthing as stated in local safety regulations.
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
●
Compliance with the following regulations is required.
●
Specialist electrical engineering knowledge is required for installation.
●
Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation unbeknown to a
layperson.
Safety regulations for the method of operation
2
10 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Mounting, installation, commissioning and maintenance
●
If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
●
When starting the fire control panel ensure that unstable conditions cannot
arise.
●
Ensure that all points listed in the 'Testing the product operability' section below
are observed.
●
You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Testing the product operability
●
Prevent the remote transmission from triggering erroneously.
●
If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
●
The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions must be observed:
–
Use the correct potential for activation; this is generally the potential of the
building installation.
–
Only check controls up to the interface (relay with blocking option).
–
Make sure that only the controls to be tested are activated.
●
Inform people before testing the alarm devices and allow for possible panic
responses.
●
Inform people about any noise or mist which may be produced.
●
Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
●
Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
●
Only use fuses with the specified fuse characteristics.
●
Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by
Siemens.
●
Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrect application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
●
Personal injuries or damage to property caused by improper use and incorrect
application
●
Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
●
Personal injury or damage to property caused by poor maintenance or lack of
maintenance
Standards and directives complied with
2
11 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
2.2
Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens
contact.
2.3
Responsibility of the operator
A fire detection installation is a piece of safety engineering equipment designed to
protect people, buildings and equipment through early detection of fires and
alarming.
The fire detection installation has to be maintained in order to satisfy this
requirement. Within the European Union, the maintenance intervals are defined in
the EN 54 standard and/or are also governed by national and local requirements.
Maintenance is required in order for the fire detection installation to function
correctly. The fire detection installation consists of components the function of
which may be impaired by ambient conditions and aging.
Maintenance of a fire detection installation is governed by the EN54 standard.
Manufacturer's recommendations
The following work should be carried out at regular intervals to maintain the fire
detection system:
●
Visual check for damage on the devices or possible sources of error
●
Quarterly inspection of system parts including test triggering of fire alarm
●
Annual maintenance including inspection work, checking the power supply and
emergency power supply
●
Replacement of batteries by the date stated by the battery manufacturer at the
latest (printed on battery)
●
Keep a logbook to document system messages, isolations and maintenance
work.
The frequency of inspections and service work is dependent on the ambient
conditions.
If using fire detection systems in critical ambient conditions, e.g. in rooms with a
high concentration of dust, high air humidity or large temperature fluctuations,
shorter inspection intervals may be needed.
Responsibility of the operator
3
12 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
3 System overview
The FC720 Cerberus PRO fire control panels can be operated as standalone
panels or networked into a fire detection system. Up to 32 stations (fire control
panels, fire terminals) are networked via the C-WEB/SAFEDLINK system bus. The
Cerberus PRO fire control panels support operation of the C-NET detector line.
1
FC722 or FC724 fire control panel in Comfort housing
2
FC722 fire control panel in the Standard housing
3
FT724 fire terminal
4
Laptop or PC with Cerberus-Engineering-Tool software
5
C-NET detector line
6
Periphery e.g. RT alarm transmission installation or acoustic signal
transmitter etc.
b
e
1
2
3
j
l
n
4
5
6
h
i
u
7
8
9
q
0
#
C
Cerberus
TM
a
b
d
e
1
2
3
n
o
4
5
6
g
h
u
7
8
9
p
q
0
#
C
Cerberus
T M
a
b
d
e
1
2
3
n
o
4
5
6
g
h
u
7
8
9
p
q
0
#
C
Cerberus
T M
a
b
d
e
1
2
3
n
o
4
5
6
g
h
u
7
8
9
p
q
0
#
C
Cerberus
T M
Responsibility of the operator
3
13 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
C-NET detector line
The C-NET is a monitored bus line using 2-wire technology, to which up to 252
devices per loop or 32 devices per stub can be connected. C-NET line devices are
automatic fire detectors, manual call points, I/O components, transponders, and
indication and operating devices such as floor repeater terminals. With the
exception of the FDCIO223 transponder, which requires its own power supply, all
C-NET line devices are also supplied with operating voltage via the C-NET. There
is a line separator integrated in each line device. In the event of a C-NET fault
(short-circuit/wire break), the defective line segment is isolated by two neighboring
line separators. When using a loop, the connected devices remain ready to detect.
With a stub, the faulty line segment is isolated after the line separator. The fault is
displayed on the station.
C-WEB/SAFEDLINK
Up to 32 Cerberus PRO stations can be networked via the C-WEB to form a
system. Redundant operations are guaranteed by the network's ring topology.
Thanks to the C-WEB, system-wide alarming and access to individual fire detection
system devices is possible. There may be a distance of up to 1000 m in the C-
WEB between two stations. At greater distances, special repeaters or even optical
waveguide connections can be used. A second network card can also be fitted for
stricter fail-safe requirements (EN54).
The network connection can also be realized by the Ethernet with limitations.
However this does not satisfy the requirements of EN54.
More details of networking can be found in the system documentation.
14 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
3.1
Station overview
FC722
fire control panel
(2-loop)
FC724
fire control panel
(4-loop)
FT724
fire terminal
Max. C-NET addresses
252 *
504 *
―
Without loop extension
2 loops *
4 loops *
―
With loop extension
4 loops *
8 loops *
―
Supply
Power supply
70/150 W
150 W
optional (70 W)
Batteries (capacity)
max. 2x 26 Ah
max. 2 x 26 Ah
optional (7 Ah)
External DC supply 24 V
―
―
redundant
Operating unit
integrated
integrated
integrated
Inputs and outputs
RT alarm, relay
1
1
―
RT fault, relay
1
1
―
RT alarm monitored
1
1
―
RT fault monitored
1
1
―
Outputs for monitored, acoustic
signal transmitter
1
2
―
Freely configurable
inputs/outputs
8
12
―
Options
Loop extension (C-NET)
max. 1
max. 2
―
Network module (SAFEDLINK)
max. 2
max. 2
max. 2
Ethernet switch (modular)
max. 1
max. 1
external
Repeater (SAFEDLINK)
max. 1*
max. 1*
max. 1*
RS232 / RS485 module
max. 2
max. 2
max. 2
Fire brigade periphery module
[DE]
1
1
―
Event printer
1
1
1
LED module; 24 red/green and
yellow LEDs each
max. 5
max. 5
max. 5
EVAC-NL operating unit [NL]
max. 1
max. 1
max. 1
Sounder module
max. 2
max. 2
―
RT interface [NL]
max. 1
max. 1
―
License keys
max. 1
max. 1
max. 1
Key switch
(Kaba type)
max. 1
max. 1
max. 1
* Note system limits!
The description of system components and options does not form part of these
brief instructions (For detailed information, refer to the system documentation).
[DE] option for Germany [NL] option for the Netherlands
15 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
4 Mounting
Before mounting and installation, check all the fire detection installation
components visually for damage caused by improper transport and handling.
Figure 1: Unpacking and checking
Components with clear signs of damage must not be used in the station or
operated as fire detection installation components. When assembling the station
and its modules, observe national and local standards and requirements. The
following mounting instructions refer to the specifications of the EN 54 standard
and the manufacturer's recommendations. The site chosen to assemble the station
and associated components must match the planning documents for the fire
detection installation.
C
Cerberus
TM
16 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
4.1
Mounting instructions
The station's equipment pack contains an mounting model with the dimensions
needed and details of the mounting points to assist with mounting.
The station must be assembled in a dry, clean and well vented room.
The station must be assembled at a distance of least one door leaf width from the
room's entrance. Select the height of mounting such that the display and optical
indications are approx. 1.6 -1.7m above where the observer stands.
The station and its components should be protected from dampness and interfering
external influences such as dust, great temperature fluctuations and mechanical
stress.
