Text of Ascon tecnologic TRH52 Operating Instructions

Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 1

TRH52 ACTIVE HUMIDITY AND TEMPERATURE PROBE WITH 4... 20 mA OUTPUTS OPERATING INSTRUCTIONS Vr 01 (ENG) - 18/11 - cod.: ISTR-MTRH52ENG01 ASCON TECNOLOGIC S.r.l. Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY Tel.: +39 0381 69871 - Fax: +39 0381 698730 http:\\www.ascontecnologic.com [email protected] PREFACE D D This manual contains the information necessary for the product to be installe

Ascon tecnologic TRH52 Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 2

3. INSTALLATION WARNINGS 3.1 Mechanical mounting The device, in an 80 x 80 mm plastic container, is designed for wall mounting using screws passing through the slotted holes on the case. – Install the instrument as far as possible from electromagnet- ic sources as motors, power relay, relays, electrovalves, etc.; – Avoid to place the probe in places where are present cor- rosive and polluting g

Ascon tecnologic TRH52 Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 3

5. PROBLEMS AND MAINTENANCE 5.1 Measurements errors Reading errors can occur if settling time is too short, or be caused by steam, sprayed water, air drafts, direct exposure to sunlight, or presence of condensation on the sensor. To obtain accurate measurements the sensor should be left to settle in the existing atmosphere for some time. To reduce the possibility of condensation on the humid- ity s

Ascon Tecnologic - TRH52 - OPERATING INSTRUCTIONS - PAG. 4

7.3 Functional features Humidity range: 0... 100%RH (4... 20 mA); Humidity overall accuracy: ±3% between 20... 80%RH (typical values at 25°C); 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 0 10 20 30 40 50 60 70 80 90 100 (%RH) %RH Relative Humidity measurement accuracy Temperature range: -40... 60°C (4... 20 mA); Temperature overall accuracy: 1%; Response time in steady conditions (Signal: 63%; %RH: