PREFACE
D
D
This manual contains the information necessary for
the product to be installe
Ascon tecnologic TRH52 Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 2
3.
INSTALLATION WARNINGS
3.1
Mechanical mounting
The device, in an 80 x 80 mm plastic container, is designed
for wall mounting using screws passing through the slotted
holes on the case.
– Install the instrument as far as possible from electromagnet-
ic sources as motors, power relay, relays, electrovalves, etc.;
– Avoid to place the probe in places where are present cor-
rosive and polluting g
Ascon tecnologic TRH52 Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 3
5.
PROBLEMS AND MAINTENANCE
5.1
Measurements errors
Reading errors can occur if settling time is too short, or be
caused by steam, sprayed water, air drafts, direct exposure
to sunlight, or presence of condensation on the sensor.
To obtain accurate measurements the sensor should be left
to settle in the existing atmosphere for some time.
To reduce the possibility of condensation on the humid-
ity s
Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 4
7.3
Functional features
Humidity range: 0... 100%RH (4... 20 mA);
Humidity overall accuracy: ±3% between 20... 80%RH
(typical values at 25°C);
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
0
10
20
30
40
50
60
70
80
90
100
(%RH)
%RH
Relative Humidity measurement accuracy
Temperature range: -40... 60°C (4... 20 mA);
Temperature overall accuracy: 1%;
Response time in steady conditions (Signal: 63%;
%RH: