Rae H2 Operating Instructions
Text of the manual
SINGLE CHANNEL LOOP DETECTOR
OPERATING INSTRUCTIONS
I
General
The Model H2 is a single channel detector with a solid state Detect Output and a
solid state Fail Output. Please verify source voltage before applying power.
The Model H2 will operate on voltages between 8 and 30 VDC with a maximum
current requirement of 45 mA.
II
Indicators and Controls
i
Power
iii DIP Switches
Switch
OFF
ON
Factory Default
1
Frequency
(See table in Frequency section)
OFF
2
ON
3
Fail-Safe
Fail-Secure
OFF
4
No Boost
Sensitivity Boost
OFF
5
Detect Output Delay
(See table in Output Delay section)
OFF
6
OFF
7
Detect Output Extension
(See table in Output Extension section)
OFF
8
OFF
Frequency (DIP Switches 1 and 2)
When loops are loc
Detect Output Delay (DIP Switches 5 and 6)
An Output Delay time of zero, two, five, or ten seconds can be programmed
using DIP switches 5 and 6. Output Delay time is the time before the Detect
Output activates following vehicle detection. If the Output Delay feature is
programmed to a value other than zero the Detect Output is "ON" only if a
vehicle is
Model H2 Operating Instructions
P/N 889-0805-00
4
IV Failed Loop Diagnostics
The Fail LED (red) provides loop failure information. The Fail LED is "OFF"
when the loop inductance value is within tolerance, and no past out of tolerance
conditions have existed. The Fail LED flashes at a one Hertz rate (50% duty
cycle) when the current loop inductance value is