The station must be assembled in a place freely accessible to authorized staff and
the emergency services.
A level, non-vibrating wall surface with load bearing capacity and suitable mounting
materials (e.g. screws and plugs) are needed to secure the station to the wall.
The mounting surface and selected mounting must be suitable for the weight of the
equipped station incl. the batteries used.
The station may only be fitted using the 19" method if using the associated
components.
Mounting is not permitted in rooms with high levels of electromagnetic interference,
e.g. in control rooms or right next to power cables and inductive loads.
WARNING
Electric shock
Mounting and installation work may only be undertaken by qualified staff and
when the system is de-energized.
NOTICE
Damage resulting from electrostatics
Take appropriate EMC protective measures when handling electronics modules.
17 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5 Installation
The following installation instructions refer to the specifications of the EN 54
standard and the manufacturer's recommendations. The installation may only be
undertaken by an electrician. Detailed instructions can be found in the system
documentation.
●
Use a suitable cable, e.g., NYM 3 x 1.5 mm2 (max. 2.5 mm²) or a cable type
with similar performance features to connect the AC voltage from the line
supply.
●
The line voltage fuse must be designed for a current level of 10 A.
●
The mains connection cable must be routed into the control panel housing from
above or from the rear.
●
Provide a suitable mains separator or an appropriately labeled automatic cutout
for the mains voltage connection.
●
The nominal voltage required (AC 230 V or AC 115 V) is stated on the control
panel type plate.
●
Use a separate residual current unit for residual current circuit breakers.
Depending on the installation conditions, voltage surge protection (primary
protection) is required for the mains connection.
Planning and system limits
Before the installation, check whether the system's planning is suitable for the
system limits. This applies e.g. to all technical data and details of cable lengths,
number of line devices, number of networked stations, battery capacity and
compliance with requirements from standards and national guidelines and local
requirements.
Details of planning can be found in the system documentation.
Information about lightning protection
Further information and detailed specifications relating to producing a lightning
protection concept can be found in the relevant literature and associated
standards.
WARNING
High voltage! Danger to life!
Risk of electric shock
●
Mounting and installation work may only be undertaken by qualified staff and
when the system is de-energized.
●
Only use cable openings or the edge protection strips provided to protect
cables.
NOTICE
Overvoltage
Damage possible
●
Observe the nominal voltage required (AC 230 V) as per the control panel
type plate!
●
The fuses used and stated in the factory must not be bypassed or replaced
with any type other than that stated.
●
Take appropriate EMC protective measures when handling electronics
modules.
Position of printed circuit boards / components
5
18 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.1
Position of printed circuit boards / components
Figure 2: Position of components in housing (Standard) for FC722
Figure 3: Position of components in housing (Comfort) for FC722 or FC724
1
Batteries
6
Mains connection terminals (L1,N,PE)
2
Power supply (70 W)
7
Loop extension option (C-NET) 1 x for FC722, 2 x for FC724
3
Power supply (150 W)
8
Shield connection terminal blocks or cable kit option
(communication)
4
Periphery board (2 loops)
9
Space for more options, e.g. fire brigade periphery module
5
Periphery board (2 loops or 4
loops)
10
Type plate
You will find further information on removing the FC722 and FC724 stations and
the housings and options available in the system documentation.
After mounting the type plate must be stuck to the outside of the housing in a
clearly visible location and the mounting date added.
Power supply - mains voltage connection
5
19 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.2
Power supply - mains voltage connection
When supplied from the factory, the power supply's internal cabling is already
connected.
Power units available
24 V DC/2.5 A, power 70 W, max. battery capacity which can be connected 17 Ah
24 V DC/5 A, power 150 W, max. battery capacity which can be connected 45 Ah
Figure 4: Mains connection in Standard and Comfort housings
1
EMC-critical zone (no high-voltage power permitted)
4
Cable strain relief for mains supply line
2
Mains connection from below (not permitted when batteries
are fitted)
5
Mains connection from above
(recommended)
3
Power supply terminals
6
EMC boundary
●
The network cables must be inserted from above.
●
The mains lead must be placed along the left side of the housing (observe
EMC zone boundary).
●
Signal and control lines must only be fed into the housing on the right from
above or from the rear.
●
Batteries must be installed in the correct positions.
●
No cable openings should be made in the base of the housing, unless an
additional empty housing is mounted below the station to accommodate the
batteries.
●
The mains connection voltage needed (230 V AC/115 V AC) can be found on
the station's type plate.
2
3
5
6
1
4
2
3
4
5
1
6
Power supply - mains voltage connection
5
20 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Connecting mains voltage
WARNING
Voltage
Electric shock
●
Before connecting the mains voltage ensure that it is not energized and is
locked to prevent it being activated.
Figure 5: Mains connection for Standard and Comfort housings
1
Mains cable (supplied from above), 3 x 1.5 mm2
e.g. NYM cable type
6
Cable tie
2
Strain relief clamp
PE
Protective conductor (terminal on the left)
3
Ground on the rear panel
N
Neutral conductor (terminal in the middle)
4
Disconnect terminal
L1
External conductor (terminal on the right, with
mains disconnector)
5
Primary cabling for power supply
1.
Lay the mains cable (1) along the left side of the housing.
2.
Insulate the mains cable as needed and connect it to the power supply
terminals (PE, L1, N). Use cable end sleeves for wires.
3.
Fixate the cable with the strain relief clamp (2).
4.
Secure the cable with cable ties (6).
L1
N
PE
4
1
6
3
L1
N
PE
1
2
3
5
5
2
4
Power supply - mains voltage connection
5
21 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.2.1
Emergency power supply
Should the AC mains voltage fail, the emergency power supply will be provided by
the connected batteries with no interruptions. The emergency power bridging time
depends on the control panel's quiescent and alarm current and the battery
capacity used. Once the emergency power bridging time has lapsed, it must be
possible for the external signal transmitters to be activated in the event of an alarm.
This activation must also be ensured at a battery final voltage of DC 21.2 V.
NOTICE
Error during configuration detection
Additional effort for troubleshooting
●
Only connect the battery connection cables (*) once all installation work is
complete because the station will start as soon as the batteries are
connected.
Figure 6: Diagram with battery wiring on 70 W power unit
Emergency power bridging time
Depending on national and local requirements, a bridging time of 72 hours or more
may be needed for the emergency power supply. The battery capacity needed
must be calculated and the calculation checked by measuring the power consumed
during an alarm (with mains voltage deactivated). The Quantities Tool software is
available for calculating the battery capacity.
New batteries / initial commissioning
When using new batteries, they must be charged for at least 24 hours before
commissioning. If the date of manufacture (printed on batteries) is more than nine
months ago, they will need charging for at least 48 hours.
Total discharge
There is no guarantee that totally discharged batteries can be correctly charged
again. Replace batteries that have been totally discharged with new ones. You
may only use the approved battery types for the emergency power supply in fire
detection systems. Also note the details provided by the battery manufacturer.
