ADLINK Technology ND-6021 Operation & User’s Manual
File Specifications
| Brand: | ADLINK Technology |
| Category: | Control Unit |
| Model: | ND-6021 (Operation & User’s Manual), pr5WtUq9Me3L2 |
| File Info: | Adobe Acrobat PDF (DjVu) |
| File Size: | — |
| Pages: | 60 pages |
Download PDF
Download ADLINK Technology ND-6021 Manual (60 pages)Read Online:
Read the ADLINK Technology ND-6021 Operation & User’s Manual online using the built-in PDF viewer. This document explains how to operate the device, adjust settings and perform regular maintenance.
Key Pages of Document
Command Set 3-3
‘ !’ = 0x24
‘ 0’ = 0x30
‘ 1’ = 0x31
‘ 4’ = 0x34
‘ 6’ = 0x36
AC = ( 0x24 + 0x30 + 0x31 + 0x34 + 0x30 + 0x30 + 0x36 + 0x30
+ 0x30 ) MOD 0x100
Note : 1. There is no spacing between the command words and the
checksum characters.
2. Every command follows a
2-1 Initialization & Installation
ADLINK Technology ND-6021 2. Initialization & Installation 2. 1. Software Installation 1. If you have already installed “ NuDAM Administration” then skip other steps. 2. Backup your software diskette. 3. Insert “ NuDAM Administration” diskette into floppy drive A: 4. Change drive to A: 5. Installation command syntax INSTALL drive: drive na ...
3-24 Initialization & Installation
Read Leading Code Setting
@Description
Read command leading code setting and host watchdog status.
@Syntax
~(Addr)0
3-2 Initialization & Installation
ADLINK Technology ND-6021 Format of NuDAM Commands
(Leading Code)(Addr)(Command)[Data][Checksum]
Command Set 3-33
ADLINK Technology ND-6021 3. 20. Host is OK @Description When host watchdog timer is enable, host computer must send this command to every module before timeout otherwise “host watchdog timer enable” module‘ s output value will go to safety state output value. Timeout value and safety state output value is defined in 3.14. “ Set Host Watchdog Timer & Safety V ...
3-32 Initialization & Installation
ADLINK Technology ND-6021 (SafeC)
@Example
User command:
~063
Initialization & Installation 1-7
ADLINK Technology ND-6021 Pin Definitions of ND-6024 Pin # Signal Name Description 1 DI4 Digital input channel 4 2 DI3 Digital input channel 3 3 DI2 Digital input channel 2 4 DI1 Digital input channel 1 5 DI0 Digital input channel 0 6 Default* Initial state setting 7 (Y) DATA+ RS-485 series signal, positive 8 (G) DATA- RS-485 series signal, negative ...
3-30 Initialization & Installation
User command:
~062112800800800800
3-16 Initialization & Installation
ADLINK Technology ND-6021 3. 10. Analog Data Output
@Description
Send a value to analog output module at specified address. The data
format of the value can be engineering unit, percent, or hexdecimal
value, which is set by configuration setting command.
(ND-6024 only supports engineering format.)
@Syntax
#(Addr)(OutData)
2-3 Initialization & Installation
ADLINK Technology ND-6021 5. Use the NuDAM Administrating utility to configure the address ID, Baud rate and check-sum status of the module. Initialization Wiring Figure 2-1 Layout for Initialization the NuDAM module 2. 3. Install a New NuDAM to a Existing Network Equipments for Install a New Module • A existing NuDAM network • New NuDAM modules. ...
4-3 Data Format
ADLINK Technology ND-6021 •
If the output range is set as 4 to 20 mA
•
The desired analog output current is 10 mA
The data value should be : 037.50
Command Set 3-29
ADLINK Technology ND-6021 @Response
!(Addr)
ADLINK Technology ND-6021 user guide recommended for: HSL-DI32-UD, MPC-8164, SMARC LEC-PX30, cPCI-R6100, HSL-4XMO.
⚠️ Download Safety
The Control Unit Operation & user’s manual (60 pages) is completely safe to download (last scan date: 30/04/2026).
Control Unit: Frequently Requested PDF Instructions
-
Graco PR70 Series Dispenser Repair and parts manual
82 -
Seametrics PD10 Control Unit Instructions
4 -
Festo Pneumatic LFR-E S-B Series Control Unit Operating instructions manual
6 -
Jandy Jandy Control Unit Installation and operation manual
44 -
Wetelux 707331 Control Unit Instruction manual
15 -
SIM Tech SIMCom SIM6216C Control Unit Hardware design
64