Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 1
e33B
DIGITAL ELECTRONIC
TEMPERATURE CONTROLLER
WITH DEFROSTING FUNCTION
OPERATING INSTRUCTIONS
Vr 02 (ENG) - 18/10 - cod.: ISTR-Me33BENG02
ASCON TECNOLOGIC S.r.l.
Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY
Tel.: +39 0381 69871 - Fax: +39 0381 698730
http:\\www.ascontecnologic.com
[email protected]
PREFACE
D
D
This manual contains the information necessary for
the product to be instal
Ascon tecnologic e33B Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 2
temperature control device, the defroster, the evaporator
fans and a configurable auxiliary device (Light, Alarm, etc.).
The 3 inputs for temperature probes can be used for the
cell temperature control, to measure the evaporator tem-
perature and/or other auxiliary temperatures (e.g. products
temperature, condenser temperature, etc.).
The digital input, alternative to the Pr3 probe, can be config-
u
Ascon tecnologic e33B Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 3
2.2
Standard mode parameters programming
To access the instrument function parameters when pass-
word protection is disabled, press the keys
/ and
/
at the same time and keep them pressed for about 5 s, after
which the display shows the code that identifies the first pro-
grammable parameter. Press the
/
keys to display the
desired parameter, then, pressing the
/ key, the display
shows the param
Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 4
When the keyboard is locked, if any of the key is pressed,
the display showss Ln to indicate that the lock is active.
To unlock the keyboard it is enough to contemporaneously
press
/ +
/
keys and keep them pushed for 5 s, after
which the label LF appears on the display and all the key
functions will be available again.
2.7
Variables display
The display normally shows the variable set with paramete
Ascon tecnologic e33B Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 5
4.3
Electrical connections
Carry out the electrical wiring by connecting only one wire to
each terminal, according to the following diagram, checking
that the power supply is the same as that indicated on the
instrument and that the load current absorption is no higher
than the maximum electricity current permitted.
As the instrument is built-in equipment with permanent con-
nection inside housing,
Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 6
If iEt = oF the selection of Eco/Normal modes via the digital
input is disabled.
If itt = oF the time-out switching from Eco to Normal mode
is disabled.
Temp.
SPE
SP
rd
rEd
iEt (1)
iEt
time
Normal
Normal
eco
iTt (2)
Pr1
Switching to Economic mode is indicated by the label Eco.
In addition, the selection of the Eco mode is always com-
bined with the function of turning OFF the output configured
as L1
Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 7
5.4
Digital input configuration
The digital input function (available on terminal 12 or instead
of Pr3 input if ip3 = dg) is defined using the iFi parameter
and the action is delayed for the time programmed with pa-
rameter iti. The iFi parameter can be configured for the
following functions:
0
Digital input not active;
1
Cell door opening with NO contact: at input closure (and
after the iti) the i
Ascon tecnologic e33B Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 8
5.6
Temperature control
The instrument controls the temperature with an ON/OFF
action and operates on the outputs configured as ot and
HE depending on the PR1 probe measuring, the acive Set
Point/s SP1 (or SP2, SP3, SPE and SPH), the Hysteresis rd
(or rEd and/or rHd) and the function mode set with rHC.
Using rHC can be set the following functioning modes:
C
Cooling;
H
Heating.
SP
Temp.
rd
time
off
o
Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 9
eter Pod.
During the power ON delay phase, the display shows the
indication od alternated with the normal visualization.
All these functions are disabled if the relative parameters are
set to OFF (oF).
5.8
Defrost control
The defrost control acts on the outputs configured as ot and dF.
The type of defrost is set by the parameter ddt:
EL
With electrical heating (or By stopping compres-
sor): while de