Akku -
Akku 1
Akku 1
N
22 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.3
Hardware components
5.3.1
Periphery board
Position of connection terminals on periphery board (2-loop) of
FC722 fire control panel
Figure 7: Periphery board (2-loop) for FC722
X1
Connection of power unit
X3
Ribbon cable to PMI & mainboard (operating unit on pivot frame)
X6
Monitored outputs for acoustic signal transmitter, alarm and fault messages
X7
Changeover contacts for RT Alarm and RT Fault (remote transmission)
X8
Configurable inputs/outputs (1-4), supply voltage Vsys 1
X9
Configurable inputs/outputs (5-8), supply voltage Vsys 2
X11
C-NET loop 1 or stub 1+2
X12
C-NET loop 2 or stub 3+4
X400 Ribbon cable peripheral data bus
Fxxx
SMD fuses 1A/T
X15
23 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Position of connection terminals on periphery board (4-loop) of
FC724 fire control panel
Figure 8: Periphery board (4-loop) for FC724
X1
Connection of power unit
X11
C-NET loop 1 or stub 1+2
X3
Ribbon cable to PMI & mainboard (operating unit on pivot
frame)
X12
C-NET loop 2 or stub 3+4
X5
Monitored outputs for acoustic signal transmitter
X15
2 x C-NET loop extension
X6
Monitored outputs for alarm and fault messages
X21
C-NET loop 3 or stub 5+6
X7
Changeover contacts for RT Alarm and RT Fault (remote
transmission)
X22
C-NET loop 4 or stub 7+8
X8/1 Configurable inputs/outputs (1-8), supply voltage Vsys 1
X400
Ribbon cable peripheral data
bus
X8/2 Configurable inputs/outputs (9-16), supply voltage Vsys 2
Fxxx
SMD fuses 1A/T
More details of the periphery board can be found in the 'System documentation'.
X8/2
X8/1
X15
X15
24 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.3.2
Relay for fault and alarm (RT activation)
Assignment of connection terminals on periphery board (identical for FC722 and
FC724). Permitted cable cross-section: 0.2…1.5 mm2.
FC722 and FC724
X7
Designation
Description
6
FAU_NC
Break contact fault (normally closed)
Potential-free
directional contact
Max. 24 V DC/1 A
5
FAU_COM
Center tap fault (common)
4
FAU_NO
Make contact fault (normally open)
3
AL_NC
Break contact alarm (normally closed)
Potential-free
directional contact
Max. DC 24 V / 1 A
2
AL_COM
Center tap alarm (common)
1
AL_NO
Make contact alarm (normally open)
The relays can be used e.g. for non-monitored activation of remote transmission
equipment 'RT' (e.g. phone dialing equipment).
Fault relay (inverse operation)
The fault relay is activated when at least one station fault has been detected. This
relay is activated when the control panel is in idle mode (, NC, inverse operation).
In the event of a fault message, the relay changes the switching condition (to C,
NO). Thanks to inverse operation, a fault message will still be sent in the event of
the station losing all power.
Connection to an external monitoring
input (example)
Connection of external control
voltage e.g. for an acoustic or optical
fault message (example)
Alarm relay
The alarm relay is activated when at least one station alarm message has been
detected.
Example of connection with external signal transmitter, e.g. an optical normal
operation/alarm message display.
Normal operation
Alarm
X7
NO
NO
+
+ Ub (DC)
NO
+ Ub (DC)
25 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.3.3
Monitored outputs for alarm and fault (FT activation)
Connection terminals on periphery board (2-loop) of FC722 and/or periphery board
(4-loop) of FC724.
Permitted cable cross-section: 0.2…1.5 mm2.
FC722
X6
Designation
Description
6
FAU_OUT
Output fault
5
VSYS_O
Supply output for consumer fault
4
AL_OUT-
Alarm output (-)
3
AL_OUT+
Alarm output (+)
2
SOUND1-
Output for acoustic signal transmitter (-)
1
SOUND1+
Output for acoustic signal transmitter (+)
FC724
X6
Designation
Description
4
FAU_OUT
Output fault
3
VSYS_O
Supply output for consumer fault
2
AL_OUT-
Alarm output (-)
1
AL_OUT+
Alarm output (+)
X6
X6
26 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
The outputs can be used e.g. for monitored activation of remote transmission
equipment 'RT' (e.g. phone dialing equipment).
The connection lines are switched with a monitoring resistor (termination resistor).
The resistance value stated corresponds to monitored normal operation. All
resistance values outside this range result in a fault message.
Enabling example for transmitting a
fault message
Termination resistor
R = 1.6 kOhm – 2.3 kOhm
Enabling example for transmitting an
alarm message
Monitoring resistor (R + Ri)
Rges = 2.3 kOhm – 5.5 kOhm
X6
+
X6
AL_OUT-
AL_OUT+
+
27 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.3.4
Connection of monitored acoustic signal transmitters
Assignment of connection terminals on periphery board (2-loop) of FC722 and/or
periphery board (4-loop) of FC724.
Permitted cable cross-section: 0.2…1.5 mm2.
FC722
X6
Designation
Description
6
FAU_OUT
Output fault
5
VSYS_O
Supply output for consumer fault
4
AL_OUT-
Alarm output (-)
3
AL_OUT+
Alarm output (+)
2
SOUND1-
Output for acoustic signal transmitter (-)
Potential-free
directional contact
Max. DC 24 V / 1 A
1
SOUND1+
Output for acoustic signal transmitter (+)
FC724
X5
Designation
Description
4
SOUND2-
Output for acoustic signal transmitter 2 (-)
Monitored/switchin
g positively
Max. DC 24 V / 1 A
3
SOUND2+
Output for acoustic signal transmitter 2 (+)
2
SOUND1-
Output for acoustic signal transmitter 1 (-)
Monitored/switchin
g positively
Max. DC 24 V / 1 A
1
SOUND1+
Output for acoustic signal transmitter 1 (+)
Diagram showing principle
In normal operation, the connection is monitored for wire breaks and short-circuits
on the connection line. A monitoring current flows through the termination resistor
R (2.3 kOhm to 5.5 kOhm). All resistance values outside this range are recognized
as faults. The termination resistor should be connected directly to the connection
terminals of the monitored signal transmitter.
In the event of an alarm (with output activated), the polarity on the connection
terminal is reversed and the blocking diode is switched in the conducting direction.
The external signal transmitter is activated with the output voltage (DC +24 V).
Fx ⇒ SMD fuse 1 A/T (on the periphery board)
R ⇒ termination resistor (coverage area 2.3 kOhm – 5.5 kOhm)
V ⇒ blocking diode type 1N 4xxxx
M ⇒ flow of current in normal operation (monitoring)
A ⇒ flow of current during an alarm
Note the station's total current (e.g. for the 70 W power unit, max. 2.5 A).
X6
X5
+
M
+
+
28 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.3.5
Configurable inputs/outputs and supply voltage Vsys
The assignment of connection terminals on periphery board (2-loop) of FC722 and
periphery board (4-loop) of FC724 is not identical.
Assignment on FC722 periphery board (2-loop)
Permitted cable cross-section: 0.2 to 1.5 mm2.
FC722
X8
Designation
Description
6
GND_01
(–) supply output 1
DC 20 V – DC 30 V/1 A
5
VSYS_01
(+) supply output 1
4
I/O4
Configurable input/output 4
Individual current max.
300 mA
total current max. 1 A
3
I/O3
Configurable input/output 3
2
I/O2
Configurable input/output 2
1
I/O1
Configurable input/output 1
FC722
X9
Designation
Description
6
GND_02
(–) supply output 2
DC 20 V – DC 30 V/ 1 A
5
VSYS_02
(+) supply output 2
4
I/O8
Configurable input/output 8
Individual current max.
300 mA
total current max. 1 A
3
I/O7
Configurable input/output 7
2
I/O6
Configurable input/output 6
1
I/O5
Configurable input/output 5
Each of these freely configurable inputs/outputs can either be configured as an
input or output. The function and external circuit needed depend on the mode of
operation selected.
X8
X9
29 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Example: Principle circuit on I/O 1 (connection 1).
I/O 1 as 'input'
The input can be triggered with a potential-free,
external switching contact. In such cases, the
corresponding input is switched to GND.
Depending on the programming, a permanent or
sensing contact can be connected. The activated
input can be used to program one of the station's
control functions.
I/O 1 as 'output'
Configuration as 'output' allows for the activation of
external devices (e.g. relays) with 'Vsys' voltage
should certain events arise. In such cases, the
corresponding output is switched to GND.
