5006167-YTG-F-0517 TECHNICAL GUIDE MODULAR PSC AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MP SERIES Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at: www.upgnet.com and www.york.com Additional rating information can be found at: www.ahridirectory.org WARRANTY SUMMARY Standard 5-year limited parts warranty. Extended 10-year limited parts warranty when product is registered online within 90 days of purchase for replacement or closing for new home construction. ® DESCRIPTION This unique modular syst ...
5006167-YTG-F-0517 LIST OF SECTIONS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 FEATURES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 DIMENSIONS & DUCT CONNECTION DIMENSIONS . . . . . . . . . . . 3 DIMENSIONS - MP MODULAR AIR HANDLERS & CM MULTI-POSITION FULL CASED COILS . . . . . . . . . . . . . . . . . . 3 COOLING CAPACITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 PHYSICAL & ELECTRICAL DATA - C ...
3 5006167-YTG-F-0517 DIMENSIONS & DUCT CONNECTION DIMENSIONS � � � ��������� ������������������ ������������������� ����������� ���������� ������������ ������������ � �������� ������� � ������� ������� � �������������� �������������� ��������������� ������� � � ��� ...
5006167-YTG-F-0517 COOLING CAPACITY1 Models Rated CFM2 Entering Air Dry/Wet Bulb (°F) MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG) 35/107.9 40/118.9 45/130.7 50/143.3 CM18B 600 85/72 45.7 41.6 36.8 30.5 80/67 38.5 33.9 28.5 22.3 75/62 31.5 26.5 20.5 15.9 70/57 24.4 19.5 15.2 11.5 CM24B 800 85/72 52.2 47.5 41.8 35.0 80/67 43.6 38.3 31.9 24.5 75/62 35.2 29.5 22.7 16.2 70/57 27.1 20.7 15.5 11.4 CM24C 800 85/72 52.2 47.5 41.8 35.0 80/67 43.6 38.3 31.9 24.5 75/62 35.2 29.5 22.7 16.2 70/57 27.1 20.7 15.5 11.4 CM30B 1000 85/72 75.3 67.8 56.8 47.1 80/67 62.6 54.6 44.2 34.5 75/62 50.2 41.3 32.0 22.9 70/57 37 ...
5 5006167-YTG-F-0517 CM48C 1400 85/72 108.0 98.4 88.1 73.8 80/67 93.3 82.1 69.7 57.0 75/62 75.9 64.4 53.1 41.9 70/57 60.7 49.9 39.4 32.4 CM48C 1600 85/72 115.2 105.0 93.9 79.0 80/67 88.3 78.2 65.5 52.6 75/62 72.7 60.8 50.1 37.6 70/57 57.7 46.9 36.6 29.7 CM48D 1600 85/72 115.2 105.0 93.9 79.0 80/67 88.3 78.2 65.5 52.6 75/62 72.7 60.8 50.1 37.6 70/57 57.7 46.9 36.6 29.7 CM60C 1800 85/72 115.1 103.0 91.7 78.6 80/67 96.8 85.9 73.7 60.5 75/62 80.7 69.4 57.5 43.5 70/57 58.7 48.9 37.7 32.7 CM60D 1800 85/72 115.1 103.0 91.7 78.6 80/67 96.8 85.9 73.7 60.5 75/62 80.7 69.4 57.5 43.5 70/57 58.7 48.9 37.7 32.7 CM64D 1800 85/72 133. ...
5006167-YTG-F-0517 ELECTRICAL HEAT - MINIMUM FAN SPEED Heater Kit Models1,2,3 Nom. kW @240V Air Handler Models MP08B MP12B MP14D MP16C MP20D 6HK(0,1)6500206 2.4kW Low Low Low Low Low 6HK(0,1)6500506 4.8kW Low Low Low Low Low 6HK(0,1)6500806 7.7kW Low Low Low Low Low 6HK(0,1)6501006 6HK36501025 9.6kW Low Low Low Low Low 6HK(1,2)6501306 12.5kW Med Low Low Low Low 6HK(1,2)6501506 6HK36501525 14.4kW – Med Low Low Low 6HK(1,2)6501806 6HK36501825 17.3kW – Med Low Low Low 6HK(1,2)6502006 6HK46502025 19.2kW – Med Med High Low 1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect. 2. (1,2) - 1 = with servi ...
7 5006167-YTG-F-0517 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 Air Handler Models Heater Models1,2 Heater Amps @240V Field Wiring Min. Circuit Ampacity MOP.3 208V 230V 208V 230V MP08B 6HK(0,1)6500206 10 12.6 13.7 15 15 6HK(0,1)6500506 20 23.4 25.7 25 30 6HK(0,1)6500806 32 36.6 40.3 40 45 6HK(0,1)6501006 40 45.0 49.6 45 50 6HK(1,2)6501306 52 58.2 64.3 60 70 MP12B 6HK(0,1)6500206 10 14.1 15.2 15 20 6HK(0,1)6500506 20 24.9 27.2 25 30 6HK(0,1)6500806 32 38.1 41.8 40 45 6HK(0,1)6501006 40 46.5 51.1 50 60 6HK(1,2)6501306 52 59.7 65.8 60 70 6HK(1,2)6501506 60 68.2 75.0 70 80 6HK(1,2)6501806 72 81.4 89.7 90 ...
