Ascon tecnologic e34B Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 1

e34B DIGITAL ELECTRONIC TEMPERATURE CONTROLLER WITH DEFROSTING FUNCTION OPERATING INSTRUCTIONS 20/06 - code: ISTR_M_e34B_E_02_-- ASCON TECNOLOGIC S.r.l. Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY Tel.: +39 0381 69871 - Fax: +39 0381 698730 http:\\www.ascontecnologic.com [email protected] PREFACE D D This manual contains the information necessary for the product to be installed correc

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 2

The 4 outputs can be used to control the compressor or the temperature control device, the defroster, the evaporator fans and a configurable auxiliary device (Light, Alarm, etc.). The 3 inputs for temperature probes can be used for the cell temperature control, to measure the evaporator tem- perature and/or other auxiliary temperatures (e.g. products temperature, condenser temperature, etc.). The di

Ascon tecnologic e34B Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 3

-2.0 Press and hold for 1s Press and release (e.g. 4.0°) eco 10.0 (e.g. -5.0°) trb -5.0 (e.g. 4.0°) sp1 4.0 (e.g. 2.0°) sp2 2.0 (e.g. 0.0°) sp3 0.0 or Press and hold for 5s 2.2 Standard mode parameters programming To access the instrument function parameters when pass- word protection is disabled, press the keys / and / at the same time and keep them pressed for about 5 s, after which the disp

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 4

2.5 Reset parameters to default value The instrument allows the reset of the parameters to values programmed in factory as default To restore the default parameters value set value -48 at r.p password request. Therefore, to make the reset to the default parameters, enable the Password using the tPP parameter so that the r.p setting is requested, at this point insert -48 instead of the programmed ac

Ascon tecnologic e34B Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 5

4. INSTALLATION WARNINGS 4.1 Mechanical mounting The instrument, in case 78 x 35 mm, is designed for flush- in panel mounting. Make a 71 x 29 mm hole and insert the instrument, fixing it with the provided special brackets. In order to obtain the declared front protection degree, mount the gasket and use the screw type bracket (both optional). Avoid placing the instrument in environments with very h

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 6

5. FUNCTIONS 5.1 ON/Stand-by function Once powered the instrument can assume 2 different conditions: ON: Means that the controller uses the control functions. STAND-BY: Means that the controller uses no control function and the display is turned off except for the Stand-by LED. The transition between Standby and ON is equivalent to power ON the instrument providing the electrical power In case of po

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 7

5.3 Measure and display configuration With parameter iuP it is possible to select the tempera- ture engineering unit and the desired measure resolution (C0 = °C/1°; C1 = °C/0.1°; F0 = °F/1°; F1 = °F/0.1°). The instrument allows the measure calibration, which can be used to recalibrate the instrument according to applica- tion needs, the calibration is made by using parameters iC1 (input Pr1)

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 8

a contact that is NO in normal operation then closed during the alarm (see alarm memory); -t To control a silenceable alarm device through a con- tact that is NC in normal operation then opened during the alarm; -L Control an alarm that cannot be silenced through a contact that is NC in normal operation then opened during the alarm; -n To control an alarm with a memory function through a contact th

Ascon tecnologic e34B Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 9

The time protections described in the next paragraph (PP1/PP2/PP3) always work on the ot configured output. In the event of a probe error, it is possible to set the instrument so that the ot output continues working in cycles according to the times programmed with param- eter rt1 (activation time) and rt2 (deactivation time). If a Pr1 probe error occurs, the instrument activates the ot output for rt

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 10

times of the ot output (ot output activated). This mode is usually used in refrigeration systems with compres- sor stop defrosting. cS Defrost cycle at each compressor stop. The instrument starts a defrost cycle every time the ot output is deac- tivated, when the Set Point is reached or at the expira- tion of the interval set with ddi paramreter. If ddi = oF the defrost happens only at compressor