The output's activation condition (e.g. alarm, fault,
isolation etc.) is defined in the customer data
programming.
X8
I/O1
X8
I/O1
30 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Assignment on FC724 periphery board (4-loop)
Permitted cable cross-section: 0.2 to 1.5 mm2.
FC724
X8/1
Designation
Description
8
GND_01
(-) supply output 1
DC 20 V – DC 30 V/ 1 A
7
VSYS_01
(+) supply output 1
6
I/O6
Configurable input/output 6
Individual current max.
300 mA
Total current max. 1 A
5
I/O5
Configurable input/output 5
4
I/O4
Configurable input/output 4
3
I/O3
Configurable input/output 3
2
I/O2
Configurable input/output 2
1
I/O1
Configurable input/output 1
X8/2
Designation
Description
16
GND_02
(-) supply output 2
DC 20 V – DC 30 V/ 1 A
15
VSYS_02
(+) supply output 2
14
I/O12
Configurable input/output 12
Individual current max.
300 mA
Total current max. 1 A
13
I/O11
Configurable input/output 11
12
I/O10
Configurable input/output 10
11
I/O9
Configurable input/output 9
10
I/O8
Configurable input/output 8
9
I/O7
Configurable input/output 7
Example: Principle circuit with I/O 1 (connection 1) and/or I/O 2 (connection 9)
I/O 1 as 'input'
The input can be triggered with a potential-free,
external switching contact. In such cases, the
corresponding input is switched to GND.
Depending on the programming, a permanent or
sensing contact can be connected. The activated
input can be used to program one of the station's
control functions.
I/O 2 as 'output'
Configuration as 'output' allows for the activation of
external devices (e.g. relays) with 'Vsys' voltage
should certain events arise. In such cases, the
corresponding output is switched to GND.
The output's activation condition (e.g. alarm, fault,
isolation etc.) is defined in the customer data
programming.
X8/1
X8/2
X8/1
I/O1
I/O2
X8/2
C-NET detector line
5
31 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.4
C-NET detector line
Up to 252 line devices, such as automatic fire detectors, manual call points,
transponders, and other C-NET devices can be connected to one C-NET detector
line.
The C-NET connection is on the periphery board.
Depending on the control panel type (2 or 4 loops), 252 or 504 line devices can be
operated on a station.
Most C-NET line devices, such as fire detectors, are supplied with the operating
voltage required directly by the C-NET. An external power supply is always needed
for the FDCIO223 transponder.
Figure 9: C-NET loop with various line devices
1
Automatic fire detectors
Loop extension (C-NET)
The number of C-NET detector lines can be doubled. The loop extension (C-NET)
which is fitted on the periphery board is needed for this purpose.
The maximum number of addressable line devices per station remains limited to
252 or 504.
The loop extension (C-NET) has no electrical isolation between the two loops.
Line separator
All C-NET devices have an integrated line separator. In the event of a fault, e.g. a
short-circuit or wire break in the C-NET detector line, the line separator is opened
and the C-NET detector line segment in which the fault was found is shut down.
The C-NET devices remain functional and ready to detect. The fault is displayed on
the station.
C-NET
C
C erberus
T M
FDCIO222
FDS229
FDS221
4
4
FDCIO222
4
FDCIO221
1
1
FDCIO221
1
FDCIO223
24 V DC
FC722/FC724
1
FDCL221
DBS720
DBS720
FDMxxx
FDF241-9
FDL241-9
FT2010
FT2011
Synoptics
PCB
FT2001
FDCIO223
24 V DC
SynoLine 300
Connectable C-NET devices
5
32 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Connection factor (AK, RK, MK)
The number of connectable C-NET devices and the max. line length depend on the
connection factor of the terminated line devices. The maximum number of 126 C-
NET devices per loop and the max. length of line of 3300 m can be greatly reduced
depending on the type and volume of line devices used.
See also
1 Connectable C-NET devices [➙ 32]
1 Wiring principle behind C-NET devices [➙ 39]
1 C-NET topology and connection [➙ 36]
5.5
Connectable C-NET devices
The table below contains a list of all devices which can be connected to the C-NET
detector line. It also highlights which devices feature an alarm indicator (AI) and to
which an external alarm indicator (Ext. AI) or a sounder base (DBS720) can be
connected.
Device type
Type
Description
↑ AI
Ext. AI
DBS 720
Heat detector
HI720
Heat detector for demanding
applications
X
X
X
HI722
Heat detector for standard applications
X
X
X
Flame detector
FDF241-9
Flame detector with three sensors for
demanding applications with many
deceptive phenomena
X
X
–
Smoke detector
FDL241-9
Linear smoke detector for demanding
applications with many deceptive
phenomena
X
X
–
OP720
Optical smoke detector for standard
applications with few deceptive
phenomena
X
X
X
Multi-sensor
detector
OH720
Simple optical-thermal point detector
X
X
X
OOH740
Optical-thermal multi-sensor fire
detector for demanding application
X
X
X
OOHC740
Optical-thermal multi-sensor fire
detector with CO measurement
X
X
X
OOH740-A9-Ex 2
Optical-thermal multi-sensor fire
detector with ambient supervision with
collective DualProtocol and FDnet/C-
NET. For areas at risk of explosion
X
X
X
Aspirating smoke
detector
FDA221
Aspirating smoke detector up to a
monitoring area of 500 m2
X
X
X
FDA241
Aspirating smoke detector up to a
monitoring area of 800 m2
X
X
X
Connectable C-NET devices
5
33 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Device type
Type
Description
↑ AI
Ext. AI
DBS 720
Manual call point
FDM221
Direct activation for indoor applications
X
–
–
FDM223
FDM223H
Indirect activation (large housing)
X
X
–
FDM223-Ex
Indirect activation (large housing) for
areas at risk of explosion
X
X
–
FDM224
FDM224H
Indirect activation (large housing)
X
X
–
FDM225
Direct activation for indoor applications
X
–
–
FDM226
Direct activation for outdoor applications
X
–
–
FDM233
Indirect activation, suitable for migration
from existing SIGMASYS systems to
Cerberus systems
X
–
–
FDM234
Direct activation, suitable for migration
from existing SIGMASYS systems to
Cerberus systems
X
–
–
FDM243H
Indirect activation, robust housing for
use outdoors and in humid rooms,
suitable for migration from existing
SIGMASYS systems to Cerberus
systems
X
–
–
Input module
FDCI221
1 potential-free contact input
X
–
–
FDCI222
4 potential-free contact inputs
X
–
–
Zone module
FDCI723
1-zone module for connecting to
collective or conventional fire detectors,
with external supply. With safety barrier
SB3 for areas at risk of explosion as
well
X
–
–
Input/output
module
FDCIO221
1 potential-free contact input and
1 control output for any control
X
–
–
FDCIO222
4 potential-free contact inputs and
4 control outputs for any controls
X
–
–
FDCIO223
2 inputs/outputs can be alternatively
used either for controlling sounders or
connecting collective detector lines.
Mixed operation, i.e. 1 input channel
and 1 output channel, is also possible.
X
–
–
FDCIO224
4 potential-free contact inputs and 4
control outputs for the connection of the
VdS extinguishing interface in
compliance with the VdS or realization
of fire controls in compliance with
EN 54.
