ABB TTF300 Operating Instruction
Text of ABB TTF300 Operating Instruction
ABB MEASUREMENT & ANALYTICS | OPERATING INSTRUCTION
TTF300
Field-mount temperature transmitter
Temperature transmitter for all
communications protocols.
Redundancy thanks to two inputs.
Measurement made easy
—
TTF300
Introduction
The TTF300 is available with the HART,
PROFIBUS PA and FOUNDATION Fieldbus
communication protocols.
The TTF300 has global approvals for explosion
protection up to Zone 0.
Safety-relevant applications up to SIL 3
(redundant)
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G
Table of contents
Change from one to two columns
1
Safety .......................................................................... 4
General information and instructions .................................. 4
Warnings .................................................................................... 4
Intended use .......................................................................
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G 3
10 Commissioning ........................................................ 39
General ..................................................................................... 39
Checks prior to commissioning .......................................... 39
Communication ...................................................................... 39
HART® Communication .............................
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G 1 Safety
General information and instructions
These instructions are an important part of the product and
must be retained for future reference.
Installation, commissioning, and maintenance of the product
may only be performed by trained specialist personnel who have
been authorized by the plant operator accordingly. The specialist
personnel must have read and understood the manual and m
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G 5
Intended use
This device is intended for the following uses:
•
To measure the temperature of fluid, pulpy or pasty
substances and gases or resistance/voltage values.
The device has been designed for use exclusively within the
technical limit values indicated on the name plate and in the data
sheets.
•
The maximum ambient temperature must not be exceeded.
•
The IP rating of the hous
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G Change from two to one column
2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
hange from one to two columns
Ex marking
Note
•
Further information on the approval of devices for use in
potentially explosive atmospheres can be found in the
explosion protection test certificates (at
www.abb.com/temperature).
•
Depending on the design, a specific marking in
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G 7
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
Model TTF300-H1H
IECEx certificate of conformity
IECEx PTB 09.0014X
Model TTF300-H1P and TTF300-H1F
IECEx certificate of conformity
IECEx PTB 11.0108X
Ex ia IIC T6...T1 Ga
Ex [ia IIC Ga] ib IIC T6...T1 Gb
Ex [ia IIIC Da] ib IIC T6...T1 Gb
IECEx dust explosion protection
Approved for use in Zone 21 and 22.
Model TTF300-J5H
IECEx
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G … 2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
Temperature data
Transmitter
ATEX / IECEx intrinsic safety, ATEX non-sparking
Temperature class
Permissible ambient temperature range
Device category
1 use
Device category
2 / 3 use
T6
−50 to 44 °C
(−58 to 111.2 °F)
−50 to 56 °C
(−58 to 132.8 °F)
T4 to T1
−50 to 60 °C
(−58 to 140.0 °F)
−5
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G 9
Type of protection flameproof (enclosure) Ex db IIC
Supply circuit
Maximum voltage
US = 30 V
Maximum current
Is = 32 mA, limited by the
upstream fuse
(rated fuse current 32 mA)
Measurement current circuit
Maximum voltage
UO = 6.5 V
Maximum current
IO = 17.8 mA
Maximum power
PO = 39 mW
Dust explosion protection type of protection
Ex tb IIIC T135°C Db, Ex tc IIIC T135°C Dc
Non-intrinsica
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G … 2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
Installation instructions
ATEX / IECEx
The installation, commissioning, maintenance and repair of
devices in potentially explosive atmospheres must only be
carried out by appropriately trained personnel. Works may be
carried out only by persons, whose training has included
instructions on different types of
ABB Transmitter Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated | For Device |
|---|---|---|---|---|---|---|---|
TTF200 |
ABB Transmitter Operating instruction (File: PDF, 10-07-2026) |
36 | 901 | 181 | 10-07-2026 | view all | |
Endura ACA592 |
#XM5Y76: Endura ACA592 Transmitter Operating instructions manual |
94 | 354 | 71 | 30-05-2026 | view all | |
4680 |
PDF User Manual (@16MIPC), ABB 4680 Transmitter (23-08-2026) |
20 | 899 | 207 | 23-08-2026 | view all | |
4623 |
PDF User Guide (@7YNN6H), ABB 4623 Transmitter (25-04-2026) |
32 | 1010 | 213 | 25-04-2026 | view all | |
LMT100 |
PDF User Guide (@W2PBFZ), ABB LMT100 Transmitter (16-04-2026) |
84 | 683 | 130 | 16-04-2026 | view all | |
Navigator 540 |
ABB Transmitter Instruction manual (File: PDF, 12-07-2026) |
54 | 1270 | 204 | 12-07-2026 | view all | |
TTF350 |
User Guide: ABB TTF350 (L24CJB, Upd.09-06-2026) |
304 | 1437 | 216 | 09-06-2026 | view all | |
LST300 Series |
ABB LST300 Series User Guide (Operating instruction), @88T6UN |
60 | 96 | 22 | 22-08-2026 | view all | |
LWT300 series |
#7YZWA9: LWT300 series Transmitter Operation & user’s manual |
92 | 1148 | 265 | 10-04-2026 | view all |