5006167-YTG-F-0517 ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60 Air Handler Models Heater Models Heater Amps @240V Min. Circuit Ampacity MOP.1 208V 230V 208V 230V Circuit Circuit 1st 2nd 1st3 2nd 1st3 2nd 1st3 2nd MP08B 6HK16501306 52 20.5 37.6 22.5 41.5 25 40 25 45 MP12B 6HK16501306 52 22.0 37.6 24.0 41.5 25 40 25 45 6HK16501506 60 24.9 43.3 27.2 47.9 25 45 30 50 6HK16501806 72 42.3 39.0 46.4 43.1 45 40 50 45 6HK16502006 80 46.6 43.3 51.2 47.9 50 45 60 50 MP14D 6HK16501306 52 22.3 37.6 24.3 41.5 25 40 25 45 6HK16501506 60 25.2 43.3 27.5 47.9 30 45 30 50 6HK16501806 72 29.5 39.0 46.6 43.1 30 40 50 45 6 ...
9 5006167-YTG-F-0517 ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-3-60 Air Handler Models Heater Models1 Heater Amps @240V Min. Circuit Ampacity MOP.2 208V 230V 208V 230V Circuit Circuit 1st 2nd 1st3 2nd 1st3 2nd 1st3 2nd MP12B 6HK46502025 46.2 28.3 25.0 30.9 27.6 30 25 35 30 MP14D 6HK46502025 46.2 28.5 25.0 31.1 27.6 30 25 35 30 MP16C 6HK46502025 46.2 28.6 25.0 31.3 27.6 30 25 35 30 MP20D 6HK46502025 46.2 30.1 25.0 32.8 27.6 35 25 35 30 1. The 20kW heater model (6HK46502025) come with service disconnects standard. 2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay ...
5006167-YTG-F-0517 ACCESSORIES Refer to Price Manual for specific model numbers where not shown. TXV Kits - Air handlers are shipped with “Flex-coils” without a factory installed metering device. For added flexibility, an R-22 or R-410A TXV or orifice can be field installed to meet your refrigerant choice. All kits are chatleff style and require no brazing to install. Electric Heaters - 6HK models shown under electrical data include sequential operation and temperature dual limit switches for safe, efficient operation. Service disconnects are provided where shown. Bottom Rack Filter Kit - The filter frame access ...
11 5006167-YTG-F-0517 COMBUSTIBLE FLOOR BASE ACCESSORY LIMITATIONS These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as follows: Airflow must be within the minimum and maximum limits approved for electric heat, indoor coils and outdoor units. TYPICAL APPLICATIONS Floor Base Models Used with Dimensions A B C 1FB1917 MP08B, MP12B 17.5 14.0 16.0 1FB1921 MP16C 21.0 17.5 19.5 1FB1924 MP14D, MP20D 24.5 21.0 23.0 DOWNFLOW AIR HANDLER WARM AIR PLENUM with 1” flange out on each side. FIBERGLASS INSULATION FIBERGLASS TAPE under flange. COMBUSTIBLE FLOOR BASE ACCE ...
5006167-YTG-F-0517 TYPICAL THERMOSTAT CONNECTION A0370-002 W2 ��� ��� ��� ��� FIELD INSTALLED JUMPER IF SINGLE STAGE THERMOSTAT IS USED. ...
13 5006167-YTG-F-0517 Dry coil conditions only, tested without filters. For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Heating applications tested at 0.50” w.c. esp. AIR FLOW DATA - CFM1 (208 Volt) Models CM Models Blower Motor Speed External Static Pressure (in. WC.) 0.10 0.20 0.30 0.40 0.50 0.60 0.70 208 Volt MP08B CM18B High 975 965 953 926 889 772 724 Medium 729 719 700 643 614 540 354 Low 576 561 501 455 407 289 209 CM24B High 950 944 927 907 876 838 742 Medium 713 703 686 656 591 533 478 Low 560 546 511 448 398 294 208 MP12B CM30B High 1459 1410 1342 1275 1200 1129 1022 Me ...
5006167-YTG-F-0517 Copyright © 2017 by Johnson Controls, Inc. All rights reserved. Supersedes: 5006167-YTG-E-1116 York International Corp. 5005 York Drive Norman, OK 73069 Dry coil conditions only, tested without filters. For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Heating applications tested at 0.50” w.c. esp. AIR FLOW DATA - CFM1 (230 Volt) Models CM Models Blower Motor Speed External Static Pressure (in. WC.) 0.10 0.20 0.30 0.40 0.50 0.60 0.70 230 Volt MP08B CM18B High 1142 1126 1093 1057 1009 953 852 Medium 855 840 826 798 756 696 594 Low 676 663 638 ...
Modulator PDF Instructions
VECOAX NETWORK COMPACT HDMI RF MODULATOR MANUAL User reference manual for the PVI VeCOAX Modulator. The guide focuses on error codes, product handling, assembly reference.
Comprehensive setup guide for the Power Acoustik EFM-100 Modulator. This documentation guides on hardware instructions, system parameters, user instructions, application scenarios.
Warranty 600-103 Rev C 600-103 Rev C Multiplex Technology, Inc. Warrants this products to be free from defects in materials and workmanship for a period of one year from the date of purchase or MTI will repair, or at its option, replace the defective product. Operational manual for the Channel Plus 5425 Modulator. It describes step-by-step testing procedures, device calibration, safety, basic operation.
RCA CRF907 Compact RF Modulator (CRF-907) Auto-Switching automatically detects the incoming video source. Allows connection of an audio/video component such as a DVD player, video game system, or camcorder. Specifications Video Accessories Projector Stands Official user manual for the Audiovox CRF907 Modulator. The document elaborates on device functions and configuration options, functional overview, setup instructions.