X
–
–
Connectable C-NET devices
5
34 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Device type
Type
Description
↑ AI
Ext. AI
DBS 720
Line separator
FDCL221
Line separator for the correct
connection of several stub lines at one
point on a loop
X
–
–
FDCL221-M
Multi line separator module for the
correct connection of several stub lines
on a loop via a line separator
X
–
–
Ex loop separators FDCL221-Ex
Line separator for the correct
connection of a stub line at one point on
a loop in an area at risk of explosion
X
–
–
Alarm sounder
FDS221
Acoustic alarm device with various
tones and sound levels
X
X
–
FDS229
Acoustic alarm sounder with
supplementary optical indication with
various tones and sound levels and
beacon
X
X
–
Sounder base
DBS720
Detector base with integrated alarm
device
–
–
–
Interbase
DBS721
Sounder interbase with integrated
acoustic alarm device
–
–
–
DBS728
Interbase with integrated alarm device,
acoustic and optical
–
–
–
DBS729
Interbase with integrated alarm device,
acoustic and optical
–
–
–
Detector base
DB721
Detector base with loop contact
X
X
–
Floor repeater
terminal
FT2010
For the system-wide indication and
operation of the most important
information and functions
X
–
–
Floor repeater
display
FT2011
For the system-wide indication of the
most important information
X
–
–
Mimic display
indication
FT2001
For the system-wide indication of events
X
–
–
External alarm
indicator
DJ119x
For optical indication in the event of
alarm
–
–
–
External alarm
indicator
FDCAI221
Addressable alarm indicator that can be
assigned to any cause using a control
–
–
–
Radio gateway
FDCW221
For the wireless transmission of
detector signals to the C-NET
X
X
–
Radio smoke
detector
DOW1171
Smoke detector for the wireless
transmission to the radio gateway
FDCW221
X
--
–
Manual call point
with radio base
SMF6120
SMF121
Manual call point for the wireless
transmission to the radio gateway
FDCW221
--
--
–
SWING radio
gateway
FDCW241
Gateway for the wireless transmission
of detector signals to the C-NET 1
X
X
–
Connectable C-NET devices
5
35 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Device type
Type
Description
↑ AI
Ext. AI
DBS 720
Neural radio fire
detector (SWING)
FDOOT271
Optical-thermal fire detector with radio
transmission to the radio gateway
FDCW241 1
X
X
–
Radio manual call
point (SWING)
FDM273
Indirect activation via radio gateway
FDCW241
X
–
–
FDM275
SWING manual call point, activation via
radio gateway FDCW241
X
–
–
Aspirating smoke
detector
VLF
VESDA LaserFocus (laser monitoring)
–
–
–
Table 1: Devices which can be connected to the C-NET detector line
X
Possible / available
–
Not possible / not available
1
Availability is communicated with the delivery release
2
Check with your country representative that this detector is approved for
C-NET in your country.
Most devices are supplied via the detector line.
The input/output module FDCIO223 must have an external power supply.
All ↑ C-NET devices have an integrated line separator.
NOTICE
Influencing the earth fault monitoring
Faults
●
For devices on the C-NET with a separate supply, the supply must be
electrically isolated. FDCIO223 is an exception to this rule.
The number of connectable devices depends on the specific AK, RK, MK
connection factor of the type and is calculated using the 'Quantities Tool' software.
Note the specifications of the individual C-NET devices in the 'List of Compatibility'
document, see 'Applicable documents' chapter.
See also
1 C-NET detector line [➙ 31]
C-NET topology and connection
5
36 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.6
C-NET topology and connection
Permissible topology for the C-NET
The C-NET can only be wired in the topologies shown below. Regardless of the
topology (loop, stub or loop with sub-stub), the C-NET system limits, such as
length, cable resistor, number of line devices etc., must be observed.
Either one loop or two stubs can be connected to a C-NET line connection (2-wire
line on block of 4 terminals).
Loop
(max. 1 loop per line connection)
Stub line
(max. two stubs per line connection)
Sub-stubs on loop
A sub-stub may only be connected between two line devices and/or
line separators, and directly on the terminal connection.
Wiring NOT admissible
NOT admissible!
Sub-stub on sub-stub
NOT admissible!
Sub-stub on a stub
The connection terminals for the C-NET are located on the periphery board or on
the loop extension (C-NET).
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
C-NET topology and connection
5
37 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
C-NET connection terminals
Figure 10: Position of C-NET connection terminals (FC722 and FC724) incl. loop extension
1
Fire control panel FC722
A loop extension (C-NET) can be fitted as an
option.
* maximum of 252 C-NET devices (including
loop extension)
2
Fire control panel FC724
Two loop extensions (C-NET) can be fitted as
an option.
* maximum of 504 C-NET devices (including
loop extensions)
X11 Line connection 1
X21 Line connection 3
X12 Line connection 2
X22 Line connection 4
X13 Optional line 1 and/or 3
X14 Optional line 2 and/or 4
One single C-NET line connection (4 terminals) allows max. 252 C-NET line
devices to be connected. These can be located on one single loop or spread over
max. two stubs (max. 32 line devices per stub).
Loop connection example
●
Max. 252 line devices per loop
Figure 11: C-NET loop circuit
Alternatively two stubs can be connected instead of one loop.
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
T M
+
+
C-NET topology and connection
5
38 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Stub connection example
●
Max. 32 line devices per stub
●
Total of max. 64 line devices per line connection (4 terminals)
Figure 12: C-NET stub circuit
Loop extension
The loop extension (C-NET) can be used to double the number of lines, but the
total number of C-NET devices which can be connected is not increased (max. 252
or 504). The line devices can be spread over several loops or stubs.
The loop extension (C-NET) is mounted onto the periphery board. Installation of
the two loop extensions is identical on both periphery boards. The two connections
(X13/X14) on the loop extensions are not electrically isolated.
Depending on the control panel type (2 or 4 loops), up to 4 C-NET loops or 8 stubs
can be connected.
Cable types
As a result of national standards and requirements, installation may require a
particular cable type. The relevant requirements and planning documents should
be taken into account here. The following cable types can always be used for
cabling the detector line:
●
twisted, with and without shielding (recommended)
●
untwisted, with and without shielding
Cable shielding
When using shielded lines (e.g. fire detection cable J-Y(St)Y, n x 2 x 0.8 mm),
ensure that the cable shielding is only connected on one side. The fire control
panel's function may be impaired by a missing or incorrect cable shielding
connection. The 'shield connection terminal blocks' option is available for the
shielding connection. Depending on the installation environment and requirements
of relevant standards, cable shielding may have to be connected and merged at
one central connection point.
Limitations
●
The following restrictions apply if more then 126 devices are connected to a
loop (a maximum of 252 may be connected):
–
No support for ’turbo isolation’
–
Restricted loop length (see outline quantities tool FX7210 )
–
A total of 252 addresses are possible per line card
–
Line tester only supports a maximum of 126 addresses
In accordance with EN 54, a maximum of 32 detectors may fail in one fire sector in
the event a simple fault (e.g. wire breakage, short-circuit).
Details of the cable specification for the C-NET can be found in the system
documentation.
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
+
+
Wiring principle behind C-NET devices
5
39 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.7
Wiring principle behind C-NET devices
The screw terminals for directly connecting the fire detection cable are integrated in
every C-NET line device. The connection terminals with input (+/-) and output (+/-)
are the same for all line devices, with the exception of the detector base.
Figure 13: Wiring example of C-NET detector devices on loop
A
Connection terminal for detector base
and sounder base
1b Corresponds to +, input/output
5
Corresponds to –, input
6
Corresponds to –, output
S
Shielded connection cable, optional
1
Manual call point
3
Transponder
2
Input/output modules
4
Alarm sounder with beacon
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
0
#
C
Cerberus
TM
1b
6
6
5
1b
5
FC722 / FC724
C-NET
A
1
2
3
4
S
40 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Figure 14: Wiring example of C-NET detector devices on stub
(1) If shielded connection cables are used, the cable shielding must be connected
on one side.
* The number of connectable C-NET devices and the max. line length depend on
the device connection factor. The maximum number of 126 C-NET devices per
loop and the max. length of line of 3300 m can be greatly reduced depending on
the type and volume of line devices used. The necessary calculation is performed
using Quantity Tool A6V10211118. See chapter 'Applicable documents'
5.8
C-WEB network
The C-WEB is a monitored 2-wire bus line (SAFEDLINK) and allows 32 Cerberus
PRO stations such as FC722/FC724 type fire control panels and FT724 fire
terminals to be networked. The maximum distance between 2 stations is 1000 m. A
repeater (SAFEDLINK) can be used to double the distance to 2 x 1000 m (requires
external supply).
A network card (option) is needed per station for networking via the C-WEB.
All stations networked via the C-WEB can communicate with one another,
depending on configuration. This makes system-wide operation, control and
alarming possible.
Figure 15: Networking by means of C-WEB/SAFEDLINK
1
PC with 'Cerberus Engineering Tool' software or management station
2
Station with remote transmission
3
SAFEDLINK station, networked with another 3 stations via Ethernet (max. 4 stations)
FN2002 Repeater (SAFEDLINK) for extending the C-WEB
b
e
1
2
3
j
l
n
4
5
6
h
i
u
7
8
9
r
0
#
C
Cerberus
TM
C-WEB/SAFEDLINK
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Ce rb eru s
T M
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerb erus TM
FC724
FC722
FC722
FT724
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerbe rusT M
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerb erus TM
FC724
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerbe rusT M
Ethernet
1
2
3
4
FN2002
41 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Guidelines
●
Fire control panels with 512 and more fire detectors (irrespective of the remote
transmission connection) must be equipped with 2 network cards
(SAFEDLINK) (according to EN 54).
●
Fire control panels with a central remote transmission connection (irrespective
of the number of detectors in the system) must be equipped with 2 network
cards (SAFEDLINK) (according to EN 54).
●
Fire control panels monitoring surfaces larger than 12,000 m2 must be
equipped with 2 network cards (SAFEDLINK) (according to EN 54).
●
A network of up to 32 stations (incl. SAFEDLINK stations) via Ethernet is
supported, but does not meet the requirements of EN 54.
●
Furthermore, the fire detection system can be connected to a management
station via BACnet/Ethernet.
C-WEB (2-wire bus)
Ethernet (does not comply with
EN 54)
Max. line length between two stations
1000 m
100 m (without switch or router)
Max. number of stations in network
32
14
Max. line length between the repeater and the
station
1000 m in each case
---
Maximum nunber of Repeaters between 2
stations
1
---
Maximum number of repeaters in the C-WEB
network
32
---
C-WEB connection to network card
The C-WEB is connected to the connection terminals on the first network card.
A second network card (SAFEDLINK) can also be used for redundant network
operation (according to EN 54 guidelines).
The first network card must always be fitted on the left space (connection strip
X13) on the PMI & mainboard of the operating unit.
Figure 16: Installation of network cards on PMI & mainboard of operating unit (view of rear)
1
Space for first network card
2
Space for a second network card (degraded
mode module)
X13
X12
X3
X3
42 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Figure 17: Wiring the network cards (SAFEDLINK)
Cable type and transmission speed
Use only twisted pair cables with a minimum of 10 twists per meter. Trouble-free
operation cannot be guaranteed with any other cable types. Two wires are
required.
Both shielded or unshielded cables can be used.
Data rate in the C-WEB
The speed of transmission in the C-WEB can be adjusted depending on the actual
installation conditions. An example application would be dealing with a
communication fault that has occurred with the standard data rate setting of
315 kbit/s because the installation cable is of low quality. In this case the system's
speed of transmission can be changed from 'Standard' to 'Low'.
Details of the C-WEB and cable specification for the C-WEB can be found in the
system documentation.
X3
B2
A2
B1
A1
X3
Indication and operating elements
C-WEB network
6
43 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
6 Indication and operating elements
Fire control
panel FC72x
Fire terminal
FT724
LED module
FTO2008
Floor repeater
terminal FT2010
Floor repeater
display FT2011
Cerberus
Remote
Indication
Alarm
X
X
X
X
X
X
Pre-alarm
X
X
X
X
X
X
Fault
X
X
X
X
X
X
Isolation
X
X
X
X
X
X
Test mode
X
X
X
--
--
X
Technology
X
X
X
--
--
X
Activation
X
X
X
--
--
X
Information
(Note)
X
X
X
--
--
X
Activated
remote
transmission
(RT)
X
X
X
X
--
X
Operation
Acknowledge
X
X
--
X
--
X
Reset
X
X
--
X
--
X
Scroll in event
lists
X
X
--
X
X
X
Deactivate
internal
buzzer
X
X
--
X
X
X
Deactivate
sounder
X
X
--
--
--
X
Table 2: Functions of the individual operation and indication devices
X = possible/available
-- = not possible / not available
Indication and operating elements
C-WEB network
6
44 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Figure 18: Operation and display front of Cerberus PRO fire control panel
1
Display, illuminated with plain text display
2
Cursor keypad for navigation/selection of menu items
3
Menu button
4
Keypad (for direct selections by entering numbers and/or entering and changing objects-specific display
texts)
5
C button (Cancel) and OK button (confirmation of selection)
6
Menu-dependent function keys (softkeys)
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
1
2
3
4
5
6
Indication and operating elements
Extra indication and operating devices
6
45 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
6.1
Extra indication and operating devices
The fire terminal is also provided for indication and operation as is the floor
repeater terminal and floor repeater display although these two offer only restricted
functions.
Fire terminal
The fire terminal is an indication and operating unit without the functionality of a
station. It makes possible all display and operating functions of a Cerberus PRO
fire control panel within a C-WEB network, but does not normally have its own
power unit or emergency power supply. A power unit (70 W) or batteries can also
be used.
FT724 fire terminal
The display and operation are the same as that for a fire control panel
Functions
●
Supplied via fire control panel or optional supply
●
Separate 24 V supply input, monitored
●
Can be networked via C-WEB or Ethernet
●
System-wide visibility configurable
Floor repeater terminal / floor repeater display
The FT2010 floor repeater terminal and FT2011 floor repeater display allow for the
decentralized indication of the most important events in the fire detection system
and limited operation. Both devices can be connected to the C-NET directly as line
devices. The power is supplied via the C-NET or through an external power unit (if
supplied externally, the voltage source does not need to be electrically isolated)
Floor repeater terminal FT2010
The following indications and operations are possible on the floor repeater
terminal:
Display
●
Alarm and fault messages of connected station(s)
●
Activated remote transmission (RT)
Operation
●
Acknowledge (start investigation time)
●
Reset
●
Scroll in event lists
●
Deactivate buzzer
●
Four freely programmable keys
Floor repeater display FT2011
The following indications and operations are possible on the floor repeater
display:
Display
●
Alarm and fault messages of connected station(s)
Operation
●
Scroll in event lists
●
Deactivate buzzer
a
b
d
e
1
2
3
j
l
n
o
4
5
6
g
h
i
u
7
8
9
p
q
r
0
#
C
Cerberus
TM
Extra indication and operating devices
7
46 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7 Commissioning
This chapter describes initial commissioning of the Cerberus PRO fire control panel
(individual control panel, not networked).
●
Activating access level
●
Start auto-configuration
●
Display C-NET line devices
●
Enter customer texts for the control panel, C-NET and individual line devices
via the control panel keypad
Figure 19: Line tester FDUL221
NOTICE
Connecting C-NET and line tester to the station at the same time
The line tester or station may be damaged.
●
Do not connect C-NET and line tester to the station at the same time.
ϖ
C-NET is not yet connected to the station.
ϖ
Before commissioning and auto-configuration of the stations, the connected C-
NET loops or stubs must be checked for correct function using the FDUL221
line tester.
1.
Connect the line tester FDUL221 to the C-NET detector line.
2.
Test the C-NET detector line for short-circuits, open lines, and ground faults.
3.
Check the number of devices on the C-NET detector line based on the display
on the line tester.
4.
Check the branch-off position of the stubs and the number of devices at the
stubs.
5.
Check the type of the respective C-NET device.
6.
Remedy any errors/faults which may be active before commissioning or auto-
configuration
You will find information about line tester FDUL221 in document 008250.
Activating access level
7
47 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.1
Activating access level
The 'Station' is protected against unauthorized operation by access levels.
Authorization for access level 3 is needed for the functions described below.
If the authorization code is not entered, operation is only possible in access level
1 (guest), e.g., for acknowledging the control panel buzzer or scrolling through the
display messages.
The authorization code set in the factory is '0000'. This authorization code must be
changed once the station has been configured.
Logout timeout
The 'Station' is provided with a time control function for the operation.
The operation enable for an access level expires after a configurable period of time
has passed since the last entry.
7.1.1
Log in / Change access level
You can enable an 'Access level' by entering your PIN in the PIN entry dialog, or by
pressing . Alternatively you can use the key switch (optional) to release an
Access level.
If you press a key on the ↑ Person Machine Interface whose function requires a
higher 'Access level', the PIN input dialog is displayed automatically.
Login/logout
Enter PIN: ****
Logout or guest-login: no PIN +
Confirm with /Exit with
Delete with
Table 3: PIN entry dialog box
Enabling an 'Access level' without a PIN
1.
Press
Auto-configuration of control panels
7
48 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.2
Auto-configuration of control panels
This function requires the control panel, components, and C-NET to have been
correctly installed. Once auto-configuration is complete, the control panel is ready
for detection with limitations. A fire is recognized by the connected fire detectors
and displayed on the control panel. Configuration with the FXS7212 Cerberus
Engineering Tool is required in order to assign controls, define individual alarm
responses, and make adjustments in line with object-specific requirements.
NOTICE
Overwriting an existing configuration
Parts of an existing customer-specific configuration are lost.
●
First save an existing customer-specific configuration.
ϖ
Every loop or stub line is tested with the line tester FDUL221 to ensure it is
functioning and installed correctly.
κ
Run auto-configuration as described in the 'Auto-configuring a line' chapter.
The station is ready to detect - with limitations. The C-NET devices have been
addressed. Should an event occur, e.g. a triggered fire detector and its C-NET
address are displayed.
WARNING
Control panel is ready for detection - with limitations.
Alarm transmission to the fire brigade is not configured.
Activation of acoustic signal transmitters is not configured.
●
Configure the controls needed.
Customer text (e.g. detector number, installation location etc.) can be entered for
each C-NET device for improved clarity.
Auto-configuration of control panels
7
49 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.2.1
Auto-configure line
The 'Line' element category in the 'Maintenance' menu facilitates the reading-in of
the current topology, for example. This creates part of the elements in the
'Detection tree'.
NOTICE
Overwriting an existing configuration
Parts of an existing customer-specific configuration are lost.
●
First save an existing customer-specific configuration.
Auto-configuring a line:
1.
In the main menu, select the 'Topology' menu item.
The 'Topology' window is open.
2.
Select 'Hardware tree'.
The 'Element' window is open.
3.
Select 'Station' and press the 'Lower level' .
The elements of 'Station' are displayed.
4.
Select the corresponding 'C-NET line card (onboard/FCL2001)' module and
press the 'Lower level .
All lines of 'C-NET line card (onboard/FCL2001)' are indicated.
5.
Select a line and press 'More Options' .
The 'Select option' window is open.
6.
Select 'Execute commands' and confirm with .
The window including the possible commands is displayed.
7.
Select the 'Auto-configure line' command and confirm with .
The line is auto-configured.
Auto-configuration of control panels
7
50 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Display for auto-configuration
Main menu
Exit with
Access level 3
Message summary
Functions
Favorites
Topology
(1)
(2)
(3)
(4)
Element search
Event memory
Login/logout
Settings/administration
(5)
(6)
(7)
(8)
Function
On/Off
Function
All
LED
test
κ
Select 'Topology', continue with
Topology
Exit with
Access level 3
Detection tree
Hardware tree
Control tree
(1)
(2)
(3)
Function
On/Off
Function
All
LED
test
κ
Select 'Hardware tree', continue with
001 Element
Hardware tree
Station
1
Lower
level
More
Options
κ
Select 'Station 1', continue with 'Lower level'
005
FC721
Elements
Main building
Station 1
Module
Module
Module
Module
1
2
3
4
Onboard I/Os
Onboard I/Os
'C-NET line card (onboard/FCL2001)'
Communication interfaces
Upper
level
Lower
level
More
Options
κ
Select 'Module 2', continue with 'Lower level'
Auto-configuration of control panels
7
51 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
007 Elements
'C-NET line card (onboard/FCL2001)'
Module 2
Line
Line
Line
Line
11
12
21
22
Line
Line
Line
Line
Upper
level
Lower
level
More
Options
κ
Select 'Line 1', continue with 'More Options'
Selecting option
Execute commands
Show details
(3)
(5)
κ
Select 'Execute commands', continue with
Select command
Read in installed devices
Detector line OFF
Auto-configure line
Set customer text
Accept replaced devices
(1)
(2)
(3)
(4)
(6)
κ
Select 'Auto-configure line', continue with
The line is auto-configured.
Displaying C-NET devices
7
52 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.3
Displaying C-NET devices
After auto-configuration, the individual C-NET detector lines and the associated C-
NET devices of each line can be displayed and configured.
Depending on the control panel type (2 or 4 loops) and the control panel design,
the depiction may vary and several lines may be displayed.
You can display the lines and devices as follows. The displays are depicted in the
same way as those in the 'Auto-configuring a line' chapter with the exception of the
'Show details' command.
ϖ
At least one line is configured.
1.
In the main menu, select the 'Topology' menu item.
The 'Topology' window is open.
2.
Select 'Hardware tree'.
The 'Element' window is open.
3.
Select 'Station' and press the 'Lower level' .
The elements of 'Station' are displayed.
4.
Select the corresponding 'C-NET line card (onboard/FCL2001)' Module and
press the 'Lower level' .
All lines of 'C-NET line card (onboard/FCL2001)' are indicated.
5.
Select a line and press 'More Options'' .
The 'Select option' window is open.
6.
Select 'Execute commands' and confirm with .
The window including the possible commands is displayed.
7.
Select the 'Show details' command and confirm with .
The details are displayed.
Displaying C-NET devices
7
53 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Example of selecting a line
004 Elements
C-NET line card
(onboard/FCL2001)
Module 2
Line
Line
Line
Line
11
12
21
22
Line
Line
Line
Line
Upper
level
Lower
level
More
Options
004 Elements
Line 12
Device
Device
Device
Device
11
12
21
22
OH720
HI720
OP720
OP720
Upper
level
Lower
level
More
Options
κ
Check whether all devices of this C-NET detector line are displayed correctly.
You can use the type designation to detect the type of device displayed (smoke
detector, heat detector, manual call point etc.)
You will find a list of type designations in the 'C-NET devices' chapter
Entering/Changing customer text
7
54 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.4
Entering/Changing customer text
You can enter customer text for any element on the control panel, independently of
Cerberus-Engineering-Tool.
Once customer text has been entered or changed, the updated display is only
shown the next time the element is accessed.
Entering or changing customer text does not lead to a reboot.
'Set customer text'
1.
Select an element
2.
Press the 'Execute Commands' softkey
3.
Select the 'Set customer text' command.
4.
Enter the desired customer text and confirm the entry with .
The customer text has been entered.
Changing customer text
Proceed in the same way as when entering customer text but change the existing
customer text.
7.5
Setting the system time
The set system time is used to log all the control panel's messages, save them in
the event memory and output them on a connected printer.
7.5.1
Setting time and date
You will have to reset the clock if the fire control panel has been de-energized. In
countries with central European summer time (CEST), the system clock
automatically switches between daylight savings time and regular time.
'Enter date / time'
1.
Select 'Main menu' > 'Settings/administration' > 'System commands'.
The 'System commands' window is open.
2.
Select 'Set system time'.
The 'Enter date / time' window is open.
3.
Enter the date and time and/or confirm with .
The cursor jumps to the next field and terminates the input after the last
field.
Adjusted or confirmed date and time are set.
Enter date / time
25-04-09 12:42:58
(dd-mm-yy) (hh:mm:ss)
Confirm with /Exit with
Delete with
Table 4: Input window for time and date
Changing access authorization PIN
7
55 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.6
Changing access authorization PIN
After successful commissioning, the 4-digit access authorization (PIN) for the
corresponding access level must be changed. Keep the new PIN in a safe place.
If the PIN is lost, a system reset must be undertaken to the station's factory setting.
The control panel configuration, including all customer data, is cleared in the
process.
The '0000' PIN set in the factory then applies again after a system reset.
7.6.1
PIN administration
You can change an existing PIN and create a new PIN or delete a PIN with the
corresponding authorization.
PIN administration not available
If PIN administration is not available at the station, you must configure the PINs in
Engineering Tool. You will find more information in document A6V10210424.
'Change PIN'
1.
Select 'Main menu' > 'Settings/administration' > 'Manage PINs'.
2.
Select the 'Change PIN' menu item.
3.
Enter the PINs in accordance with the input fields and confirm with .
The PIN has been changed.
Change PIN
Old PIN: ****
New PIN: ****
Verify new PIN: ****
Confirm with /Exit with
Delete with
Changing access authorization PIN
7
56 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
'Create PIN'
ϖ
You have the required authorization level.
1.
Select 'Main menu' > 'Settings/administration' > 'Manage PINs'.
2.
Select the 'Create PIN' menu item.
3.
Enter an admissible access level.
4.
Enter the PIN in accordance with the input fields and confirm with .
A new PIN has been created.
Create PIN
Access level: __
Enter PIN: ****
Verify PIN: ****
Confirm with /Exit with
Delete with
'Delete PIN'
ϖ
PIN is present.
ϖ
You have the required authorization level.
1.
Select 'Main menu' > 'Settings/administration' > 'Manage PINs'.
2.
Select 'Delete PIN'.
3.
Enter the PIN in accordance with the input fields and confirm with .
PIN has been deleted.
Delete PIN
Enter PIN: ****
Verify PIN: ****
Confirm with /Exit with
Delete with
Restart the station
7
57 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
7.7
Restart the station
The configuration of the ↑ 'Station' remains the same.
There are the following ways in which to restart the ↑ 'Station':
●
Via the menu on the display
●
PMI & mainboard FCM2004 and FCM2027: With the 'S32' button
●
↑ CPU card: With the 'S8' button
Via the menu on the display
If you are using two ↑ CPU cards, you must perform the following procedure once
for each CPU card.
1.
Press .
The PIN input dialog is displayed.
2.
Enter a valid PIN and confirm with .
The 'User successfully logged in' message is displayed.
The main menu is displayed.
3.
Select the 'Topology' > 'Hardware tree' > 'Station' menu items.
The elements of the 'Station' are listed.
4.
Select module 101 or module 102 'CPU (FCC2001/06)'.
5.
Press the 'MoreOptions' softkey and select 'Execute commands'.
6.
Select the 'Reset module' command.
The 'Station' shuts down.
The 'Station' is switched off for several seconds.
The 'Station' restarts.
Restart the station
7
58 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
PMI & mainboard FCM2004 and FCM2027
ϖ
Switches S38-1 and S38-2 are set to the 'OFF' position on the PMI &
mainboard FCM2004.
κ
On the PCB of the operating unit, press and hold down the 'S32' button for
<2 s.
The 'Station' shuts down.
The 'Station' is switched off for several seconds.
The 'Station' restarts.
↑ CPU card
1.
Briefly press the 'S8' button on the CPU card until a 'R' is displayed on the LED
matrix display.
2.
As soon as the 'R' is displayed, press and hold the 'S8' button for approx. 2 s to
confirm the selection.
A checkmark on the LED matrix display confirms the selection.
The CPU card is restarted.
You will find information on the ↑ CPU card FCC2004, the LED matrix display,
and operating the 'S8' button in document A6V10210368. See chapter 'Applicable
documents'.
Testing the installation
Checking functions
8
59 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
8 Testing the installation
The fire detection installation can be switched to 'Test' operation mode to check it
is functioning properly.
8.1
Checking functions
The table below shows the recommended intervals for checking functions. National
specifications always take priority.
For details of the function test, refer to the 'Applicable documents' chapter.
Function
Activity
Interval
(years)
1
2
5
Software
Check date and time.
X
Detector lines:
●
C-NET
Trigger an automatic detector and a manual call point per line.
X
Trigger all manual call points
X
Trigger all automatic fire detectors.
X
Check all detectors for soiling and application.
X
Check the function of the input/output modules.
X
On each line check whether short-circuit / open line triggers a 'Fault'.
Check the loop line function.
During short-circuit also check the separator function.
X
Fire controls
Check activation of the controls up to and with the interface.
X
Check isolations carried out by the customer. Arrange a time with the
customer.
X
Degraded function
X
Mains failure
Check 'Delayed for in case of a mains failure' function.
Alarm organization
Check the function of the delay times t1 and t2.
X
Alarm activation by automatic detector on 'unmanned'
⇒ Global alarm.
X
Alarm activation by manual call point on 'manned' and 'unmanned'
⇒ Local alarm/global alarm.
X
Check automatic switchover 'Manned' / 'Unmanned' on the basis of
the event memory entry.
X
Check activation of the remote transmission equipment with 'Alarm'.
X
Actuate the corresponding danger level by activating a detector with
the detector exchanger and tester
X
Alarm devices
In emergency power operation check all alarm devices taking the
event category into account:
'Pre-alarm'
'Alarm'
'Fault'
X
60 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Glossary
AI
Abbreviation for 'alarm indicator'.
C-NET device
A device connected to the C-NET detector line.
CPU
Abbreviation for 'Central Processing Unit'. The
computing unit of the fire control panel.
PMI
The arrangement of operating and display
elements on a fire control panel or on a fire
terminal. Includes the LEDs, buttons, the display,
and the operation options such as the key
switch, fire brigade control and display (FBA),
and the EVAC NL Person Machine Interface.
Station
Unit for system control. Fire control panel or fire
terminal.
61 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Index
C
Customer text
Entering / changing ......................................... 54
D
Date
Set .................................................................. 54
Download center
URL ................................................................. 7
H
Hardware reset
Station ............................................................ 57
L
Line
Auto-configuration ........................................... 49
Log in ............................................................. 47
Login.............................................................. 47
O
Original language
Source language .............................................. 5
P
PIN ................................................................ 47
Input dialog ..................................................... 47
Manage, create, delete, change ...................... 55
Releasing an access level ............................... 47
R
Releasing an access level ................................ 47
Restart
Station ............................................................ 57
S
Set
Date and time ................................................. 54
Source language ............................................... 5
Station
Hardware reset ............................................... 57
Restart ............................................................ 57
T
Time
Set.................................................................. 54
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
+41 41-724 24 24
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2009
Technical specifications and availability subject to change without notice.
Document ID: A6V10211094_f_en_--
Manual FS720
Edition: 2015-12-15